• If a low impedance quick-connect coupling is used at the opposite (manifold) end of the hose, use positive
locking mechanisms to prevent loss of water when the hoses are disconnected. The connections must
minimize water spill and air inclusion into the system when they are disconnected.
Fill the heat exchanger with water
See this topic to learn how to fill ThinkSystem Rear Door Heat eXchanger V2 with water.
About this task
S038
CAUTION:
Eye protection should be worn for this procedure.
Attention:
Wear safety goggles or other eye protection whenever you fill, drain, or purge air or nitrogen from
the heat exchanger.
Procedure
Step 1. If the inner hose access panel is installed, lift and remove it from the heat exchanger.
Figure 68. Removing the inner hose access panel
62
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide