Lenze EPM-H502 Скачать руководство пользователя страница 56

Technical data

General data and operating conditions

2

 56

EDBPM−H502  DE/EN/FR  5.1

2

Technical data

2.1

General data and operating conditions

 

  

General data

Conformity and approval

Conformity

CE

2004/108/EC

EMC Directive

Approval

UL

cULus

Underwriter Laboratories Inc. (File no. E189179)

Protection of persons and equipment

Enclosure

IP65 (front)

EMC

Applied standards for
limit values

EN 61000−6−4
(2007)

Noise emission. Restriction of use: Protection
requirements are not ensured in residential areas.

EN 61000−6−2
(2005)

Noise immunity. Restriction of use: Protection
requirements are not ensured in residential areas.

Operating conditions

Ambient conditions

Climate

Storage

−20 ... +60 °C

Transport

−20 ... +60 °C

Operation

0 ... +50 °C

Humidity

<85 %, without condensation

Mounting conditions

Weight

0.5 kg

Содержание EPM-H502

Страница 1: ...Betriebsanleitung EDBPM H502 O Ä Oä HMI EPM H502 Bedieneinheit Operating unit Unité de commande Operating Instructions Instructions de mise en service ...

Страница 2: ...achten Sie die enthaltenen Sicherheitshinweise Please read these instructions before you start working Follow the enclosed safety instructions Veuillez lire attentivement cette documentation avant toute action Les consignes de sécurité doivent impérativement être respectées ...

Страница 3: ...FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C 1 2 3 4 ASP8 N C CAN Shield CAN V 1 2 3 4 5 1 0 2 h505_011 ...

Страница 4: ... H502 DE EN FR 5 1 Legende zur Übersicht Pos Beschreibung Funktion Klemmenleiste 4 polig DC Spannungsversorgung 24 V Minidin Buchse 8 polig Serieller Port ASP für PC oder SPS Klemmenleiste 5 polig Systembus CAN ...

Страница 5: ... 5 EDBPM H502 DE EN FR 5 1 Diese Dokumentation ist gültig für die Bedieneinheit EPM H502 ab der Typenschildbezeichnung Typ EPM H502 1A 10 Produktreihe EPM Bedieneinheit Hardwarestand Softwarestand ...

Страница 6: ...009 TD23 Neuauflage wegen Neuorganisation des Unterneh mens 13251833 3 0 05 2008 TD23 Firmierung gändert in Lenze Digitec Controls GmbH 00470641 2 0 07 2003 TD23 Komplette Überarbeitung zur Serie 00466870 1 0 03 2003 TD23 Erstauflage zum Feldtest 0Abb 0Tab 0 Tipp Dokumentationen und Software Updates zu weiteren Lenze Produkten finden Sie im Internet im Bereich Services Downloads unter http www Len...

Страница 7: ...uen 20 4 ElektrischeInstallation 22 4 1 Versorgungsspannung anschließen 22 4 2 Systembus CAN verdrahten 23 5 Inbetriebnahme 25 5 1 Erstes Einschalten 25 5 2 Projekt in die Bedieneinheit übertragen 26 5 2 1 Bedieneinheit und PC verbinden 26 5 2 2 Projekt Download 27 5 2 3 Verbindung zum PC entfernen 29 5 3 Statusmeldungen der Bedieneinheit 30 5 4 Datum Uhrzeit und Kontrast einstellen 31 6 Bedienung...

Страница 8: ...Inhalt i 8 EDBPM H502 DE EN FR 5 1 8 Wartung 42 9 Anhang 43 9 1 Chemikalienbeständigkeit 43 9 2 Stichwortverzeichnis 45 ...

Страница 9: ... und Hinweise beachten ƒ Die Betriebsanleitung muss stets komplett und in einwandfrei lesbarem Zustand sein 1 2 Verwendete Begriffe Begriff Im folgenden Text verwendet für Antriebsregler Lenze Frequenzumrichter 8200 vector und 9300 vector Lenze Servo Umrichter 9300 und 9400 HMI Human Machine Interface 1 3 Lieferumfang Lieferumfang Wichtig l 1 Bedieneinheit EPM H502 l 1 Betriebsanleitung l 4 Befest...

Страница 10: ...eichnet die Art und die Schwere der Gefahr Hinweistext beschreibt die Gefahr und gibt Hinweise wie sie vermieden werden kann Piktogramm und Signalwort Bedeutung Gefahr Gefahr von Personenschäden durch gefährliche elektri sche Spannung Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Gefa...

Страница 11: ...rumfang 1 11 EDBPM H502 DE EN FR 5 1 Anwendungshinweise Piktogramm und Signalwort Bedeutung Hinweis Wichtiger Hinweis für die störungsfreie Funktion Tipp Nützlicher Tipp für die einfache Handhabung Verweis auf andere Dokumentation ...

Страница 12: ...d Geräteschutz Schutzart IP65 frontseitig EMV Angewandte Normen zu Grenzwerten EN 61000 6 4 2007 Störaussendung Nutzungsbeschränkung Die Einhal tung der Schutzanforderungen in Wohngebieten ist nicht gewährleistet EN 61000 6 2 2005 Störfestigkeit Nutzungsbeschränkung Die Einhal tung der Schutzanforderungen in Wohngebieten ist nicht gewährleistet Einsatzbedingungen Umgebungsbedingungen Klimatisch La...

Страница 13: ... 16 Pixel 9 1 11 7 mm Text 24 32 Pixel Fonts programmierbar Kontrasteinstellung Software Hintergrundbeleuchtung LED Elektrischer An schluss DC Spannungsversorgung 24 VDC 18 32 VDC Leistungsaufnahme 10 W bei 24 VDC Absicherung Feinsicherung Æ5 20 mm 800 mA F Netzwerk Systembus CAN Protokoll Systembus CAN Netzwerk Topologie Linie beidseitig abgeschlossen mit 120 W Systembus Teilnehmer Master oder Sl...

Страница 14: ...armpuffer Anzahl 256 Automatische Operationen Anzahl 32 Backup Wiederherstellen Funktion vorhanden Balkengrafik Funktion vorhanden Befehle Alarmregister drucken Funktion vorhanden Alarmregister im Flash sichern Anzeigen Alarmregister Bedienseite Blattvorschub auf dem Drucker Die generelle Seitennummer auf Null setzen Hardcopy Hilfe der Seite Nächste Seite Passwort ändern Passwort Login Passwort Lo...

Страница 15: ...Vorangehende Seite Bit Passwort Bit 8 Bitmap Bildverzeichnis Funktion vorhanden Bogen Funktion vorhanden Datenfeld Funktion vorhanden Der Rezeptstruktur zugeordnete System Variablen Funktion vorhanden Direktbefehl mit Wert Struktur ABZIEHEN Funktion vorhanden EINGEBEN ODER UND XOR ZUFÜGEN Druck Funktion vorhanden Druckseiten Total Felder pro Seite Anzahl 64 128 Dynamische Bitmaps mit Bitgruppen St...

