6
Commissioning
6.4
Setting the IP configuration
32
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.2
Setting via codes in the »Engineer«
You can also set the IP parameters manually via code in the »Engineer« under the
Settings
tab.
The IP parameters are written to codes
(IP address),
(subnet mask), and
(gateway address).
With the
C00002 = "11: Save all parameter sets"
device command, the current IP configuration is
saved non-volatilely.
Decimal representation of the IP parameters
By clicking the
[ int ]
buttons on the right next to the input fields, the IP parameters are represented
as decimal values.
In the case of the decimal representation, the byte sequence is inverted.
Example:
IP address 192.168.0.1
•
= 16820416 [00000001.00000000.10101000.11000000
bin
]
Note!
• The IP address must only be allocated manually in the »Engineer« if the PROFINET
network is not operated on the IO controller yet (IP address has not been allocated by
the IO controller yet).
• While setting the IP parameters in the »Engineer«, PROFINET communication with the
IO controller must not take place at the same time.
Byte 3
Byte 2
Byte 1
Byte 0
1
0
168
192
0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 0 1 0 1 0 0 0 1 1 0 0 0 0 0 0