Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
93
Parameter reference
Parameters of the Communication Unit
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13002
C13003
C13005
Parameter | Name:
C13002 | Gateway Address
Data type: UNSIGNED_8
Index: 11573 = 0x2D35
Setting of the gateway address
Setting the IP configuration of the Inverter Drive 8400 motec (
Setting range
(min. value | unit | max. value)
0
255
Subcodes
Lenze setting
Info
C13002/1
0
Gateway address (most significant byte)
C13002/2
0
Gateway address
C13002/3
0
Gateway address
C13002/4
0
Gateway address (least significant byte)
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13003 | MAC ID
Data type: OCTET_STRING
Index: 11572 = 0x2D34
Display of the MAC-ID
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13005 | IP Config Control
Data type: UNSIGNED_8
Index: 11570 = 0x2D32
Selection how the IP configuration is to be effected.
(Instance attribute 3 (Configuration Control) in the
TCP/IP Interface Object (245 / 0xF5) (
Setting the IP configuration of the Inverter Drive 8400 motec (
Selection list
(Lenze setting printed in bold)
Info
0 Use stored IP
The IP configuration currently saved in the
Communication Unit is used.
1 Use BOOTP
The IP configuration is assigned by the scanner using
BOOTP.
2 Use DHCP
The IP configuration is assigned by the scanner using
DHCP.
The assignment of a gateway address which is not in the
same subnetwork than the IP address, is rejected.
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT