Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
366
7
EtherCAT communication
7.9
Parameterising the time stamp
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.9
Parameterising the time stamp
7.9.1
2 digital inputs with time stamp function - EPM-S207
Parameter data
7.9.2
2 digital outputs with time stamp function - EPM-S310
Parameter data
Subindex Name
Description/value
Lenze
01
Length - process
image input data
Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.
0x14 or
0x3C(fix)
02
Length - process
image output data
Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.
0x00 (fix)
03
Input delay DI 0
0x00 = 1
s
0x02 = 3
s
0x04 = 10
s
0x07 = 86
s
0x09 = 342
s
0x0C = 273
s
No other values are permissible.
0x02
04
Input delay DI 1
0x02
05
Edge 0-1 at DI x
Time stamp entry on rising edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: reserved
0x00
06
Edge 1-0 on DI x
Time stamp entry on falling edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: reserved
0x00
Subindex Name
Description/value
Lenze
01
Length - process
image input data
Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.
0x14 or
0x3C(fix)
02
Length - process
image output data
Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.