Страница 16: ...2048 Kopf Fußzeilen Total Felder pro Kopf Fußzeile 64 128 Kreise Funktion vorhanden Linien Funktion vorhanden Makros Total Befehl Makro Anzahl 1024 16 Meldungens Hilfen Anzahl 256 Meldungsfeld Funktion vorhanden Multilinguale Texte Anzahl Sprachen 4 Passwort Ebenen Anzahl 10 Programmierbare Fonts Funktion vorhanden Projektbilder Funktion vorhanden Rechtecke Funktion vorhanden Reporte Anzahl 32 Rez...

Страница 17: ...ld Anzahl 24 Variablen Grenzwerte und lineare Kor rektur Variablen Anzahl je Seite 32 Bewegungsvariablen be wegliches symbolisches Feld Schwellenvariablen Numerische Gleitpunkt Va riablen Numerische Variablen DEC HEX BIN BCD String Variablen ASCII Wochentagsfeld Funktion vorhanden 1 von der Projektgröße begrenzter Richtwert ...

Страница 18: ...ung 2 18 EDBPM H502 DE EN FR 5 1 2 2 2 Schnittstellenbeschreibung 1 2 3 4 5 6 7 8 h310_010 Abb 2 1 ASP8 Minidin 8pol Buchse Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 n c 4 RTS RS232 OUT 5 CTS RS232 IN 6 n c 7 Signal GND 8 5 VCC reserved n c Nicht angeschlossen ...

Страница 19: ... 2 19 EDBPM H502 DE EN FR 5 1 2 3 Abmessungen a d e c f c b h502_001 Abb 2 2 Abmessungen a mm b mm c mm d mm e mm f mm 166 0 100 0 32 0 4 0 39 6 102 0 2 4 Einbauausschnitt a b h502_02 Abb 2 3 Einbauausschnitt a mm b mm 157 0 91 0 ...

Страница 20: ...den Einbauausschnitt entnehmen Sie den technischen Daten 19 So befestigen Sie die Bedieneinheit 0 1 h502_003 1 Bedieneinheit mit Dichtung in den Einbauausschnitt schieben FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 2 2 2 2 N C CAN Shield CAN V 1 2 3 4 5 h502_004 2 Befestigungsschellen in die Öffnungsschlitze der Bedieneinheit schieben ...

Страница 21: ...lation Bedieneinheit einbauen 3 21 EDBPM H502 DE EN FR 5 1 3 3 2 2 3 3 FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 N C CAN Shield CAN V 1 2 3 4 5 h502_005 3 Schrauben gegen die Einbautafel drehen und festziehen ...

Страница 22: ...ƒ Bedieneinheit nur im spannungslosen Zustand verdrahten 4 1 Versorgungsspannung anschließen FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C PE N L1 18 32VDC 1 2 3 4 ASP8 N C CAN Shield CAN V 1 2 3 4 5 h502_006 Abb 4 1 Anschluss der Versorgungsspannung Klemmenbelegung Klemme Bezeichnung Erläuterung 1 DC 24 V Versorgungsspannung DC 18 V 32 V 2 DC 0 V GND Versorgungsspannung Bezugspotential 3 n c Nicht ...

Страница 23: ...EDBPM H502 DE EN FR 5 1 4 2 Systembus CAN verdrahten Prinzipieller Aufbau Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H315 A1 h315_004 Abb 4 2 Verdrahtung des Systembus CAN A1 Busteilnehmer 1 A2 Busteilnehmer 2 An Busteilnehmer n ...

Страница 24: ... Teilnehmer an Klemme Bezeichnung Erläuterung 1 V GND Bezugspotential 2 CAN LO Systembus LOW Datenleitung 3 Shield Schirm des Systembus Kabels auflegen 4 CAN HI Systembus HIGH Datenleitung 5 n c Nicht angeschlossen Folgen Sie bei der Verwendung des Übertragungskabels unseren Empfehlun gen Spezifikation des Übertragungskabels Gesamtlänge 300 m 1000 m Kabeltyp LIYCY 2 x 2 x 0 5 mm2 paarverseilt mit ...

Страница 25: ...halten Für die Inbetriebnahme ist eine vollständige Verdrahtung des Systembus not wendig ÜberprüfenSie vor dem Einschalten der Versorgungsspannung ƒ die gesamte Verdrahtung auf Vollständigkeit und Kurzschluss ƒ ob das Bussystem beim physikalisch ersten und letzten Busteilnehmer abgeschlossen ist ...

Страница 26: ...zwischen PC und Bedieneinheit nur bei ausgeschalteten Geräten herstellen l HMI Designer FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C 1 2 3 4 ASP8 1 2 0 N C CAN Shield CAN V 1 2 3 4 5 h502_007 Abb 5 1 Bedieneinheit und PC verbinden 1 ProgrammieradapterEPZ H111 auf die ASP8 Schnittstelle stecken 2 Downloadkabel EPZ H110 mit Programmieradapter EPZ H111 verbinden 3 Downloadkabel EPZ H110 auf COM1 oder ...

Страница 27: ...wählen ob mit dem Laden des Projekts gleichzeitig die Firmware aktualisiert werden soll Die Firmware muss immer beim ersten Download eines Projekts in die Bedieneinheit bzw nach einem Update des Projektierungstool HMI Designer aktualisiert werden Tipp Beispiel Projekte für die Bedieneinheit finden Sie im Projektierungstool HMI Designer unter Datei Öffnen Samples ...

Страница 28: ... die Systemseite anwählen Erst das Display in einer beliebigen Ecke oder kurz berühren Hinweis Diese Ecke darf kein anwählbares Feld enthalten Anschließend sofort die diagonal gegenüberliegende Ecke kurz berühren Die Systemseite erscheint 4 Das Feld TRANS PAGE berühren Die Transfer Page erscheint Wenn WAITING FOR DOWNLOAD FROM ASP angezeigt wird ist die Bedieneinheit bereit für den Datenempfang vo...

Страница 29: ...3 Verbindungzum PC entfernen So entfernen Sie die Verbindung zum PC 1 PC ausschalten 2 Versorgungsspannung für Bedieneinheit abschalten 3 Programmieradapter EPZ H111 an der Bedieneinheit und Downloadkabel EPZ H110 am PC abziehen 4 Versorgungsspannung für Bedieneinheit einschalten Die Bedieneinheit ist betriebsbereit ...

Страница 30: ...ren Sie die Felder Beispiel A den Status der Bedieneinheit abfragen 1 Das Display in einer beliebigen Ecke oder kurz berühren Hinweis Diese Ecke darf kein anwählbares Feld enthalten 2 Sofort die diagonal gegenüberlie gende Ecke kurz berühren 0 1 2 3 B zwischen den Statusanzeigen mehrerer Ports umschalten l Z B zwischen CAN Port und ASP Port l Statusmeldungen werden nur bei be legtem benutztem Port...

