Bulletin G-269
August, 2018
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email:
Web Site: http://www.leonardvalve.com
INSTALLATION, ADJUSTMENT, SERVICE
MODEL 269-LF, 369-LF
THERMOSTATIC / POINT OF USE MIXING VALVES
369-LF (3/4” NPT)
ASSE 1069 CERTIFIED
WARNING!!
WATER TEMPERATURES IN EXCESS OF 110°F (43°C) MAY CAUSE SCALDING, SEVERE
INJURY, OR DEATH!!
Maximum Operating Pressure: 125 PSI (860 KPA)
IMPORTANT!
These thermostatic water mixing valves can be adjusted to deliver water at temperatures
exceeding 110°F (43°C). After installation, the installer must check the outlet water temperature and adjust
the temperature setting to ensure delivery of a safe water temperature not exceeding 110°F (43°C). See
“Temperature Adjustment” next page
.
1. Valve should be installed where it can be easily cleaned,
adjusted or repaired.
2. Inlets are furnished with NPT connections. When
soldering close to this unit,
DO NOT OVERHEAT,
internal components may become damaged.
3. Leonard recommends that unions and shutoffs are
installed on the inlets and outlet.
4. Use solder or pipe cement sparingly. Supply pipes should
be flushed before the valve is connected. Flush outlet
pipe and valve as soon as it is connected.
269-LF & 369-LF WARNING:
When using flex hoses be careful, swivel connectors may damage inlet checks and / or
element on outlet on 269-LF and 369-LF models. Coupling fittings may be needed if swivel
connectors have a brass protruding tube or any protrusion that may damage the valve.
269-LF (1/2” NPT)
ASSE 1069 CERTIFIED
ECO-MIX
™
These products are certified to meet Low Lead requirements of
wetted surface area containing less than 0.25% lead by weight
WARNING:
This
product
can
expose
you
to
chemicals including lead, which is known to the State
of California to cause cancer. For more information, go
to
!