8400 BaseLine D | Software Manual
Drive control (DCTRL)
Controller commands
54
L
Firmware 03.00 - DMS EN 5.0 - 07/2009
4.2
Controller commands
4.2.1
General information
The commands in the subcodes of code
enable
the direct control of the controller. This comprises e.g. the following subcodes:
– 16, enable controller (CINH)
"0" = controller is inhibited by software, "1" = enable via external switch
– 17, quick stop (QSP)
"0" = activate QSP via external switch, "1" = activate QSP via software
the management of parameter sets and diagnosis services:
– Parameter set management, e.g. subcode 7, load parameter set 1
– Logbook management
– Error management
– Identification, e.g. motor parameters, inverter characteristic
Regarding the execution of the commands, there are two different groups:
1. Commands with immediate control effect (e.g. quick stop). These commands contain
the static status information ON or OFF.
2. Commands with a pure command nature
The subcodes of the second group do not execute the action immediately. However, after
the command is written, they deliver dynamic status information and thus demonstrate
the command progress:
After the activation value (1: On / start) is written, it can be read until the following state
is reported:
"2": Busy and then > (0: Off / ready)
If a problem occurs during the execution of a device command, the returned information is
"4": Action cancelled
or
"5": No access