9.2
Diagnostic data
• Pending diagnostic data are signalled from the controlled node to the managing node by means
of an emergency message.
• Code
serves to suppress sending emergency messages to the managing node. You can
select which type of error is to be suppressed.
• Errors and warnings are sent to the managing node as extended diagnostic messages.
• The diagnostic data are visible via the PLC Engineering software.
Bytes
Meaning
Value [hex]
1 ... 6
Diagnostic block header
0x0010 001C 0100
7 ... 8
Alarm type
0x0001 (diagnosis)
9 ... 12
API (Application Programming Interface)
0x0000 0000
13, 14
Slot number
0x0001 / 0x0002
15, 16
Subslot number
0x0001
17 ... 20
Module ID
ID according to module
21 ... 24
Submodule number
ID according to module
25, 26
Alarm specification
0xB000
27, 28
User structure ID
0x0001
29 ... 32
Error code
Reference manual/online help for the Inverter Drive 8400 motec