Configuration
2−137
l
EDSVF9383V−EXT EN 2.0
2.4.47.1
Main setpoint channel
l
The signal at the input NSET−N is initially led by the function JOG−select.
l
The JOG function overrides the setpoint input NSET−N. I.e. a selected JOG value switches the
input inactive. After this, the following signal conditioning uses the JOG value.
l
The signals in the main setpoint channel are limited to the range of ±199.99 %.
2.4.47.2
JOG setpoints
The JOG setpoints are parameterised under C0039/1 ... C0039/15.
l
JOG setpoints are fixed values that are defined under C0039/1 ... C0039/15.
l
The JOG values can be activated via the inputs NSET−JOG*x.
l
The four inputs NSET−JOG*x are binary coded, so that 15 JOG values can be called.
l
The decoding for the enabling of the JOG values is carried out according to the following
table:
Output signal
1st input
NSET−JOG*1
2nd input
NSET−JOG*2
3rd input
NSET−JOG*4
4th input
NSET−JOG*8
NSET−n
0
0
0
0
JOG 1
1
0
0
0
JOG 2
0
1
0
0
JOG 3
1
1
0
0
JOG 4
0
0
1
0
JOG 5
1
0
1
0
JOG 6
0
1
1
0
JOG 7
1
1
1
0
JOG 8
0
0
0
1
JOG 9
1
0
0
1
JOG 10
0
1
0
1
JOG 11
1
1
0
1
JOG 12
0
0
1
1
JOG 13
1
0
1
1
JOG 14
0
1
1
1
JOG 15
1
1
1
1
0 = LOW
1 = HIGH
l
If all inputs are set to 0, the input NSET−N is active.
l
The number of inputs to be assigned depends on the number of JOG setpoints required. A
maximum of 4 inputs and thus 15 selection possibilities are available. Digital signal sources
are assigned under C0787 and the corresponding subcode.
Number of the required JOG setpoints
Number of the inputs to be assigned
1
at least 1
1 ... 3
at least 2
4 ... 7
at least 3
8 ... 15
4
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...