Firmware 03.00 - DMS EN 5.0 - 07/2009
L
177
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00007
C00007
C00010
Parameter | Name:
C00007 | Select control mode
Data type: UNSIGNED_16
Index: 24568
d
= 5FF8
h
Configuration of the digital inputs
Selection list
(Lenze setting printed in bold)
Info
0 Wiring has changed
This display appears if the defined configuration has
been reparameterised via the connection parameters.
10 Terminal 0
The technology application is controlled using the digital
input terminals of the controller.
• DI1 = JOG 1/3
• DI2 = JOG 2/3
• DI3 = DCB
• DI4 = R/L
12 Terminal 2
The technology application is controlled using the digital
input terminals of the controller.
• DI1 = JOG 1/3
• DI2 = JOG 2/3
• DI3 = QSP
• DI4 = R/L
14 Terminal 11
The technology application is controlled using the digital
input terminals of the controller.
• DI1 = R/L
• DI2 = DCB
• DI3 = MPotUp
• DI4 = MPotDown
16 Terminal 16
The technology application is controlled using the digital
input terminals of the controller.
• DI1 = JOG 1/3
• DI2 = JOG 2/3
• DI3 = R/QSP
• DI4 = L/QSP
20 Keypad
The technology application is controlled via the keypad:
: Setpoint selections
: Device commands
: Status of last device command
Increase speed
Reduce speed
21 PC
The technology application is controlled using the "Free
parameters" of the controller (PC control).
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00010 | Minimum analog setpoint
Data type: INTEGER_16
Index: 24565
d
= 5FF5
h
From version 03.00.00
Setting range
(min. value | unit | max. value)
0.0
%
100.0
Subcodes
Lenze setting
Info
C00010/1
0.0 %
Min. analog setpoint
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100