Electrical installation
EMC−compliant wiring
EDK82ZAFSC−010 DE/EN/FR 6.1
38
H1_E_INST−Hi_EMV
6
Electrical installation
EMC−compliant wiring
Please observe the following for wiring according to EMC guidelines:
Note!
ƒ
Separate control cables from motor cables.
ƒ
Lead the shields as far as possible to the terminals (unshielded core length
< 40 mm).
ƒ
Connect control and data cable shields as follows:
–
Analog
signal cable shields must be connected
with one end
at the
inverter.
–
Digital
signal cable shields must be connected
with both ends
.
ƒ
More information about wiring according to EMC guidelines can be
obtained from the corresponding documentation for the standard device.