Electrical installation
Connection of system bus (CAN)
54
EDBCSXE040 EN 6.0
Specification of the transmission cable
We recommend the use of CAN cables according to ISO 11898−2:
CAN cable according to ISO 11898−2
Cable type
Twisted pair with shielding
Impedance
120
W
(95 ... 140
W
)
Cable resistance
Cable length
£
300 m
£
70 m
W
/m
Cable length
£
1000 m
£
40 m
W
/m
Signal propagation delay
£
5 ns/m
Bus cable length
Note!
The permissible cable lengths must be observed.
1. Check the compliance with the total cable length in Tab. 5−1.
The baud rate determines the total cable length.
CAN baud rate
[kbit/s]
Max. bus length
[m]
50
1500
125
630
250
290
500
120
1000
25
Tab. 5−1
Total cable length
2. Check the compliance with the segment cable length in Tab. 5−2.
The segment cable length is determined by the cable cross−section used and the number
of nodes. Without a repeater, the segment cable length corresponds to the total cable
length.
Number of nodes
Cable cross−section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
2
240 m
430 m
650 m
940 m
5
230 m
420 m
640 m
920 m
10
230 m
410 m
620 m
900 m
20
210 m
390 m
580 m
850 m
32
200 m
360 m
550 m
800 m
63
170 m
310 m
470 m
690 m
Tab. 5−2
Segment cable length
3. Compare the two values detected.
If the value detected from Tab. 5−2 is smaller than the total cable length to be provided
from Tab. 5−1 , repeaters must be used. Repeaters divide the total cable length into
segments.
Observe...
the information on the use of a repeater in the
CAN Communication Manual
.
Содержание ECSDE012
Страница 1: ...EDBCSXE040 y Ä y ä Operating Instructions ECS ECSEExxx ECSDExxx ECSCExxx Power supply module ...
Страница 3: ... 3 EDBCSXE040 EN 6 0 ECSEE_002A ...
Страница 168: ...Index 12 168 EDBCSXE040 EN 6 0 W Warning 68 112 Warranty 12 X XT EMZ9371BC keypad Diagnostics 123 Parameter setting 72 ...