Commissioning
The commissioning described here applies to the wiring example "Local 2-wire control" shown on the
previous page.
Setting parameters
1. Load default settings: P700.01 = 1
2. Set the following parameters:
Display code
Name
Setting
P400.02
Start
Digital input 1 [11]
P400.04
Error reset
Not connected [0]
P400.08
Run forward
Digital input 2 [12]
P400.09
Run reverse
Digital input 3 [13]
P400.13
Reverse rotating direction
Not connected [0]
P400.18
Setpoint: Preset B0
Not connected [0]
P400.19
Setpoint: Preset B1
Not connected [0]
P210.00
Min. frequency
Application-specific
(see the following diagram)
P211.00
Max. frequency
P220.00
Acceleration 1
P221.00
Deceleration 1
P430.02
AI1 freq @ min
P430.03
AI1 freq @ max
P430.02
P211.00
P430.03
P430.02
P210.00
P220.00
P221.00
f
t
AI1
Save parameter settings
P700.03 = 1 or press key
on the keypad for longer than 3 s.
Fault reset
A fault can be reset by switching off and on the main power supply or using the keypad keyboard:
1. Press button
.
2. Press button
.