Initial switch-on and functional test
Target: Get the motor connected to the inverter to rotate in best time.
Necessary conditions:
•
The power rating of the motor connected is appropriate for the inverter.
•
The parameter settings correspond to the delivery status (Lenze setting).
1. Preparation
1. Wire the power connections.
2. Wire digital inputs X3/DI1 (start/stop), X3/DI3 (reversal) and X3/DI4 (frequency preset 20 Hz).
3. Do not wire terminal X3/AI1 (analog setpoint selection) or set to GND.
2. Switch on mains and check readiness for operation
1. Switch on mains voltage.
2. Observe LED status displays "RDY" and "ERR" on the front of the inverter:
a) When the blue LED "RDY" blinks and the red LED "ERR" is off, the inverter is ready for operation. The
controller is inhibited.
You can start the drive.
b) If the red LED "ERR" remains lit, a fault is active.
Eliminate the fault before you carry on with the functional test.
Carry out functional test
1. Start drive
1. Start inverter: X3/DI1 = HIGH.
2. Activate frequency preset 1 (20 Hz) as speed setpoint: X3/DI4 = HIGH.
The drive rotates with 20 Hz.
3. Optional: Activate reversal
a) X3/DI3 = HIGH.
The drive rotates at 20 Hz in the opposite direction.
b) Deactivate reversal again: X3/DI3 = LOW.
Speed characteristic (example)
2. Stop drive
1. Deactivate frequency preset 1 again: X3/DI4 = LOW.
2. Stop inverter again: X3/DI1 = LOW.
The functional test has been completed.
Control with Keypad
The "Keypad Full Control" control mode can be activated with the keypad key “CTRL”. Both the control and
the setpoint selection are then made via the keypad. This special control mode can be, for instance, used
during the commissioning phase if external control and setpoint sources are not ready to use yet.
If the local keypad control is active, "LOC" is displayed in the lower status row of the keypad and the red LED
flashed.
•
After the "CTRL" key has been pressed, the activation of the control mode must be confirmed with the
key. (The key serves to cancel the action.)
•
When the control mode is changed over, the motor is first stopped and the "Forward" direction of
rotation is set. Then, the motor can be started and stopped via the keypad.