DC−bus operation
Braking operation in a drive system
Basic considerations
l
121
EDS700ACBA EN 5.1
7.6
Braking operation in a drive system
7.6.1
Basic considerations
If the regenerative power of a drive exceeds the storage capacity of the DC bus, the
excessive energy must be consumed or dissipated. Target of the DC bus is to use the
excessive energy for other axes.
Check for all operating situations that may occur in the DC−bus interconnetion whether the
brake power provided by the brake choppers is high enough for the maximum regenerative
power that may occur. If necessary, several power supply modules with an integrated brake
chopper can be integrated into the drive system to increase the brake power (parallel
connection).
If several brake choppers are used, the following conditions must be met:
ƒ
The limiting monitoring functionalities must be considered when dimensioning the
continuous brake power for the DC bus:
– Brake chopper monitoring
– Brake resistor monitoring
ƒ
The temperature monitoring of the brake resistors must lead to power−off, otherwise
the brake resistors or devices may be destroyed.
ƒ
The brake choppers are protected by changing the duty cycle or switching them off
temporarily. They are automatically switched on again.
ƒ
One device must be defined as "master", and the other devices must be defined as
"slaves", in order to provide for the simultaneous switching of all brake choppers,
irrespective of tolerances. How to proceed:
– For "Slave activation", apply digital input DI3 of each slave to GND potential
(GD/0 V). By this, the device−internal brake chopper switching threshold of the
slave is set to a value above the tolerance zone (790 V).
– For control by the master, interconnect digital output DO1 of the master with DI1
of the slaves. Like this, the slaves will chop on request by the master, isochronously
with the master (at 765 V).
X2
0.
2
DO
1
DO2
GD
X2
0.1
D
I1
D
I
2
D
I
3
M
aster
Slave
|
X2
0.
2
DO
1
DO2
GD
X2
0.1
D
I1
D
I
2
D
I
3
DC
2
4
V
(+
1
9
.
2
...
+28
.
8
V)
i700S010 3
Fig. 13
Wiring of X20
X20
Connection of digital inputs and outputs at the power supply module
.1
Connector on the left−hand side
.2
Connector on the right−hand side
DIx
Digital input
DOx
Digital output (e.g. for controlling relays)
GD
Reference potential GND
Содержание E70AC Series
Страница 1: ...EDS700ACBA Usx Usx Hardware Manual i700 l E70AC Servo Inverter i700 Translation...
Страница 2: ...0Fig 0Tab 0...
Страница 75: ...Mechanical installation 5 l 75 EDS700ACBA EN 5 1...
Страница 147: ...Accessories overview Terminals 11 l 147 EDS700ACBA EN 5 1 E70AZEVK001 i700ZM001 A...
Страница 148: ...Accessories overview Terminals 11 l 148 EDS700ACBA EN 5 1 E70AZEVK002 i700ZM001 C...
Страница 149: ...Accessories overview Terminals 11 l 149 EDS700ACBA EN 5 1 E70AZEVK003 i700ZM001 B...
Страница 150: ...Accessories overview Terminals 11 l 150 EDS700ACBA EN 5 1 E70AZEVK004 i700ZM001 D...
Страница 151: ...Accessories overview Terminals 11 l 151 EDS700ACBA EN 5 1 E70AZEVK005 i700ZP005 a...
Страница 152: ...Accessories overview Terminals 11 l 152 EDS700ACBA EN 5 1 E70AZEVK006 i700ZP005 b...
Страница 157: ...Accessories overview EMC accessories Shield mounting 11 l 157 EDS700ACBA EN 5 1 ezamb_001 EZAMBKBM 10 mm 8 30 mm...
Страница 161: ......