![Lenze 8200 vector series Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/lenze/8200-vector-series/8200-vector-series_mounting-instructions_1882277137.webp)
Commissioning
Parameter setting with E82ZBC keypad
Vector control
137
EDK82EV222 DE/EN/FR 13.0
Vector control
The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.
Switch−on sequence
Comment
1.
Connect keypad
2.
Ensure that controller inhibit is active after mains
connection
Terminal X3/28 = LOW
3.
Switch on the mains
4.
5.
The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
The
USEr
menu is active
6.
Go to the
ALL
menu
7.
Change to the
mode to configure the basic settings for
your drive
Blinking on the display:
0050
8.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
9.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
10.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
11.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
12.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
13.
Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
14.
Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for
the standard I/O)