Страница 31: ...RANS PAGE B Datum Uhrzeit einstellen 1 Feld SET CLOCK berühren um das Menü anzuwählen SET CONTRAST 04 SET CLOCK Wed 13 09 00 12 50 10 ESC 2 Gewünschtes Feld anwählen oder ESC 12 50 10 13 09 00 3 Wert ändern oder 4 Ggf Schritt 2 und 3 wiederholen um weitere Werte zu ändern 5 Bestätigen Sie die Eingabe Das Menü für Uhrzeit Datum und Kontrast wird angezeigt C Kontrast am Display einstellen 1 Feld SET...

Страница 32: ...sten für die hexadezimale Dateneingabe Vorzeichen eingeben Gleitkomma eingeben ESC ESC Parametereingabe abbrechen Hilfe Informa tions Alarm und Statusmeldungen verlassen Pfeil auf Parameterebene l Vorherigen dynamischen Text anwählen l Vorheriges alphanumerisches Zeichen anwäh len Pfeil ab Parameterebene l Nächsten dynamischen Text anwählen l Nächstes alphanumerisches Zeichen anwäh len Pfeil links...

Страница 33: ... 1 Wechseln Sie in die Parameter Ebene siehe B 2 Lassen Sie den Cursor auf der rechten Ziffer stehen 0 7 4 1 8 5 2 9 6 3 ESC 9876 3 Geben Sie den Wert der ersten Stelle ein Alle anderen Stellen werden auf Null gesetzt 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0001 4 Geben Sie den Wert der nächsten Stelle ein Die eingegebenen Ziffern werden eine Stelle nach links geschoben 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0012 5 Gebe...

Страница 34: ...B 2 Lassen Sie den Cursor auf der rechten Ziffer stehen SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 1A3F 3 Geben Sie den Wert der ersten Stelle ein Alle anderen Stellen werden auf Null gesetzt SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 000B numerischer Wert 0 9 alphanumerischer Wert 1 A 6 F 4 Geben Sie den Wert der nächsten Stelle ein Die zuvor eingegebenen Ziffern werden eine Stelle nach links ge sc...

Страница 35: ...erischer Wert 0 9 alphanumerischer Wert 1 A 6 F 4 Bestätigen Sie die Eingabe Der Cursor wechselt in die Menü Ebene G einen binären Wert vollständig neu ein geben 1 Wechseln Sie in die Parameter Ebene siehe B 2 Geben Sie den neuen Wert ein wie in C beschrieben 0 1 ESC 0001 H eine einzelne binäre Ziffer ändern 1 Wechseln Sie in die Parameter Ebene siehe B 2 Geben Sie den neuen Wert ein wie in D besc...

Страница 36: ...Eingabe Der Cursor wechselt in die Menü Ebene 6 Ändern Sie den Text ESC ON nächster Text vorheriger Text 7 Bestätigen Sie die Eingabe Der Cursor wechselt in die Menü Ebene K ein Symbol in einem Symbolfeld ändern 1 Wechseln Sie in die Parameter Ebene siehe B 2 Ändern Sie das Symbol z B ESC nächstes Symbol vorheriges Symbol 3 Bestätigen Sie die Eingabe Der Cursor wechselt in die Menü Ebene L einen W...

Страница 37: ...te Zeile zeigt Datum und Uhrzeit wann die Meldung ausgelöst wurde ƒ signalisiert wenn eine Informationsmeldung vorhanden ist Symbole und Zeichen in den Informationsmeldungen Symbole und Zeichen in der Zeile Datum Uhrzeit Bedeutung Die Informationsmeldung wurde zum erstenmal aufgerufen HELP Der Informationsmeldung ist eine Hilfe zugeordnet 40 Sie möchten Berühren Sie die Felder Beispiel A eine Info...

Страница 38: ...lt ein programmierbares Meldungsfeld Dieses Feld zeigt die numerische Größe der Variablen die die Meldung aktiviert hat ƒ Die letzte Zeile zeigt Datum und Uhrzeit wann die Meldung ausgelöst wurde ƒ signalisiert wenn eine Alarmmeldung vorhanden ist Symbole und Zeichen in den Alarmmeldungen Symbole 1 Zeichen in der Zeile Datum Uhrzeit Bedeutung Nicht quittierter Alarm Quittierter Alarm jedoch Alarmu...

Страница 39: ...rmregister ist das Auftreten des Alarms chronologisch nach Da tum und Uhrzeit gespeichert l Ein H in der linken Spalte signali siert dass ein Alarmregister ange wählt ist HIST ESC Druck im Tank uebersteigt die max Grenze 150 0 13 09 2000 10 45a 13 09 2000 10 48a 13 09 2000 10 55a Wasserstand unterhalb der Schwelle des Prozesses 10 13 09 2000 10 45a 13 09 2000 10 50a 13 09 2000 10 53a H 0001 H 0032...

Страница 40: ...che Zeichengröße für Projektseiten können max 16 Zeilen 40 Zeichen lang sein einfache Zeichengröße Sie möchten Berühren Sie die Felder Beispiel A die Hilfe zu einer Informationsmeldung aufrufen 1 Berühren Sie das programmierte Feld HELP ESC Druck uebersteigt die Sicherheitsgrenze 125 5 13 09 2000 10 45a HELP Temperatur uebersteigt die Sicherheitsgrenze 1700 13 09 2000 10 55a HELP 2 Hilfe schließen...

Страница 41: ...en Sitz prüfen l Leitung auf Beschädigung kontrollie ren COM BROK Kommunika tion unterbro chen Serielles Datenkabel zwischen Bedieneinheit und PC ist defekt oder nicht richtig angeschlossen l Sub D Stecker auf richtigen An schluss und festen Sitz prüfen l Serielles Datenkabel austauschen ASIC ko1 Kommunika tion mit Sys tembus CAN unterbrochen l Fehlerhafte Verdrahtung z B Verpolung des System bus ...

Страница 42: ...rei wenn die vorgeschriebenen Einsatzbedin gungen eingehalten werden 12 ƒ Reinigen Sie die Bedieneinheit mit denaturiertem Äthylalkohol ƒ Wenn Sie ein anderes Reinigungsmittel verwenden müssen um Verunreinigungen zu beseitigen beachten Sie die Angaben in der Tabelle im Kap 9 1 43 ...

Страница 43: ...PM H5xx und EPM H6xx bietet Lenze Schutzfolien an mit einer verbesserten Beständigkeit gegen die genannten Chemikalien Substanz Bedieneinheit EPM H3xx EPM H4xx EPM H5xx EPM H6xx mit Schutz folie Aceton L L J Ameisensäure 50 L L Ammoniak 2 L L Äthylenglykol L L L Ätznatron 2 L L Beizlösung konzentriert L Benzin J L L J Benzol J J L J Benzylalkohol L L Chlorwasserstoffsäure 10 L L Dieselöl J J J J E...

Страница 44: ...50 L L L L Toluol J J L J Trichlorethylen L J Unterchlorigsaures Na tron 20 L L Wasserstoffsuperoxyd 25 L L EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J Oberfläche ist beständig keine sichtbare Beschädigung L Oberfläche ist nicht beständig wird beschädigt nicht getestet ...

