19.10
Safely Limited Increment (SLI)
With this function, a maximum permissible position change [incr] can be set.
Within the position window, the increments parameterised can be traversed in positive and
negative directions. There is no time limit for executing this function. If the increment limits
parameterised are exceeded, an error stop is initiated.
WARNING!
A safety-rated encoder system must be used.
Without an encoder, this safety function cannot be used.
▶
Apply a safety-rated encoder system to use this function.
Functional description
Fig. 75: SLI function
A
Triggering of the function
B
Monitoring active
C
Error status
If the drive exceeds the increment parameterised in
(normal operation) or
(special operation), the stop function set in
is excecuted.
Activation of the function
The function cannot be activated if the drive is in
.
The function can be activated during operation.
The function is activated
•
via the safety bus. For this purpose, a data telegram is sent to the inverter,
see safety bus.
•
as a function of the operating mode changeover (OMS) by activation of the special opera-
tion,
.
•
by the OFF state on a safe input. For the OFF state, a function is parameterised.
See safe
inputs.
Safety functions
Safely Limited Increment (SLI)
418
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......