9
Diagnostics & error management
9.9
Error messages of the operating system
668
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CE1: CAN RPDO1 [xx.0135.00001]
CE2: CAN RPDO2 [xx.0135.00002]
CE3: CAN RPDO3 [xx.0135.00003]
CE5: CAN RPDO4 [xx.0135.00004]
CI01: Module missing/incompatible [xx.0140.00013]
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
: Time monitoring for RPDO1 has been
triggered.
• RPDO1 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
: Time monitoring for RPDO2 has been
triggered.
• RPDO2 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
: Time monitoring for RPDO3 has been
triggered.
• RPDO3 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
: Time monitoring for RPDO4 has been
triggered.
• RPDO4 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The optional communication module has been removed
or there is a connection problem or incompatibility with
the standard device.
• Check connection between the communication
module and standard device.
• Check if the module is plugged in correctly.
• In case of an incompatibility, either the module or the
software of the standard device is out of date. In this
case, please contact Lenze.