Страница 45: ...en 9 C Chemikalienbeständigkeit 43 D Daten eingeben 33 Datum einstellen 31 DC Spannungsversorgung 13 Display 13 Kontrast einstellen 31 E Eigenschaften 14 Einbauausschnitt 19 Einsatzbedingungen 12 Feuchtebeanspruchung 12 Montagebedingungen Gewicht 12 Umgebungsbedingungen klimatisch 12 Einschalten erstes 25 Elektrische Daten 13 Elektrische Installation 22 Versorgungsspannung anschließen 22 Erstes Ei...

Страница 46: ...6 Projekt in die Bedieneinheit übertragen 26 Projekt Download 27 S Speicher 13 Statusmeldungen 30 Störungsbeseitigung 41 Störungsmeldungen 41 Systembus CAN Baudrate 13 Verdrahtung 23 T Tastenfunktionen 32 Technische Daten 12 DC Spannungsversorgung 13 Display 13 Einbauausschnitt 19 Elektrische Daten 13 elektrischer Anschluss 13 Leistungsaufnahme 13 Schnittstellenbeschreibung 18 Speicher 13 Systembu...

Страница 47: ...Anhang Stichwortverzeichnis 9 47 EDBPM H502 DE EN FR 5 1 ...

Страница 48: ...48 EDBPM H502 DE EN FR 5 1 Key for the overview Pos Description Function Terminal block 4 pin 24V DC voltage supply Minidin socket 8 pin Serial port ASP for PC or PLC Terminal block 5 pin System bus CAN ...

Страница 49: ...M H502 DE EN FR 5 1 This documentation applies to the operating unit EPM H502 with the following nameplate data or higher Type EPM H502 1A 10 Product series EPM Operating unit Hardware version Software version ...

Страница 50: ...TD23 New edition due to reorganisation of the company 13251833 3 0 05 2008 TD23 Change of company name to Lenze Digitec Controls GmbH 00470641 2 0 07 2003 TD23 Complete revision for series production 00466870 1 0 03 2003 TD23 First edition for field test 0Fig 0Tab 0 Tip Documentation and software updates for further Lenze products can be found on the Internet in the Services Downloads area under h...

Страница 51: ... operating unit 63 4 Electrical installation 65 4 1 Supply voltage connection 65 4 2 Wiring of the system bus CAN 66 5 Commissioning 68 5 1 Initial switch on 68 5 2 Project transfer to the operating unit 69 5 2 1 Connecting operating unit and PC 69 5 2 2 Project download 70 5 2 3 Disconnectingfrom the PC 72 5 3 Status messages of the operating unit 73 5 4 Date time and contrast setting 74 6 Operat...

Страница 52: ...Contents i 52 EDBPM H502 DE EN FR 5 1 8 Maintenance 85 9 Appendix 86 9 1 Chemical resistance 86 9 2 Index 88 ...

Страница 53: ...rmation and notes relevant for them ƒ These Operating Instructions must always be complete and perfectly readable 1 2 Terminology used Term Used in this text for Controller Lenze 8200 vector and 9300 vector frequency inverter Lenze 9300 and 9400 servo inverter HMI Human Machine Interface 1 3 Scope of supply Scope of supply Important l 1 EPM H502 operating unit l 1 Operating Instructions l 4 mounti...

Страница 54: ...e of safety instructions Danger characterises the type and severity of danger Note describes the danger and gives information about how to prevent dangerous situations Pictograph and signal word Meaning Danger Danger of personal injury through dangerous electrical voltage Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken...

Страница 55: ...mation Scope of supply 1 55 EDBPM H502 DE EN FR 5 1 Application notes Pictograph and signal word Meaning Note Important note to ensure troublefree operation Tip Useful tip for simple handling Reference to another documentation ...

Страница 56: ...otection of persons and equipment Enclosure IP65 front EMC Applied standards for limit values EN 61000 6 4 2007 Noise emission Restriction of use Protection requirements are not ensured in residential areas EN 61000 6 2 2005 Noise immunity Restriction of use Protection requirements are not ensured in residential areas Operating conditions Ambient conditions Climate Storage 20 60 C Transport 20 60 ...

Страница 57: ... 6 5 8 mm text 12 16 pixels 9 1 11 7 mm text 24 32 pixels Fonts Programmable Contrast setting Software Background illumination LED Electrical connection DC voltage supply 24 VDC 18 32 VDC Power consumption 10 W at 24 VDC Fusing Miniature fuse Æ5 20 mm 800 mA F Network System bus CAN Protocol System bus CAN Network topology Line terminated at both ends with 120 W System bus node Master or slave Max...

Страница 58: ...r Function Available Save alarm register on flash Display alarm register Operating page Sheet feed on printer Set general page number to zero Hardcopy Help for the page Next page Change password Password login Password logout End project Display project information Report Commands Send recipe to device Function Available Load recipe from data memory Save recipe to data memory Delete recipe Send re...

Страница 59: ... Number 1024 1 Dynamic texts with bit group structure single bit structure or value structure Number 1024 1 Labels Function Available Clock field with seconds Function Available Clock field without seconds Function Available Function Display page help Function Available Display driver status page Set bit permanently Reset bit permanently Reverse bit Direct command with value structure Set real tim...

Страница 60: ...per recipe 128 256 Recipe field for recipe structure Function Available Buttons Number per page 24 Pages Number 64 Help for pages Number 64 Static bitmaps Function Available System messages Function Available Text lists Function Available Timers Number 32 Touch fields Number 24 Variables Limiting value and linear correction variables Number per page 32 Movement variables movable symbolic field Thr...

Страница 61: ...ion 2 61 EDBPM H502 DE EN FR 5 1 2 2 2 Interface description 1 2 3 4 5 6 7 8 h310_010 Fig 2 1 ASP8 Minidin socket 8 pin Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 n c 4 RTS RS232 OUT 5 CTS RS232 IN 6 n c 7 Signal GND 8 5 VCC reserved n c not connected ...

Страница 62: ...s 2 62 EDBPM H502 DE EN FR 5 1 2 3 Dimensions a d e c f c b h502_001 Fig 2 2 Dimensions a mm b mm c mm d mm e mm f mm 166 0 100 0 32 0 4 0 39 6 102 0 2 4 Mounting cutout a b h502_02 Fig 2 3 Mounting cutout a mm b mm 157 0 91 0 ...

Страница 63: ... dimensions for the mounting cutout can be found in the Technical data 62 How to mount the operating unit 0 1 h502_003 1 Push the operating unit and the seal into the mounting cutout FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 2 2 2 2 N C CAN Shield CAN V 1 2 3 4 5 h502_004 2 Insert the mounting clamps into the slots of the operating unit ...

