Parameter reference
Parameters of the communication module
66
Lenze · E84AYCEC communication module (POWERLINK) · EDS84AYCEC EN 4.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13003
C13004
Parameter | Name:
C13003 | 0x1E40.5 IP Address Router
Data type: UNSIGNED_32
Index: 11572
d
= 2D34
h
The code declares the IP address of the router which connects the EPL segment to the higher-level network. The
standard entry corresponds to the standard router address of the EPL specification:
192.168.100.254
Permissible entries replace the lowest-order byte of the standard entry with the EPL address of the node which has
the function of a router.
Setting range
(min. value | unit | max. value)
0.0.0.0
(0x00000000)
255.255.255.255
(0xFFFFFFFF)
Subcodes
Lenze setting
Info
C13003/1
3232261374
IP address router
• Lenze setting: 0xC0A864FE = 192.168.100.254
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13004 | 0x1030.5 MAC Address
Data type: OCTET_STRING
Index: 11571
d
= 2D33
h
The code indicates the physical address (MAC address) of the Ethernet interface of the communication module.
When the communication module is produced, the MAC address is assigned unequivocally worldwide and provides
addressing on the lowest level.
Subcodes
Info
C13004/1
MAC Address (octet string[6])
00-0A-86-xx-yy-zz
• 00-0A-86 = Lenze
• xx-yy-zz = consecutive number
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT