21 RG-TDMOD
Drive Control & Communication
6.2 Parameter List
Parameter No.
1
Tmd Register #
(hexadecimal
representation)
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory
Default
PV503
C01
51 (33H)
Setpoint and Control Source
Speed
Control
Program
0 Analog Terminal
Keypad
1 c40
Terminal
Keypad
2 Analog Terminal
LECOM
3 LECOM LECOM
LECOM
4 Analog
Terminal
Remote Keypad
5 c40
Terminal
Remote Keypad
6 Analog
Remote Keypad Remote Keypad
7 c40
Remote Keypad Remote Keypad
8 Analog Terminal
Modbus
9 c40
Terminal
Modbus
10 Analog Modbus
Modbus
11 c40
Modbus
Modbus
0
C02
52 (34H)
Load Lenze setting
0 No action/loading complete
1 Load 50Hz Lenze settings
2 Load 60Hz Lenze settings
3 Load OEM settings (if present)
0
CE1
CE2
CE3
CE4
53 (35H)
54 (36H)
55 (37H)
56 (38H)
Configuration
Digital Inputs
E1, E2, E3, E4
1 Activate fixed setpoint 1 (JOG1)
2 Activate fixed setpoint 2 (JOG2)
3 DC Braking (DCB)
4 Direction of Rotation
5 Quick Stop
6 CW Rotation
7 CCW Rotation
8 UP
9 DOWN
10 TRIP set
11 TRIP reset
12 Accel/decel 2
CE1 = 1
CE2 = 2
CE3 = 3
CE4 = 4
57 (39H)
Not Used
58 (3AH)
RESERVED
C09
59 (3BH)
Network Address
1 - 247
1
C10
60 (3CH)
Minimum Output Freq.
0 - 2400 (0.0 - 240 Hz)
0.0 Hz
C11
61 (3DH)
Maximum Output Freq.
75 - 2400 (7.5 - 240 Hz)
50.0 Hz
C12
62 (3EH)
Acceleration Time
0 - 9990 (0.0 - 999 sec)
5.0 sec
C13
63 (3FH)
Deceleration Time
0 - 9990 (0.0 - 999 sec)
5.0 sec
1 = The drive's programming code number; (2) = Two decimal places assumed