Страница 64: ...lation Mounting of the operating unit 3 64 EDBPM H502 DE EN FR 5 1 3 3 2 2 3 3 FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 N C CAN Shield CAN V 1 2 3 4 5 h502_005 3 Tighten the screws against the mounting board ...

Страница 65: ...operating unit only when no voltage is applied 4 1 Supply voltage connection FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C PE N L1 18 32VDC 1 2 3 4 ASP8 N C CAN Shield CAN V 1 2 3 4 5 h502_006 Fig 4 1 Supply voltage connection Terminal assignment Terminal Identification Explanation 1 24 VDC Supply voltage DC 18 V 32 V 2 0 VDC GND supply voltage reference potential 3 n c Not connected 4 PE potential ...

Страница 66: ...em bus CAN 4 66 EDBPM H502 DE EN FR 5 1 4 2 Wiring of the system bus CAN Principle structure Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H315 A1 h315_004 Fig 4 2 Wiring of system bus CAN A1 Node 1 A2 Node 2 An Node n ...

Страница 67: ...st bus device Terminal Identification Explanation 1 V GND Reference potential 2 CAN LO System bus LOW data line 3 Shield Connect the shield of the system bus cable 4 CAN HI System bus HIGH data line 5 n c Not connected For the use of the transmission cable follow our recommendations Specification of the transmission cable Total length 300 m 1000 m Cable type LIYCY 2 x 2 x 0 5 mm2 paired with shiel...

Страница 68: ...missioning 5 1 Initial switch on Commissioning requires a complete wiring of the system bus Before switching on the supply voltage check ƒ the complete wiring for completeness and short circuit ƒ whether the bus system is terminated at the first and last physical node ...

Страница 69: ...y connect PC and operating unit when the units are switched off l HMI Designer FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C 1 2 3 4 ASP8 1 2 0 N C CAN Shield CAN V 1 2 3 4 5 h502_007 Fig 5 1 Connecting operating unit and PC 1 Plug the programming adapter EPZ H111 onto the ASP8 interface 2 Connect download cable EPZ H110 to programming adapter EPZ H111 3 Plug download cable EPZ H110 onto COM1 or COM...

Страница 70: ...ou can select whether you want to update the firmware at the time the project is loaded The firmware must always be updated with the first download of a project to the operating unit or after an update of the HMI Designer planning tool Tip Sample projects for the operating unit can be found in the HMI Designer planning tool under File Open Samples ...

Страница 71: ...lisation is completed select the system page Briefly touch the display in one of the corners or Note This corner must not contain a selectable field Immediately touch the diagonally opposite corner for a moment The system page appears 4 Touch the TRANS PAGE field The transfer page appears When WAITING FOR DOWNLOAD FROM ASP is displayed the operating unit is ready to receive data from the PC 5 Tran...

Страница 72: ...gfrom the PC How to disconnect from the PC 1 Switch off the PC 2 Switch off the supply voltage for the operating unit 3 Unplug the EPZ H111 programming adapter from the operating unit and the EPZ H110 download cable from the PC 4 Switch on the supply voltage for the operating unit The operating unit is now ready for operation ...

Страница 73: ...ch the fields Example A query the status of the operating unit 1 Briefly touch the display in one of the corners or Note This corner must not contain a selectable field 2 Immediately touch the diagonally opposite corner for a moment 0 1 2 3 B switch between the status displays of different ports l E g between CAN port and ASP port l Status messages are only displayed for assigned used ports Port N...

Страница 74: ...T PROG ESC TRANS PAGE B set date time 1 Touch the SET CLOCK field to select the menu SET CONTRAST 04 SET CLOCK Wed 13 09 00 12 50 10 ESC 2 Select the desired field or ESC 12 50 10 13 09 00 3 Change the value or 4 If necessary repeat steps 2 and 3 to change additional values 5 Confirm the input The menu for time date and contrast is displayed C set the contrast of the display 1 Touch the SET CONTRA...

Страница 75: ...F 1 A 6 F Alphanumerical keys for entering hexadecimal data Enter sign Enter floating point ESC Esc Abort parameter entry quit help information alarm and status messages Up arrow Parameter level l Select previous dynamic text l Select previous alphanumeric character Down arrow Parameter level l Select next dynamic text l Select next alphanumeric character Left arrow Parameter level Place cursor on...

Страница 76: ...1 Change to the parameter level see B 2 Leave the cursor on the right digit 0 7 4 1 8 5 2 9 6 3 ESC 9876 3 Enter the value for the first digit All other digits are set to zero 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0001 4 Enter the value for the next digit The digits entered will shift one place to the left 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0012 5 If necessary enter a floating point Note Floating points can only b...

Страница 77: ...l other digits are set to zero SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 000B Numerical value 0 9 Alphanumerical value 1 A 6 F 4 Enter the value for the next digit The digits entered before will shift one place to the left SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 00BD Numerical value 0 9 Alphanumerical value 1 A 6 F 5 Repeat step 4 until the value is complete 6 Confirm the input The cursor change...

Страница 78: ...name 1 Change to the parameter level see B 0 Q A Z SP ESC 1 W S X 2 E D C 3 R F V 4 T G B 5 V H N 6 U J M 7 I K 8 O L 9 P _ REZEPT1 2 Select the desired character or 3 Change the character using the keyboard 4 Repeat steps 2 and 3 until the new name is entered e g RECIPE1 5 Confirm the input The cursor changes to the menu level 6 Change the text ESC ON Next text Previous text 7 Confirm the input T...

Страница 79: ... 1 Example Touch the fields You want to L enter a bar chart value 1 Change to the parameter level see B 2 Enter the value VAL displays the entered value numerically or ESC VAL 36 MAX 100 Min 0 3 Confirm the input The cursor changes to the menu level ...

Страница 80: ...message ƒ The last line shows the date and time when the message has been triggered ƒ signals that an information message is present Symbols and characters in the information messages Symbols and characters used in the date time line Meaning The information message has been called up for the first time HELP Help is assigned to the information message 83 You want to Touch the fields Example A call ...

Страница 81: ...ontains a programmable message field This field indicates the numerical value of the variable that has activated the message ƒ The last line shows the date and time when the message has been triggered ƒ signals that an alarm message is present Symbols and characters used in alarm messages Symbols 1 Characters used in the date time line Meaning Alarm not acknowledged Acknowledged alarm but alarm ca...

Страница 82: ...rm message l The alarm register logs all alarms chronologically with time and date stamping l If H is displayed in the left column an alarm register has been selected HIST ESC Tankpressureexceeds safetylimit 150 0 13 09 200010 45a 13 09 200010 48a 13 09 200010 55a Waterlevelbelow processorlimit 10 13 09 200010 45a 13 09 200010 50a 13 09 200010 53a H 0001 H 0032 l Close the alarm register and go ba...

Страница 83: ...cters long normal character size for project pages can be up to 16 lines 40 characters long normal character size You want to Touch the fields Example A call up the help message for an information message 1 Touch the programmed field HELP ESC Pressure exceeds safety limit 125 5 13 09 2000 10 45a HELP Temperature exceeds safety limit 1700 13 09 2000 10 55a HELP 2 Close help ESC B call up the help m...

