Configuration
2−128
l
EDSVF9383V−EXT EN 2.0
2.4.43
Monitor outputs of monitoring system (MONIT)
Purpose
The monitoring functions output digital monitor signals.
FB_monit
LU
OU
EER
..
..
..
..
P18
SD8
nErr
MONIT
Fig. 2−100
Monitor outputs of the monitoring system (MONIT)
Function
The MONIT−outputs switch to HIGH level if one of the monitoring functions responds.
The digital monitor signals respond dynamically, i.e.
l
depending on the state of the monitoring function, but
l
independent of the selected fault reaction.
Example
MONIT−LP1 (motor phase monitoring) responds if a cable disruption is detected in a motor
connection phase, although the fault reaction of LP1 is set to "Off" (C0597 = 3).
Tip!
l
Only with a corresponding signal conditioning it is possible to use the MONIT−outputs to
detect the cause of malfunction afterwards (e.g. storing the signal by using function block
FLIP).
l
A detailed description concerning monitoring /fault messages can be found in the chapter
"Troubleshooting and fault elimination".
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...