Montageanleitung

Mounting Instructions

Instructions de montage

EDK82ZAFPC-010

.C$Y

Ä.

C

$

Y

ä

PROFIBUS PT

E82ZAFPC010

Funktionsmodul

Function module

Module de fonction

Содержание E82ZAFPC010

Страница 1: ...Montageanleitung Mounting Instructions Instructions de montage EDK82ZAFPC 010 C Y Ä C Yä PROFIBUS PT E82ZAFPC010 Funktionsmodul Function module Module de fonction ...

Страница 2: ...ch for activating the bus terminating resistor 68 Status of PROFIBUS communication yellow LED 70 Connection status to the standard device green LED Plug connector X3 1 connection for PROFIBUS 61 Plug connector X3 2 connection for external voltage supply Plug connector X3 3 connection for controller inhibit CINH Nameplate 47 0Fig 0Tab 0 ...

Страница 3: ...rotective insulation 49 Dimensions 50 5 Mechanical installation 51 6 Electrical installation 52 Use of plug connectors 52 Wiring according to EMC 53 Wiring to a host 54 Bus cable length 57 Voltage supply 58 Assignment of the terminals 61 Cable cross sections and screw tightening torques 62 7 Commissioning 63 Before switching on 63 Commissioning steps 64 Configuring the host system 67 Activating th...

Страница 4: ...on about the commissioning of the function module ƒ Technical data Validity information The information given in this documentation is valid for the following devices Function module Type designation From hardware version From software version PROFIBUS PT E82ZAFPC010 3A 10 Target group This documentation is intended for persons who install and commission the described product according to the proj...

Страница 5: ...mentation uses the following conventions to distinguish between different types of information Type of information Identification Examples notes Numbers Decimal separator Point The decimal point is used throughout this documentation Example 1234 56 Symbols Page reference Reference to another page with additional information Example 16 see page 16 ...

Страница 6: ...revent dangerous situations Pictograph and signal word Meaning Danger Danger of personal injury through dangerous electrical voltage Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Danger Danger of personal injury through a general source of danger Reference to an imminent danger that may result in death or serious per...

Страница 7: ... 1 EDK82ZAFPC 010 DE EN FR 6 0 43 H2_Def_Hinweise SIC_pikt_EN Application notes Pictograph and signal word Meaning Note Important note to ensure troublefree operation Tip Useful tip for simple handling Reference to another documentation ...

Страница 8: ... assets Observe the safety instructions and residual hazards included in the documentation of the standard device Stop Electrostatic discharge Electronic components within the function module can be damaged or destroyed by electrostatic discharge Possible consequences ƒ The function module is defective ƒ Fieldbus communication is not possible or faulty Protective measures ƒ Free yourself from any ...

Страница 9: ...dule for use in conjunction with the following Lenze standard devices Product range Device identification From hardware version Frequency inverter 8200 vector Vx14 ƒ is a device intended for use in industrial power systems Any other use shall be deemed inappropriate Tip More information about this function module is available in the corresponding communication manual The PDF file can be downloaded...

Страница 10: ...umfang_BL Scope of supply E82ZAFL012C AFX007 010 016 020 Pos Scope of supply E82ZAFPC010 function module Mounting Instructions Plug connector with double screw connection 3 pole Plug connector with double screw connection 2 pole Plug connector with spring connection 4 pole Mounting clip ...

Страница 11: ...luessel_E82ZAFPC010 Identification E82AF000P0B201XX APPLICATION 010 3A22 010 3A22 010 3A22 APPLICATION 010 3A22 L Type Id No Prod No Ser No E82ZAFX005 E82ZAF P C 010 3A 10 Product series PROFIBUS Version Variant PT Plug Terminal with spring and screw connection Hardware version Software version ...

Страница 12: ...BUS node Slave Baud rate kbps 9 6 12000 automatic detection Process data words 1 word 10 words 16 bits per word DP user data length 4 parameter data words 1 10 process data words Max number of nodes Standard 32 1 bus segment With repeater 125 Max cable length per bus segment 1000 m depending on the baud rate and cable type used Communication time Sum of the cycle time and the processing time in th...

Страница 13: ...ation of the standard device Pollution EN 61800 5 1 Degree of pollution 2 Degree of protection IP20 protection against accidental contact according to NEMA 250 type 1 Protective insulation Protective insulation between bus and Type of insulation acc to EN 61800 5 1 8200 vector power stage Reinforced insulation Reference earth PE X3 2 7 X3 3 7 Functional insulation External supply X3 2 59 Functiona...

Страница 14: ...4 Technical data Dimensions EDK82ZAFPC 010 DE EN FR 6 0 50 H2_Abmess abmess Dimensions 72 51 15 30 64 E82ZAFP007 ...

Страница 15: ... Mounting Instructions for the standard device for the mechanical installation of the function module The Mounting Instructions for the standard device ƒ are part of the scope of supply and are enclosed with each device ƒ provide tips for avoiding damage through improper handling ƒ describe the obligatory order of installation steps ...

Страница 16: ...f plug connectors Stop Observe the following to prevent any damage to plug connectors and contacts ƒ Only pug in unplug the plug connectors when the controller is disconnected from the mains ƒ Wire the plug connectors before plugging them in ƒ Unused plug connectors must also be plugged in Use of plug connectors with spring connection E82ZAFX013 ...

Страница 17: ...nductor with a cross section of at least 16 mm2 reference PE to avoid potential differences between the bus nodes ƒ Observe the other notes concerning EMC compliant wiring given in the documentation for the standard device Wiring procedure 1 Observe the bus topology do not use any stubs 2 Observe the notes and wiring instructions given in the documents for the control system 3 Only use cables corr...

Страница 18: ...ins voltage 400 V protection against accidental contact is not ensured without implementing external measures Possible consequences ƒ Death or serious injury Protective measures ƒ If protection against accidental contact is required for the control terminals of the controller and the connections of the plugged device modules a double isolating distance must exist the components to be connected mus...

Страница 19: ... m E82ZAFP005 Fig 1 Example PROFIBUS with RS485 wiring without repeater No Element Note 1 Host E g PC or PLC with PROFIBUS master interface module 2 Bus cable Connects the PROFIBUS master interface module to the function modules The baud rate depends on the length of the bus cable 57 3 PROFIBUS slave Applicable standard device 45 with function module Activate bus terminating resistors at the first...

Страница 20: ...n of the transmission cable Note Only use cables complying with the listed specifications of the PROFIBUS user organisation Field Values Specific resistance 135 165 Ω km f 3 20 MHz Capacitance per unit length 30 nF km Loop resistance 110 Ω km Core diameter 0 64 mm Core cross section 0 34 mm2 Cores Twisted double insulated and shielded ...

Страница 21: ...aud rate depending on the data volume cycle time and number of nodes should only be selected as high as required for the application Tip For high baud rates we recommend to consider the use of optical fibres Advantages of optical fibres ƒ On the transmission path external electromagnetic interference remains ineffective ƒ Bus lengths of several kilometres are also possible with higher baud rates T...

Страница 22: ...g Leg_Mindestverdraht Voltage supply Internal DC voltage supply Theinternalvoltageisprovided atterminal X3 3 20 It servesto supplythecontrollerinhibit CINH GND1 GND1 B 7 20 59 20V A 28 39 7 T R A T R B GND2 X3 1 X3 2 X3 3 T R A T R B E82ZAFP011 The min wiring requirements for operation ...

Страница 23: ...odule is required if communication via the fieldbus is to be maintained even when the power supply of the standard device fails Note With external voltage supply of the function module the active bus terminating resistor is fed independently of the operation of the standard device In this way the bus system remains active even when the standard device is switched off or fails External voltage supp...

Страница 24: ...pgVersorgg Leg_Mindestverdraht External voltage supply with two voltage sources for 1 X3 3 28 controller inhibit CINH 2 X3 2 59 function module GND1 GND1 B 7 20 59 20V A 28 39 7 GND2 _ _ X3 1 X3 2 X3 3 T R A T R B T R A T R B E82ZAFP013 The min wiring requirements for operation ...

Страница 25: ... function module 24 V DC 10 reference GND1 Current consumption on 24 V DC 80 mA The current for looping through the supply voltage to other nodes via terminal 59 must be max 3 A 7 GND1 Reference potential for X3 3 20 Terminal X3 3 Designation Function level 7 GND1 Reference potential for X3 3 20 39 GND2 Reference potential for controller inhibit CINH at X3 3 28 28 CINH Controller inhibit Input res...

Страница 26: ...without wire end ferrule 1 5 mm2 AWG 16 with wire end ferrule without plastic sleeve 1 5 mm2 AWG 16 with wire end ferrule with plastic sleeve 1 5 mm2 AWG 16 Tightening torque 0 5 0 6 Nm 4 4 5 3 lb in Stripping length 10 mm Field Values Electrical connection 2 pin plug connector with spring connection Possible connections rigid 1 5 mm2 AWG 16 flexible without wire end ferrule 1 5 mm2 AWG 16 with wi...

Страница 27: ...sioning Before switching on Stop Before switching on the standard device with the function module for the first time check ƒ the entire wiring for completeness short circuit and earth fault ƒ whether the integrated bus terminating resistor is activated at the first and last physical node 68 ...

Страница 28: ... terminal 28 CINH Set terminal 28 to LOW level Later the standard device can be inhibited and enabled via the bus Documentation of the standard device 3 Connect mains voltage and if available separate voltage supply of the function module The standard device will be ready for operation after approx 1 second Controller inhibit CINH is active 69 Response The green LED Connection status to the standa...

Страница 29: ...f the standard device Response The yellow LED on the function module is blinking when the PROFIBUS is active 70 7 Select function module as source for control commands and setpoints Set C0005 200 A preconfiguration for operation with the function module is carried out Control words and status words are already linked 8 Assign process data output words POW of the master to process data input words ...

Страница 30: ...function generator input NSET1 RFG1 IN 10 Enable process output data via C1512 65535 Only required if C1511 has been changed Deactivate process data words that are not used by setting the respective subcode of code C1511 to 0 The value in C1512 is volatile and all process data are enabled after every switch on 11 Enable standard device via terminal 28 CINH Set terminal 28 to HIGH level 12 Enter th...

Страница 31: ...system The host must be configured before communication with the communication module is possible Master settings For configuring the PROFIBUS the device data base file GSE file of the communication module has to be imported into the configuring software of the master Tip The GSE file can be downloaded in the Services Downloads area at www Lenze com ...

Страница 32: ...hlussAktivieren DIP Schalter_BusAbschl_TAB Activating the bus terminating resistor The integrated bus terminating resistor can be activated with the DIP switch 0 ON E82ZAFP016 E82ZAFP010 DIP switches Switch position Function OFF Bus terminating resistor not active ON Bus terminating resistor active ...

Страница 33: ...ng communication For establishing communication via an externally supplied function module the standard device must be switched on as well ƒ After communication has been established the externally supplied module is independent of the power on off state of the standard device Protection against uncontrolled start up After a fault e g short term mains failure a restart of the drive is not always wa...

Страница 34: ...he function module green off The function module is not supplied with voltage The standard device and or the external voltage supply is switched off blinking The function module is supplied with voltage but is not connected to the standard device Causes The standard device is switched off The standard device is in the initialisation phase The standard device is not available on The function module...