Страница 84: ...nnections are firmly seated l Check cable for damages COM BROK Communication interrupted Serial data cable between operating unit and PC is defective or not correctly connected l Check Sub D connector for correct connection and firm seating l Replace serial data cable ASIC ko1 Communication with system bus CAN interrupted l Faulty wiring e g polarity of the system bus l Faulty parameterisation of ...

Страница 85: ...ing unit is maintenance free if all operating conditions described in these Instructions are observed 56 ƒ Clean the operating unit with denatured ethyl alcohol ƒ If you use any other cleaning agents please observe the information given in the table in chapter 9 1 86 ...

Страница 86: ...rating units Lenze offers protective foils with an improved resistance against the listed chemicals Substance Operating unit EPM H3xx EPM H4xx EPM H5xx EPM H6xx With protective foil Acetic acid 5 50 L L L J Acetone L L J Ammonia 2 L L Benzene J L L J Benzole J J L J Benzyl alcohol L L Diesel oil J J J J Ethanol L L L J Ethylene glycol L L L Formic acid 50 L L High pressure and temperature 100 C L ...

Страница 87: ...Concentrated L Pure acetic acid L L Sodium hydroxide 2 L L Sodium hydroxide 50 L L L Sulphuric acid 50 L L L L Toluol J J L J Trichloroethylene L J EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J Surface resists no visible damage L Surface does not resist visible damage Not tested ...

Страница 88: ...ta input 76 Date adjustment 74 DC voltage supply 57 Definitions 53 Display 57 Contrast setting 74 E Electrical data 57 Electrical installation 65 Connecting the supply voltage 65 F Fault messages 84 G General data 56 H Help messages 83 Human Machine Interface 53 Humidity 56 I Information messages 80 Initial switch on 68 Installation system bus CAN 66 Installation electrical 65 Installation electri...

Страница 89: ...ransfer 69 Status messages 73 Operation 75 P Parameters 58 PC Connecting with the operating unit 69 Disconnecting from the operating unit 72 Power consumption 57 Project Download 70 Project transfer to the operating unit 69 S Status messages 73 Switch on initial 68 System bus CAN Baud rate 57 Wiring 66 T Technical data 56 DC voltage supply 57 Display 57 Electrical connection 57 Electrical data 57 ...

Страница 90: ... 90 EDBPM H502 DE EN FR 5 1 Légende Pos Description Fonction Bornier 4 bornes Alimentation 24 V CC Prise Minidin 8 broches Port série ASP pour PC ou API Bornier 5 bornes Bus Système CAN ...

Страница 91: ... H502 DE EN FR 5 1 Validité Unité de commande EPM H502 à partir de la version ci dessous voir plaque signalétique Type EPM H502 1A 10 Série d appareils EPM Unité de commande Version matérielle Version logicielle ...

Страница 92: ... édition en raison de la nouvelle organisa tion de l entreprise 13251833 3 0 05 2008 TD23 Nouvelle raison sociale Lenze Digitec Controls GmbH 00470641 2 0 07 2003 TD23 Texte entièrement revu pour la série 00466870 1 0 03 2003 TD23 Première édition pour essais sur le terrain 0Fig 0Tab 0 Conseil Les mises à jour de logiciels et les documentations relatives aux produits Lenze sont disponibles dans la...

Страница 93: ...trique 108 4 1 Raccordement de la tension d alimentation 108 4 2 Câblage du Bus Système CAN 109 5 Mise en service 111 5 1 Première mise en service 111 5 2 Téléchargementd un projet sur l unité de commande 112 5 2 1 Etablissement de la liaison entre l unité de commande et le PC 112 5 2 2 Téléchargement du projet 113 5 2 3 Déconnexiondu PC 115 5 3 Messages d état de l unité de commande 116 5 4 Régla...

Страница 94: ...Sommaire i 94 EDBPM H502 DE EN FR 5 1 8 Maintenance 129 9 Annexe 130 9 1 Résistance aux produits chimiques 130 9 2 Index 132 ...

Страница 95: ...nes correspondantes ƒ Les instructions de mise en service doivent être complètes et lisibles en toute circonstance 1 2 Terminologie Terme Utilisé dans le présent document pour désigner Variateur de vitesse les convertisseurs de fréquence 8200 vector et 9300 vector et les servovariateurs 9300 et 9400 de Lenze HMI une interface homme machine Human Machine Interface 1 3 Equipementlivré Equipement liv...

Страница 96: ...ation L explication décrit le risque et les moyens de l éviter Pictogramme et mot associé Explication Danger Situation dangereuse pour les personnes en raison d une tension électrique élevée Indication d un danger imminent qui peut avoir pour conséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Danger Situation dangereuse pour les pers...

Страница 97: ...BPM H502 DE EN FR 5 1 Consignesd utilisation Pictogramme et mot associé Explication Remarque importante Remarque importante pour assurer un fonctionnement correct Conseil Conseil utile pour faciliter la mise en oeuvre Référence à une autre documentation ...

Страница 98: ...il Indice de protection IP65 à l avant CEM Normes appliquées pour les valeurs limites EN 61000 6 4 2007 Perturbations radioélectriques Restriction d utilisation en environnement résidentiel le respect des exigences de protection n est pas garanti EN 61000 6 2 2005 Protection contre les parasites Restriction d utilisation en environnement résidentiel le respect des exigences de protection n est pas...

Страница 99: ...te 12 16 pixels 9 1 11 7 mm texte 24 32 pixels Polices Programmables Réglage du contraste Logiciel Rétro éclairage LED Raccordement électrique Alimentation CC 24 V CC 18 32 VCC Puissance absorbée 10 W pour 24 VCC Protection par fusible Fusible pour faible intensité Æ5 20 mm 800 mA F Réseau Bus Système CAN Protocole Bus Système CAN Topologie du réseau Ligne fermée des deux extrémités avec 120 W Par...

Страница 100: ...ion oui Mémoire registre d alarmes nombre 256 Opérations automatiques nombre 32 Sauvegarde reconstitution fonction oui Graphe à barres fonction oui Instructions Imprimer registre d alarmes fonction oui Sauvegarder registre d alarmes sur la mémoire Flash Afficher registre d alarmes Page de commande Alimentation papier imprimante Mise à zéro du numéro de pages général Copie d écran Aide sur la page ...

Страница 101: ...ette réceptionnée dans mémoire tampon Page précédente Mot de passe binaire bits 8 Dossier Images Bitmap fonction oui Courbe fonction oui Champ de données fonction oui Variables système affectées au format de recette fonction oui Instruction directe avec format valeur SOUSTRAIRE fonction oui ENTRER OU ET XOR AJOUTER Imprimer fonction oui Pages à imprimer total champs par page nombre 64 128 Bitmaps ...

