Diagnostics & error management
9.9
Error messages of the operating system
664
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oC14: Direct-axis current controller limitation [xx.0123.00096]
oC15: Cross current controller limitation [xx.0123.00097]
oC16: Torque controller limitation [xx.0123.00098]
FC03: Field controller limitation [xx.0123.00099]
oC6: I2xt overload - motor [xx.0123.00105]
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Direct-axis current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Cross current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
• Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Actuator limitation according to speed controller.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
• Observe load requirements.
• Correct dimensioning or reduce setpoint from the
field weakening range if necessary.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Thermal overload of the motor.
Only self-ventilated motors can be monitored using the
I2xt function.
• Check whether is it a self-ventilated motor. If not, set
to "0: No Reaction".
• Observe load requirements.
• Correct dimensioning if necessary.
• For VFCplus control type: Check Vmin boost (