ASHRAE class compliance information
Your server complies with ASHRAE class A2, A3 and A4 specifications. System performance may be
impacted when operating temperature is outside ASHRAE A2, A3 or A4 specifications. The restrictions to
ASHRAE A2 (10-35°C) support are as follows:
Server
status
Environment requirements
Operating
Ambient temperature
:
• ASHRAE class A2: 10–35°C (50–95°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 300 m (984 ft) of altitude increase.
• ASHRAE class A3: 5–40°C (41–104°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 175 m (574 ft) of altitude increase.
• ASHRAE class A4: 5–45°C (41–113°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 125 m (410 ft) of altitude increase.
Maximum altitude
: 3050 m (10 000 ft)
Relative humidity (non-condensing)
:
• ASHRAE class A2: 8%–80%; maximum dew point: 21°C (70°F)
• ASHRAE class A3: 8%–85%; maximum dew point: 24°C (75°F)
• ASHRAE class A4: 8%–90%; maximum dew point: 24°C (75°F)
Server off
Ambient temperature
:
5–45°C (41–113°F)
Shipping or
storage
Ambient temperature
:
-40–60°C (-40–140°F)
Maximum altitude
: 3050 m (10 000 ft)
Relative humidity (non-condensing)
: 8%–90%
Attention:
Airborne particulates and reactive gases acting alone or in combination with other environmental
factors such as humidity or temperature might pose a risk to the server. For information about the limits for
particulates and gases, see “Particulate contamination” on page 255.
Notes:
The restrictions to ASHRAE A2 (10-35°C) support are as follows:
• Mellanox ConnectX-6 adapters with Active Optical Cables (AOCs), ambient temperature cannot exceed
30°C
• With 8x 3.5-inch or 8x 2.5-inch or 16x 2.5-inch front drive bays + double-wide GPUs, ambient temperature
cannot exceed 30°C
• With 8x 3.5-inch or 16x 2.5-inch front drive bays + NVIDIA T4 GPU, ambient temperature cannot exceed
30°C
To comply with ASHRAE A3 (5-40°C) and A4 (5-45°C) specifications, the server models must meet the
following hardware configuration requirements:
• No Mellanox ConnectX-6 adapters
• No Broadcom 57454 10GBASE-T 4-port OCP Ethernet Adapter, 4XC7A08240
• No GPUs
256
ThinkSystem SR665 Setup Guide
Содержание ThinkSystem SR665
Страница 1: ...ThinkSystem SR665 Setup Guide Machine Types 7D2V and 7D2W ...
Страница 20: ...16 ThinkSystem SR665 Setup Guide ...
Страница 64: ...60 ThinkSystem SR665 Setup Guide ...
Страница 80: ...Figure 24 Cable routing for configuration 4 76 ThinkSystem SR665 Setup Guide ...
Страница 109: ...BP 3 NVMe 2 3 PCIe 3 BP 3 NVMe 4 5 PCIe 7 BP3 NVMe 6 7 PCIe 8 Chapter 3 Internal cable routing 105 ...
Страница 121: ...Figure 39 Cable routing for configuration 1 Chapter 3 Internal cable routing 117 ...
Страница 124: ...Figure 41 Cable routing for configuration 2 120 ThinkSystem SR665 Setup Guide ...
Страница 129: ...Figure 44 Cable routing for configuration 6 Chapter 3 Internal cable routing 125 ...
Страница 131: ...Chapter 3 Internal cable routing 127 ...
Страница 146: ...142 ThinkSystem SR665 Setup Guide ...
Страница 182: ...Connect any cables See Chapter 3 Internal cable routing on page 61 178 ThinkSystem SR665 Setup Guide ...
Страница 220: ...On GPU air baffle 216 ThinkSystem SR665 Setup Guide ...
Страница 240: ...236 ThinkSystem SR665 Setup Guide ...
Страница 248: ...244 ThinkSystem SR665 Setup Guide ...
Страница 253: ... Copyright Lenovo 2020 249 ...
Страница 256: ...252 ThinkSystem SR665 Setup Guide ...
Страница 266: ...262 ThinkSystem SR665 Setup Guide ...
Страница 267: ......
Страница 268: ......