Страница 102: ...256 256 Registre interne octets 2048 En tête pied de page total champs par en tête pied de page 64 128 Cercles fonction oui Lignes fonction oui Macros total instruction macro nombre 1024 16 Aide sur les messages nombre 256 Champ de message fonction oui Textes multilingues nombre de langues 4 Niveaux de mot de passe nombre 10 Polices programmables fonction oui Images du projet fonction oui Rectangl...

Страница 103: ...Zone tactile nombre 24 Variables Variables limites et linéaires de correction nombre par page 32 Variables de mouvement champ symbolique mobile Variables seuil Variables numériques à virgule flottante Variables numériques DEC HEX BIN BCD Variables de chaîne de caractères ASCII Champ Jour de la semaine fonction oui 1 Valeur approximative limitée par le volume du projet ...

Страница 104: ...n de la prise 2 104 EDBPM H502 DE EN FR 5 1 2 2 2 Affectation de la prise 1 2 3 4 5 6 7 8 h310_010 Fig 2 1 Prise ASP8 Minidin à 8 broches Pin Signal 1 Rx RS232 IN 2 Tx RS232 OUT 3 N C 4 RTS RS232 OUT 5 CTS RS232 IN 6 N C 7 Signal GND 8 5 VCC réservé N C Non connecté ...

Страница 105: ...s 2 105 EDBPM H502 DE EN FR 5 1 2 3 Encombrements a d e c f c b h502_001 Fig 2 2 Encombrements a mm b mm c mm d mm e mm f mm 166 0 100 0 32 0 4 0 39 6 102 0 2 4 Encoche de montage a b h502_02 Fig 2 3 Encoche de montage a mm b mm 157 0 91 0 ...

Страница 106: ... de l encoche de montage se reporter aux Spécifications techniques 105 Pour fixer l unité de commande 0 1 h502_003 1 Glisser l unité de commande avec le joint dans l encoche de montage FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 2 2 2 2 N C CAN Shield CAN V 1 2 3 4 5 h502_004 2 Placer les colliers de fixation dans les ouvertures prévues à cet effet ...

Страница 107: ...nique Montage de l unité de commande 3 107 EDBPM H502 DE EN FR 5 1 3 3 2 2 3 3 FU SE 800 mA ASP8 0 VD C N C 18 32 VD C 10 W 2 1 3 4 N C CAN Shield CAN V 1 2 3 4 5 h502_005 3 Visser la plaque de montage à l aide des vis ...

Страница 108: ...u câblage de l unité de commande qu en l absence de tension 4 1 Raccordement de la tension d alimentation FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C PE N L1 18 32VDC 1 2 3 4 ASP8 N C CAN Shield CAN V 1 2 3 4 5 h502_006 Fig 4 1 Raccordement de la tension d alimentation Affectation des bornes Borne Désignation Explication 1 24 V CC Tension d alimentation 18 V 32 V CC 2 0 V CC GND tension d alimenta...

Страница 109: ... H502 DE EN FR 5 1 4 2 Câblage du Bus Système CAN Principe de câblage Shield CAN V CAN N C CG LO HI CG LO CG LO HI CG LO HI HI 120 120 An A2 H315 A1 h315_004 Fig 4 2 Câblage du Bus Système CAN A1 Participant au bus 1 A2 Participant au bus 2 An Participant au bus n ...

Страница 110: ...r le premier et le dernier participant au bus Borne Désignation Explication 1 V GND Potentiel de référence 2 CAN LO Bus Système LOW ligne de données 3 Shield Blindage du câble bus 4 CAN HI Bus Système HIGH ligne de données 5 N C Non raccordé Nous vous recommandons d utiliser les câbles suivants Spécifications du câble de transmission Longueur totale 300 m 1000 m Type de câble LIYCY 2 x 2 x 0 5 mm2...

Страница 111: ... mise en service Pour la mise en service il est impératif que le Bus Système soit correctement raccordé Avant la mise sous tension vérifier ƒ le câblage dans son intégralité pour éviter un court circuit ƒ si des résistances d extrémité de bus sont raccordées au premier et au dernier participant au bus ...

Страница 112: ...e PC Stop Ne relier le PC à l unité de commande qu en l absence de tension l HMI Designer FUSE 800 mA 18 32 VDC 10W 0 VDC 1 2 3 4 N C 1 2 3 4 ASP8 1 2 0 N C CAN Shield CAN V 1 2 3 4 5 h502_007 Fig 5 1 Etablissement de la liaison entre l unité de commande au PC 1 Enficher l adaptateur de paramétrage EPZ H111 dans la prise ASP8 2 Relier le câble de téléchargement EPZ H110 avec l adaptateur EPZ H111 ...

Страница 113: ...met de déterminer si le micrologiciel doit être actualisé simultanément au chargement du projet Il faut toujours procéder à l actualisation du micrologiciel lors du premier téléchargement d un projet sur l unité de commande et après une mise à jour de l outil de conception HMI Designer Conseil Pour les exemples de projet de l unité de commande voir l outil de conception HMI Designer Fichier Ouvrir...

Страница 114: ...s l initialisation sélectionner la page système Toucher brièvement l écran dans l un des coins ou au choix Remarque le coin ne doit contenir aucun champ Toucher ensuite brièvement le coin opposé en diagonale La page système apparaît 4 Toucher le champ TRANS PAGE La page Transfer Page apparaît Lorsque WAITING FOR DOWNLOAD FROM ASP s affiche l unité de commande est prête à recevoir des données du PC...

Страница 115: ...1 5 2 3 Déconnexiondu PC Pour couper la liaison avec le PC 1 Mettre le PC hors tension 2 Mettre l unité de commande hors tension 3 Retirer l adaptateur EPZ H111 de l unité de commande et le câble de téléchargement EPZ H110 du PC 4 Mettre l unité de commande sous tension L unité de commande est prête à fonctionner ...

Страница 116: ... Error Pour Toucher les champs Exemple A connaître l état de l unité de commande 1 Toucher brièvement l écran dans l un des coins ou au choix Remarque le coin ne doit contenir aucun champ 2 Toucher ensuite brièvement et immédiatement le coin opposé en diagonale 0 1 2 3 B passer de l état d un port à l autre l Ex du port CAN au port ASP l Les messages d état ne s affichent que si le port est utilis...

Страница 117: ...RESET PROG ESC TRANS PAGE B régler la date l heure 1 Toucher le champ SET CLOCK pour afficher le menu correspondant SET CONTRAST 04 SET CLOCK Wed 13 09 00 12 50 10 ESC 2 Sélectionner le champ souhaité ou ESC 12 50 10 13 09 00 3 Modifier la valeur ou 4 Le cas échéant reprendre les points 2 et 3 pour modifier d autres valeurs 5 Valider Le menu Date heure et contraste s affiche C régler le contraste ...

Страница 118: ... le signe Entrer la virgule flottante ESC ESC Abandonner la saisie de paramètres quitter les messages d aide d alarme d information et d état Touche de direction HAUT Niveau paramètres l sélectionner le texte dynamique précédent l sélectionner le caractère alphanumérique précédent Touche de direction BAS Niveau paramètres l sélectionner le texte dynamique suivant l sélectionner le caractère alphan...

