Communication
Control mode "Network (MCI/CAN)"
10.3.1
Pre-assignment of the data words
In the control mode "40: Network (MCI/CAN)" the process data words are already assigned
sensibly:
PDO
Signal
Assignment
Info
Port block LP_Network_In
RPDO1
wCtrl LA_NCtrl.wDriveControl
Control word
• See the "
"
chapter for a detailed description of the
individual control bits.
bCtrl1_B8 LA_NCtrl.bRFG_0
1
≡
Activate stop function
• Stop drive via stopping ramp (in
preparation).
bCtrl1_B11 LA_NCtrl.bSetDCBrake
1
≡
Activate DC-injection braking
Manual DC-injection braking (DCB)
bCtrl1_B12 LA_NCtrl.bJogSpeed1
Activation of fixed speed 1 ... 3
bCtrl1_B13 LA_NCtrl.bJogSpeed2
bCtrl1_B15 LA_NCtrl.bSetSpeedCcw
0
≡
Direction of rotation to the right (Cw)
1
≡
Direction of rotation to the left (Ccw)
RPDO2
wIn2 LA_NCtrl.nMainSetValue_a
Speed setpoint
• Scaling: 16384
≡
100 % rated speed
RPDO3
wIn3 -
-
...
...
RPDO8
wIn8
Port block LP_Network_Out
TPDO1
wState LA_NCtrl.wDriveControlStatus
Status word of the controller (based on DSP-
402)
• For bit assignment, see chapter entitled
"
TPDO2
wOut2 LA_NCtrl.nMotorSpeedAct_a
Actual speed value
• Scaling: 16384
≡
100 % rated speed
TPDO3
wOut3 LA_NCtrl.nOutputSpeedCtrl_a
Speed or slip controller output
• Scaling: 16384
≡
100 % rated speed
TPDO4
wOut4 -
-
...
...
TPDO8
wOut8