25
Troubleshooting
Operating instructions I510-Cabinet
8.3 Error codes
Error code
Description
Classification
Remedy
Blocking time
[s]
Reset possible
2250
CiA: Continuous overcurrent (inside the device) Error
• Check motor and wiring for short circuits.
• Check brake resistor and wiring.
• Check motor switching.
• Check motor data settings.
5
Yes
2320
Short circuit or earth leakage on the motor side Error
• Check motor cable.
• Check length of motor cable.
• Use shorter or lower-capacitance motor cable.
5
Yes
2340
CiA: Short circuit (inside the device)
Error
• Check motor cable for short circuit.
5
Yes
2350
CiA: i²*t overload (thermal state)
Error
• Check drive dimensions.
• Check machine/driven mechanics for excessive load.
• Check motor data settings.
• Reduce values for slip compensation (
P315.01
,
P315.02
) and oscillation damping (
P318.01
,
P318.02
).
5
Yes
2382
Error: Device utilisation (Ixt) too high
Error
• Check drive dimensions.
• Reduce maximum overload current of the inverter (
P324.00
).
• In case of high mass inertias, reduce maximum overload current of the inverter (
P324.00
) to 150 %.
3
Yes
2383
Warning: Device utilisation (Ixt) too high
Warning
• Check drive dimensions.
0
Yes
3120
Mains phase fault
Error
• Check mains connection wiring.
• Check fuses.
0
Yes
3210
DC bus overvoltage
Error
• Reduce dynamic performance of the load profile.
• Check mains voltage.
• Check settings for brake energy management.
• Connect brake resistor to the power unit and activate the integrated brake chopper. (
P706.01
= 0: brake
resistance).
0
Yes
3211
Warning: DC bus overvoltage
Warning
• Reduce dynamic performance of the load profile.
• Check mains voltage.
• Check settings for brake energy management.
• Connect brake resistor to the power unit and activate the integrated brake chopper. (
P706.01
= 0: brake
resistance).
0
Yes
3220
DC bus undervoltage
Trouble
• Check mains voltage.
• Check fuses.
• Check DC-bus voltage (
P105.00
).
• Check mains settings.
0
Yes
3221
Warning: DC bus undervoltage
Warning
• Check mains voltage.
• Check fuses.
• Check DC bus voltage.
• Check mains settings.
0
Yes
3222
DC-bus voltage too low for switch-on
Warning
• Check mains voltage.
• Check fuses.
• Check mains settings.
0
Yes