Motor connection
To connect the motor correctly, you must follow:
•
The notes in the terminal box of the motor.
•
The notes in the configuration document of the motor.
•
The technical data on the motor nameplate.
Second ground connection on the motor
According to standard EN 61800-5-1, an additional PE conductor is required if the leakage
current is greater than 3.5 mA for AC current or greater than 10 mA for DC current.
Scope of delivery when selecting a 2nd grounding point:
•
Toothed lock washer
•
Washer
•
Fixing screw
An additional grounding cable is not included in the scope of delivery.
The dimensioning of the grounding is done by the customer.
Electrical installation
Motor connection
36