Electrical installation
Mains connection
NOTICE
Incorrect arrangement in the control cabinet.
Malfunction of the device.
▶
When installing the devices into a control cabinet with a spatial distance, separate the devices that
generate high voltage and electromagnetic interference from extra-low voltage devices such as the IoT
Gateway x500.
NOTICE
Unstable LAN connection due to wrong cable types.The LAN connection might be interrupted.
▶
Only use cables of CAT5-S/FTP type or better.
SELV/PELV
(LPS)
L1
N
PE
L1 N
0V
+24
~
=
F
(max. 4 A)
PE
IoT Gateway x500
24E
DI1
GND
Mains connection
Connection
X50
GND
24E
DI1
Digital control signal
+ -
+ -
12-24 V DC
Connection type
Connector
Weidmüller BL
5.08/04/180 SN BK BX
Min. cable cross-section
mm²
0.75 (AWG18)
Max. cable cross-section
mm²
1.5 (AWG14)
Stripping length
mm
7
Tightening torque
Nm
0.4
Digital input DI1
Voltage range
0 - 29 V DC
Current range (ON)
2 - 5 mA
Voltage range (LOW)
0 - 3 V DC
Voltage range (HIGH)
7 - 29 V DC
By default, the digital input is not configured and does not need to be wired. The digital input provides the
opportunity to locally activate/deactivate the VPN connection of the IoT Gateway x500 (ON/OFF).
Electrical installation
Mains connection
27