background image

 

RG-MHBAC

BACnet Objects

4.2  Analog Input (AI) Object Descriptions

Object AI-1: 

Actual Frequency

 

This object represents the actual speed of the drive in Hz.

Object AI-2: 

Command Frequency

 

This object represents the commanded drive speed in Hz.

Object AI-3: 

Load Percent

 

This object represents the drive’s load current as a % of rated current.

Object AI-4: 

Total Runtime

 

This object represents the number of hours that the drive has been running since its first 
power-up.

Object AI-5: 

DC Bus Voltage

 

This object represents the drive's DC Bus Voltage as a percentage of the nominal DC bus 
voltage.

Object AI-6: 

PID Setpoint Command

 

This  object  is  for  monitoring  the  commanded  PID  Setpoint.  The  range  of  this  object  is 
defined by Drive Parameter #75 (Feedback @ Min) and Drive Parameter #76 (Feedback @ 
Max).The unit is %.

Object AI-7: 

PID Feedback

 

This object is for monitoring the current PID Feedback value at the input specified by Drive 
Parameter #74 (PID Feedback). The range of this object is defined by Drive Parameter #75 
(Feedback @ Min) and Drive Parameter #76 (Feedback @ Max).The unit is %.

4.3  Analog Value (AV) Object Descriptions

Object AV-1:  Keypad Speed Command
 

This  object  monitors  and  controls  the  Keypad  Speed  Command  (in  Hz).  The  ability  to 
command this object through the LAN is dictated by the setting of Drive Parameter #30 
(Control) and the drive’s current H/O/A Mode (Refer to Object MSI-4).

Object AV-2:  Keypad Setpoint Command
 

This object monitors and controls the Keypad Setpoint Command. The unit for this object 
is percent (%). The minimum and maximum values for this object are defined by Drive 
Parameter #75 (Feedback @ Min) and #76 (Feedback @ Max), respectively. The range of 
adjustment for Drive Parameters #75 and 76 is –32768 to 32767.

 

The ability to command this object through the LAN is dictated by Drive Parameter #30 
(Control) and the drive HOA (Refer to Object MSI-4).

Содержание AC Tech MCH Series

Страница 1: ...MCH Series Drives BACnet Communications Guide...

Страница 2: ...nc 1791 Tullie Circle NE Atlanta GA 30329 http www bacnet org Modbus is a registered trademark of Schneider Electric founder of Modbus IDA http www modbus IDA org 2003 AC Technology Corporation No par...

Страница 3: ...ed Programming Parameters 4 3 2 Omitted Parameters and Selections 4 3 3 Modified Parameters and Selections 5 3 4 Serial Communication Setup 5 4 MCH BACnet Objects 8 4 1 BACnet Object Map 8 4 2 Analog...

Страница 4: ...n installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directi...

Страница 5: ...adapt the controller to your application as described in the documentation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connect...

Страница 6: ...length of an MS TP segment is 1200 meters 4000 feet with AWG 18 cable Maximum number of nodes unit loads per segment is 32 as specified by the EIA 485 standard Because MS TP uses non return to zero N...

Страница 7: ...e of bits 0 15 of the drive s 22 bit device number It can be used by itself to represent a device number in the range of 0 to 65535 If the device number exceeds 65535 then DEVICE NUM EX must also be u...

Страница 8: ...ng of all MCH BACnet points Write commands will not be accepted without proper modification to these drive settings One exception to this is STOP commands which are always accepted over the LAN For se...

Страница 9: ...erial watchdog timeout occurrence The options for this parameter are FAULT default and PRESET 3 If FAULT is selected and the drive is running when a serial watchdog timeout occurs the drive will trip...

Страница 10: ...of serial control If Drive Parameter 30 Control is set to SERIAL AUTO and the drive was running when the timeout occurred the drive will also stop the motor by tripping into a SERIAL FAULT A fault res...

Страница 11: ...ommand PID SETPOINT 1 00 50 AI 7 PID Feedback PID FEEDBACK 1 00 0 AV 1 Keypad Speed Command KEY SPD CMD Hz 0 01 20 00 AV 2 Keypad Setpoint Command KEY STPT CMD 1 00 50 BI 1 Run Stop Status RUN_STOP 1...

Страница 12: ...back This object is for monitoring the current PID Feedback value at the input specified by Drive Parameter 74 PID Feedback The range of this object is defined by Drive Parameter 75 Feedback Min and D...

Страница 13: ...information Object BI 6 Relay 1 This object monitors the state of the drive s Relay 1 output This object can be used to indicate various drive conditions as specified by Drive Parameter 54 RELAY1 Ref...

Страница 14: ...his object indicates the type of fault on which the drive is currently tripped This object returns a value between 1 and 25 which corresponds to one of the following fault conditions Value Name Fault...

Страница 15: ...is for monitoring the source of the speed setpoint reference States 1 through 9 are speed references States 10 through 18 are setpoint references This object must be in state 1 9 or 10 for the LAN to...

Страница 16: ...peed Source Selection This object mimics the functionality of the SPEED SOURCE key on the drive keypad It is used to determine whether the drive will get its speed setpoint reference from Drive Parame...

Страница 17: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG MHBAC e2...

Отзывы: