15
Parameter reference
15.2
Parameter list
892
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00425
C00434
C00423/7
0.000 s
DO3 ON delay
C00423/8
0.000 s
DO3 OFF delay
C00423/9
0.000 s
DO "High Current" ON delay
C00423/10
0.000 s
DO "High Current" OFF delay
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00423 | DOx: Delay times
Data type: UNSIGNED_16
Index: 24152
d
= 5E58
h
Parameter | Name:
C00425 | Encoder scanning time
Data type: UNSIGNED_8
Index: 24150
d
= 5E56
h
From version 02.00.00
Encoder sample time for the digital input terminals when configured as frequency inputs
Using DI1(6) and DI2(7) as frequency inputs
Selection list
0 1 ms
1 2 ms
2 5 ms
3 10 ms
4 20 ms
5 50 ms
6 100 ms
7 200 ms
8 500 ms
9 1000 ms
Subcodes
Lenze setting
Info
C00425/1
3: 10 ms
FreqIn12: Encoder scanning time
• Only active with edge-counting procedure
= 3).
C00425/2
3: 10 ms
FreqIn67: Encoder scanning time
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00434 | OxU/I: Gain
Data type: INTEGER_16
Index: 24141
d
= 5E4D
h
Gain of the analog outputs
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00434/1
100.00 %
O1U: Gain
C00434/2
100.00 %
O2U: Gain
C00434/3
100.00 %
O1I: Gain
C00434/4
100.00 %
O2I: Gain
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100