Страница 119: ...Utilisation Saisie des données 6 119 EDBPM H502 DE EN FR 5 1 6 2 Saisie des données L ordre chronologique pour la saisie et la modification des données est décrit à l aide d un exemple ...

Страница 120: ...r sur le chiffre de droite 0 7 4 1 8 5 2 9 6 3 ESC 9876 3 Entrer la valeur de la première position Toutes les autres positions sont mises à zéro 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0001 4 Entrer la valeur de la position suivante Les chiffres entrés sont placés à gauche d une position 0 9 0 7 4 1 8 5 2 9 6 3 ESC 0012 5 Selon le cas insérer une virgule flottante Remarque Il n est possible d insérer une virg...

Страница 121: ...es autres positions sont mises à zéro SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 000B Valeur numérique 0 9 Valeur alphanumérique 1 A 6 F 4 Entrer la valeur de la position suivante Les chiffres entrés auparavant sont placés à gauche d une position SHIFT 0 7 4 D 1 A 8 5 E 2 B 9 6 F 3 C ESC 00BD Valeur numérique 0 9 Valeur alphanumérique 1 A 6 F 5 Renouveler l étape 4 jusqu à ce que la valeur soit ent...

Страница 122: ... voir B J modifier la désignation d une recette 1 Passer au niveau paramètres voir B 0 Q A Z SP ESC 1 W S X 2 E D C 3 R F V 4 T G B 5 V H N 6 U J M 7 I K 8 O L 9 P _ REZEPT1 2 Sélectionner le caractère souhaité ou 3 Modifier le caractère en utilisant le clavier 4 Renouveler les étapes 2 et 3 jusqu à ce que la nouvelle désignation soit entrée ex RECETTE1 5 Valider Le curseur passe au niveau menu 6 ...

Страница 123: ... FR 5 1 Exemple Toucher les champs Pour L entrer une valeur via un diagramme en barres 1 Passer au niveau paramètres voir B 2 Entrer la valeur VAL affiche la valeur entrée en numérique ou ESC VAL 36 MAX 100 Min 0 3 Valider Le curseur passe au niveau menu ...

Страница 124: ...ssage ƒ La dernière ligne indique la date et l heure d activation du message ƒ indique qu un message d information est activé Symboles et caractères des messages d information Symbole et caractères de la ligne Date heure Signification Ce message d information s affiche pour la première fois HELP Une rubrique d aide est affectée au message d information 127 Pour toucher les champs Exemple A appeler...

Страница 125: ... l heure ƒ L avant dernière ligne contient un champ de message configurable Ce champ indique la taille numérique des variables activées par le message ƒ La dernière ligne indique la date et l heure d activation du message ƒ indique qu un message d alarme est activé Symboles et caractères des messages d alarme Symboles 1 Caractères à la ligne Date heure Signification Alarme non acquittée Alarme acq...

Страница 126: ...torie les messages d alarme dans l ordre chronologique par date et heure l Le H dans la colonne de gauche indique qu un registre d alarmes a été sélectionné HIST ESC Pressionréservoir limitemaxiatteinte 150 0 13 09 200010 45a 13 09 200010 48a 13 09 200010 55a Niveaud eau seuil inférieurprocessatteint 10 13 09 200010 45a 13 09 200010 50a 13 09 200010 53a H 0001 H 0032 l Fermer le registre d alarmes...

Страница 127: ...ères taille de caractère simple pour les messages d information ne doivent pas dépasser 16 lignes de 40 caractères taille de caractère simple pour les pages projet Pour Toucher les champs Exemple A afficher l aide concernant un message d information 1 Toucher le champ HELP ESC Pression limite de sécuritté atteinte Température limite de sécuritté atteinte 125 5 13 09 2000 10 45a HELP 1700 13 09 200...

Страница 128: ...ont bien serrés l Vérifier si le câble est endommagé COM BROK Communication interrompue Le câble de données série reliant l unité de commande et le PC est défectueux ou n est pas correctement connecté l Vérifier si le connecteur Sub D est correctement enfiché l Echanger le câble de données série ASIC ko1 Communication avec Bus Système CAN interrompue l Câblage erroné exemple polarité incorrecte du...

Страница 129: ... aucun entretien à condition de respecter les conditions d utilisation prescrites 98 ƒ Il convient de nettoyer l unité de commande à l aide d alcool éthylique dénaturé ƒ Si cette opération est insuffisante et s il faut utiliser un autre produit nettoyant se reporter au tableau chap 9 1 130 ...

Страница 130: ...e commande EPM H5xx et EPM H6xx Lenze vous propose des protecteurs d écran avec une résistance améliorée aux produits chimiques mentionnés Substance Unité de commande EPM H3xx EPM H4xx EPM H5xx EPM H6xx Avec protecteur d écran Acétone L L J Acide acétique 5 50 L L L J Acide acétique glacial L L Acide chlorhydrique 10 L L Acide formique 50 L L Acide nitrique 5 10 L L L J Acide phosphorique 30 L L L...

Страница 131: ...d hydrogène 25 L L Tétrachloréthylène L J Toluène J J L J Trichloréthylène L J EPM H3xx EPM H310 EPM H312 EPM H315 EPM H4xx EPM H410 EPM H5xx EPM H502 EPM H505 EPM H507 EPM H510 EPM H515 EPM H520 EPM H521 EPM H525 EPM H6xx EPM H605 EPM H606 J L interface opérateur résiste à la substance chimique aucun endommagement visible L L interface opérateur ne résiste pas à la substance chimique interface op...

Страница 132: ...s défauts 128 Messages d erreur 128 Données saisie des données 119 E Ecran 99 Electricité installation Raccordement de la tension d alimentation 108 Elimination des défauts 128 Encoche de montage 105 F Fonction des touches 118 H Heure réglage 117 Humidité admissible 98 I Installation Bus Système CAN 109 Installation électrique 108 Raccordement de la tension d alimentation 108 Installation mécaniqu...

Страница 133: ...iques 99 Ecran 99 Encoche de montage 105 Mémoire 99 Puissance absorbée 99 Raccordement électrique 99 Spécifications techniques 98 T Terminologie 95 Type de câble 96 110 U Unité de commande Déconnexion du PC 115 Affectation de la prise 104 Afficher un message d alarme 125 Appeler un message d information 124 Caractéristiques 100 Etablissement de la liaison entre l unité de commande et le PC 112 Fon...

Страница 134: ...many Service Lenze Service GmbH Breslauer Straße 3 D 32699 Extertal Germany 49 0 51 54 82 0 00 80 00 24 4 68 77 24 h helpline Ê 49 0 51 54 82 28 00 Ê 49 0 51 54 82 11 12 Lenze Lenze de Service Lenze de ü www Lenze com EDBPM H502 O DE EN FR 5 1 TD23 10 9 8 7 6 5 4 3 2 1 ...

Отзывы: