Electrical installation
Power terminals
Motor connection
115
EDKCSDX064 DE/EN/FR 4.0
5.2.2
Motor connection
ECSXA010
Fig. 5−3
Motor and motor holding brake connection
Motor cables
ƒ
Use low−capacitance motor cables. Capacitance per unit length:
–
Core/core: max. 75 pF/m
–
Core/shield: max. 150 pF/m
ƒ
Length: max. 50 m, shielded
ƒ
The cross−section of the motor cables are selected according to the motor
standstill current (I
0
) when using synchronous motors or according to the
rated motor current (I
N
) for asynchronous motors.
ƒ
Length of the unshielded ends: 40 ... 100 mm (depending on the cable
cross−section)
ƒ
Lenze system cables meet these requirements.
ƒ
Use the ECSZS000X0B shield mounting kit for EMC−compliant wiring.
Mounting instructions for ECSZS000X0B shield mounting
Here you can find more information on wiring according to EMC.