Configuration
2−84
l
EDSVF9383V−EXT EN 2.0
2.4.22.2
Operating inhibited (DISABLE)
When the operation is inhibited, the output stages are inhibited and all controllers are reset. When
the operation is inhibited, the drive cannot be started by the controller enable command.
l
The function is activated via three inputs:
– Control word CAN−CTRL.B8 from CAN−IN1
– Control word AIF−CTRL.B8 from AIF−IN
– Control word C0135.B8
l
All inputs are linked by an OR−operation.
2.4.22.3
Controller inhibit (CINH)
When the controller is inhibited, the output stages are inhibited and all controllers are reset.
l
The function is activated via seven inputs:
– Terminal X5/28 (LOW = controller inhibit)
– MONIT−TRIP (HIGH = In the MONIT function block the monitoring configured to TRIP has
tripped)
– Control word CAN−CTRL.B9 from CAN−IN1
– Control word AIF−CTRL.B9 from AIF−IN
– Control word C0135.B9
– Free input DCTRL−CINH1
– Free input DCTRL−CINH2
l
All inputs are linked by an OR−operation.
2.4.22.4
TRIP−SET
The drive is controlled into the state under C0581 and indicates EEr (external monitoring).
l
The function is activated via four inputs:
– Control word CAN−CTRL.B10 from CAN−IN1
– Control word AIF−CTRL.B10 from AIF−IN
– Control word C0135.B10
– Free input DCTRL−TRIP−SET
l
All inputs are linked by an OR−operation.
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...