RG-TDMOD 4

Introduction

2.2.3  Network Termination

For an RS-485 network it is essential to install the specified termination resistors (120

W

), i.e. one at both 

ends of a network segment. Failure to do so will result in signals being reflected back along the cable which 
will cause data corruption. An external 120

W

 1/4W resistor can be connected as shown in Figure 3.

AIN

AIN

COM

U

V W

L1 L2

9 A+ A1

20

20

E1 E2 E3

71

62

7

72

COM

COM

+12 

V

+15 

V

+15 

V

+10 

V

8U

28 7

L3

E4 A2

TXA

TXB

COM

8I

Connect to
drive earth

(PE)

120

1/4W

Figure 3: Network Termination Resistor

RS-485 half-duplex interface allows up to 32 devices to communicate on the network using a twisted 
pair of wires. The wires must be terminated at both ends of the network with resistors equal to their 
characteristic impedance, typically 120

W

. In noisy environments, twisted and shielded wire should be 

used. Ground the shield at the drive end only. This will further reduce unwanted noise and improve overall 
communication reliability. In addition, grounding terminal 7 on the 

Tmd

 is recommended when using serial 

communications.

2.3  Modbus Details

A. 

Tmd

 Drives running the Modbus communication protocol use the RTU (Remote Terminal Unit) 

transmission mode and are slaves only. Therefore, the device communicating with the drives must be 
a Modbus Master. The baud rate is 9600. By default the Tmd uses  no parity and two stop bits. There 
are provisions for Odd parity, 1 stop bit and Even parity 1 stop bit as well. The bit sequence is:

DATA

Start bit

1

2

3

4

5

6

7

8

Stop bit

Stop bit

B.  At this time the 

Tmd

 drive does not support the broadcast function of the protocol.

C.  IMPORTANT NOTE: Modbus 3X and 4X Registers are numbered starting at 1. However, when transmitted 

to a slave over the serial link, the actual address transmitted is one less. This is because the addresses 
are numbered starting from 0. The 

Tmd

 register numbers are also numbered starting from 0. Therefore, 

Tmd

 register numbers always correspond exactly with the address transmitted. As a result, MODBUS 

REGISTER NUMBERS ARE ALWAYS ONE GREATER THAN 

Tmd

 REGISTER NUMBERS. WHENEVER THE 

WORDS “REGISTER #xx” APPEAR, IT SHOULD BE ASSUMED THAT THEY MEAN “

Tmd

 REGISTER xx” 

and the Modbus Register number will be one larger. In some instances we may show both for clarity. 
For example: “Register #24 (Modbus Register #25) . . .”

Содержание AC Tech TMD Series

Страница 1: ...Tmd Series Drives Modbus Communications Reference Guide...

Страница 2: ...or more information about the Modbus Protocol please refer to the Modicon Modbus Protocol Reference Guide http www Modbus org 2003 AC Technology Corporation No part of this documentation may be copied...

Страница 3: ...twork Termination 4 2 3 Modbus Details 4 2 4 Universal Registers 6 3 Data Representation Internal and External 7 3 1 Register Format 7 3 2 Data Types 7 3 3 Tmd Drive Registers 7 4 Tmd Drive Setup Oper...

Страница 4: ...egisters 24 27 17 5 5 5 Speed Command Source Registers 24 28 17 5 5 6 Speed Reference Status Registers 24 28 17 5 5 7 Present Fault Registers 24 29 18 5 5 8 Commanded Rotational Direction Registers 24...

Страница 5: ...n installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directi...

Страница 6: ...umentation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connection until the capacitors have discharged Please observe the corre...

Страница 7: ...COM U V W L1 L2 9 A A1 20 20 E1 E2 E3 71 62 7 72 COM COM 12 V 15 V 15 V 10 V 8U 28 7 L3 E4 A2 TXA TXB COM 8I Figure 1 Tmd Control Strip 2 2 Electrical Installation 2 2 1 Cable Type For RS485 Modbus n...

Страница 8: ...ing serial communications 2 3 Modbus Details A Tmd Drives running the Modbus communication protocol use the RTU Remote Terminal Unit transmission mode and are slaves only Therefore the device communic...

Страница 9: ...As with function 03 we read one register at a time except where noted 06 Preset Single Register 4X references Write single register 16 Preset Multiple Registers 4X references Although the function is...

Страница 10: ...h Reg Function 1 Drive Control WRITE ONLY Not all drives will have all control functions but when the function is available it will be at a defined bit location within Register 1 Drive Family and regi...

Страница 11: ...dropping the tenth using programmed conversion factors Table 3 lists examples of the internal units used on the Tmd series Table 3 Tmd Series Internal Units Type Unit Example SPEED 1Hz 60Hz 600 TIME 1...

Страница 12: ...al Address The Tmd drive has a serial address parameter that must be programmed prior to attempting to operate the serial interface Set Parameter C09 Network Address to a valid address 1 247 Tip Most...

Страница 13: ...he Watchdog Timer is disabled n22 1 Controller Inhibit If the drive doesn t receive valid communication for period longer than time specified in parameter n23 it will COAST to a STOP and status displa...

Страница 14: ...ls and Parameters prevents writing to any register When LOCK is asserted the drive drops out of SERIAL control After receiving the WRITE message when serial control is locked the drive will return exc...

Страница 15: ...Operation The typical sequence for a Start Stop Speed Control or Parameter Change operation is listed herein 1 Power up drive 2 Set parameter C01 Control Source Setpoint to selection 10 or 11 3 Close...

Страница 16: ...0 2400 0 1 Hz 4a RS SA 03 02 DH DL CRCH CRCL 25 19 Actual Speed R SA 03 00 19 00 01 CRCH CRCL 0 2400 0 1 Hz 4b RS SA 03 02 DH DL CRCH CRCL 26 1A Load DH Status DL R SA 03 00 1A 00 01 CRCH CRCL Refer t...

Страница 17: ...the Data High Byte and Data Low Byte format of Register 1 Drive Control Table 8 Drive Control Register 1 Data Low Byte 0 UPDATE BUFFERS 1 LOCK SECURITY 2 STOP DRIVE COAST TO STOP 3 START DRIVE 4 UNUSE...

Страница 18: ...ries drives return 66 42H The MCH Series drives return 68 44H The smd Series drives return 69 45H The TC Series drives return 70 46H The Tmd Series drives return 71 47H The SMV Series drives return 72...

Страница 19: ...p of words requested can be either 1 or 6 This is an exception to the rule of being able to read only one register at a time If 6 words are requested at register 24 the following will be returned Tabl...

Страница 20: ...al Status Register 24 byte D3L or Register 26 DL Table 12 Operational Status Bit Parameter 0 FAULT LOCKOUT 1 FAULT 2 START PENDING 3 MOTOR CALIBRATION NOT DONE 4 STOP 5 LOWER TRANSISTORS SWITCHING ON...

Страница 21: ...eypad 7 c40 Remote Keypad Remote Keypad 8 Analog Terminal Modbus 9 c40 Terminal Modbus 10 Analog Modbus Modbus 11 c40 Modbus Modbus 5 5 5 Speed Command Source Registers 24 28 Table 14 lists the Speed...

Страница 22: ...FAULT OC6 27 IDENTIFICATION FAULT bF 10 OEM DATA FAULT GF 28 A D CONVERTER FAULT Ad 11 CONFIGURATION FAULT CFG 29 REMOTE KEYPAD FAULT JF 12 DYNAMIC BRAKE OVERHEATED FAULT dF 30 LOSS OF 4 20mA SIGNAL...

Страница 23: ...ed refer to the full parameter protocol specification if access to programming parameters is required 5 9 Unlock Parameters Register 49 Register 49 Unlock Parameters unlocks programming parameters for...

Страница 24: ...f parameters Request SA 03 00 RA 00 01 CRCH CRCL Response SA 03 02 DH DL CRCH CRCL Message structure for reading 4 word Register 114 Parameter C99 Software Version Request SA 03 00 RA 00 04 CRCH CRCL...

Страница 25: ...setting 0 No action loading complete 1 Load 50Hz Lenze settings 2 Load 60Hz Lenze settings 3 Load OEM settings if present 0 CE1 CE2 CE3 CE4 53 35H 54 36H 55 37H 56 38H Configuration Digital Inputs E1...

Страница 26: ...Hz C18 68 44H Chopper Frequency 0 4kHz 1 6kHz 2 8kHz 3 10kHz 2 69 45H RESERVED C21 70 46H Slip Compensation 0 400 0 0 40 0 0 0 C22 71 47H Current Limit 30 200 200 C24 72 48H Accel Boost 0 200 0 0 20 0...

Страница 27: ...4 102 66H Motor Stator Resistance 0 6400 0 00 64 0 W 2 0 00 W C86 103 67H Motor Rated Power 0 9990 0 00 99 9 kW 2 C87 104 68H Motor Rated Speed 300 65000 RPM 1390 RPM C88 105 69H Motor Rated Current 0...

Страница 28: ...0 8 O 1 if C01 8 11 0 125 7DH Not Used 126 7EH RESERVED c40 127 7FH Freq Setpoint Command 0 2400 0 0 240 Hz 0 0 Hz c42 128 80H Start Condition 0 Start after LOW HIGH change at 28 1 Auto Start if 28 HI...

Страница 29: ...hours Read Only 143 8FH RESERVED c82 144 90H S Ramp Integral Time 0 500 0 0 50 0 sec 0 0 sec 145 91H RESERVED 146 92H RESERVED 147 93H RESERVED 148 94H RESERVED 149 95H RESERVED 150 96H RESERVED 151 9...

Страница 30: ...AULT LU 9 MOTOR OVERLOAD FAULT OC6 10 OEM DATA FAULT GF 11 CONFIGURATION FAULT CFG 12 DYNAMIC BRAKE OVERHEATED FAULT dF 13 SINGLE PHASE FAULT SF 14 EXTERNAL FAULT EEr 15 CONTROL FAULT CF 16 AUTOMATIC...

Страница 31: ...s to 1 3 The Modbus master needs to be set to use 9600 baud No other baud rates are supported by the TMD drive 4 The TMD series drive has the provision for a watchdog timer to monitor network communic...

Страница 32: ...he drive before writing any other function 4 Setting the Drive to Network Speed reference In order for the drive to respond to speed commands written to the keypad speed register the drive must be put...

Страница 33: ...operational status If this is the only data you want you can use Modbus function code 3 with a length of 1 to read register 40027 The value of that low byte of data corresponds to the following opera...

Страница 34: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG TDMOD e3...

Отзывы: