System x x3850 X6 and x3950 X6 Data Center Planning

  v1.0.3

                

                 FAST, AGILE, RESILIENT         CHOICE & FLEXIBILITY             SUPERIOR COOLING

     

   

   

     

     

The sixth generation of 
Enterprise X-Architecture 
technology, the X6 servers 
are fast in application 
performance, has an agile 
design and is a 
resilient platform that 
maximizes up time. 

The x3850 X6 server 
supports up to four 
redundant power supplies, 
and the x3950 X6 up to eight 
redundant power supplies, 
offering 750W, 900W or 
1400W capacities to meet 
your environmental needs. 

The systems provide 
Calibrated Vectored 
Cooling™, with up to ten 
redundant hot-swap fan 
packs and five fan zones with
N+1 fan redundancy per 
node. Each fan pack includes 
two counter-rotated dual-
motor fans.

Содержание System x3950 X6

Страница 1: ...gn and is a resilient platform that maximizes up time The x3850 X6 server supports up to four redundant power supplies and the x3950 X6 up to eight redundant power supplies offering 750W 900W or 1400W capacities to meet your environmental needs The systems provide Calibrated Vectored Cooling with up to ten redundant hot swap fan packs and five fan zones with N 1 fan redundancy per node Each fan pa...

Страница 2: ...vision History 1 0 0 Feb 24th 2014 Initial Release 1 0 1 October 1st 2014 Updates to format contacts webpage and email 1 0 2 April 21st 2015 Update to template 1 0 3 May 22nd 2015 Convert to Lenovo logo IMM2 Contributors Jerrod Buterbaugh System x Data Center Services Reviewers Matthew Archibald System x Data Center Services 2 ...

Страница 3: ...E CORD SELECTION 21 Switched and Monitored PDUs North America 21 Switched and Monitored PDUs International 22 Enterprise PDUs North America 23 Enterprise PDUs International 24 Front end PDUs North America 26 Front end PDUs International 26 Universal Rack PDUs 27 0U Basic PDUs North America 30 0U Basic PDUs International 30 SYSTEM X X6 POWER CORDS 31 System x x3850 X6 and x3950 X6 Worldwide PDU Pow...

Страница 4: ...ESS PROTECTION IP DECODE 100 60A THREE PHASE DELTA POWER CALCULATIONS 100 50A THREE PHASE DELTA POWER CALCULATIONS 101 30A THREE PHASE DELTA POWER CALCULATIONS 101 32A THREE PHASE DELTA POWER CALCULATIONS 102 16A THREE PHASE DELTA POWER CALCULATIONS 102 SYSTEM X6 DOCUMENTS 103 Helpful Links 103 Support 104 4 ...

Страница 5: ...ks comprises of a Compute Book Storage Book and I O Book The x3850 X6 server contains five fan zones with space for up to two fans per zone totaling ten hot swap fans with N 1 fan redundancy Up to four redundant hot swap 900W AC 1400W AC or 750W DC power supplies can be installed supporting N N N 1 and N configurations The x3950 X6 server contains ten fan zones with space for up to two fans per zo...

Страница 6: ...tage 200 240V AC 900W Max Input Amps 200 240V 5A DC Output Wattage 100 127V AC 900W Max Input Amps 100 127V 10A Nominal Input Voltage Range 100 127V AC 200 240V AC 50 60 Hz 1400W AC PSU Rating Part Number Information Power Supply Unit Part Numbers PN 44X4152 5000 altitude FC A54E PN 44X4150 5000 altitude FC A45D DC Output Wattage 200 240V AC 1400W Max Input Amps 200 240V 8A DC Output Wattage 100 1...

Страница 7: ...load and power requirements the x3850 X6 supports the following power supply installation One 900W One 1400W Two 900W Two 1400W Two 900W and two 1400W Four 900W Four 1400W Four 750W DC 7 Figure 1 x6 hot swap power supply ...

Страница 8: ...l grades such as Bronze Silver Gold Platinum and Titanium More information on 80 PLUS is available at http www 80PLUS org The power supplies used in System x X6 Systems are hot swap high efficiency 80 PLUS Platinum power supplies operating at 94 efficiency The efficiency varies by load as shown in the table below Power Efficiencies at Different Load Levels 20 load 50 load 100 load 80 PLUS Platinum...

Страница 9: ...for redundancy is also discussed x3850 X6 Power Supply Placement The power supplies are labeled from left to right when viewed from the rear of the server and are grouped in pairs as seen in the following picture Group A blue consists of PSU bay 1 and 3 and Group B green consists of PSU bay 2 and 4 PSU Bay 1 PSU Bay 2 PSU Bay 3 PSU Bay 4 Group A Group B 9 ...

Страница 10: ...n viewed from the rear of the server and are grouped in pairs as seen in the following picture Group A blue consists of PSU bay 1 3 5 and 7 and Group B green consists of PSU bay 2 4 6 and 8 PSU Bay 5 PSU Bay 6 PSU Bay 7 PSU Bay 8 PSU Bay 1 PSU Bay 2 PSU Bay 3 PSU Bay 4 Group A Group B 10 ...

Страница 11: ... power installation order for a x3850 X6 is as follows PS Bay 3 1st power supply to be installed PS Bay 2 2nd power supply to be installed PS Bay 1 3rd power supply to be installed PS Bay 4 4th power supply to be installed Note 1 2 or 4 PSU configurations are supported 3 PSU configurations are not supported The suggested power installation order for a x3950 X6 is as follows PS Bay 3 1st power supp...

Страница 12: ... as intended Power policies are discussed in the next section The following rules apply when connecting the server to input feeds for redundancy PSUs in group A and PSUs in group B must be balanced in both quantity and power output A B If the groups are not balanced the system will not boot As an example mixed wattages must be balanced Feed 1 group A 900W and 1400W PSUs Feed 2 group B 900W and 140...

Страница 13: ...Us Feed 1 Feed 2 Group A Group B Example of input feed wiring for 2 x 900W and 2 x 1400W PSUs Feed 1 Feed 2 Group A Group B 13 PS 3 Bay 1 Empty PS 4 Bay 4 Empty PS 2 Bay 2 1400W PS 1 Bay 3 1400W PS 1 Bay 3 900W PS 3 Bay 1 900W PS 2 Bay 2 900W PS 4 Bay 4 900W PS 1 Bay 3 1400W PS 2 Bay 2 1400W PS 3 Bay 1 900W PS 4 Bay 4 900W ...

Страница 14: ...e throttling When the server is booting Power Maximizer runs in the background to verify the available power in the system If Power Maximizer determines the available power in the system does not meet the systems power load based on the hardware installed and does not meet the Power Policy chosen in the IMM2 the system will not be allowed to boot Power Maximizer is discussed further in the followi...

Страница 15: ... first time regardless of the installed hardware or if you have not yet implemented a power policy You can set and change the Power Policy and System Power Configurations using the IMM2 web interface The power configurations and policies can be changed via the web CIM and ASU interfaces These settings cannot be changed by UEFI The following figure is the IMM2 power policy page 15 ...

Страница 16: ...set Power Limiting Power Capping The below image is a screenshot of the power capping policy page Note that setting a power capacity limit works by throttling the hardware s performance such as the CPU so it will produce less power Ensure you confirm your servers power consumption via the power monitoring tools in the IMM2 The power monitoring and allocation tool is discussed in the next section Y...

Страница 17: ...at all components installed in your server could potentially consume It is not a picture of the servers real time power usage For real time AC power usage use the Power History tab which is discussed in the next section The IMM2 will use the power supply utilization information and the DC power consumption information to ensure the server has enough power source s installed to power all of the har...

Страница 18: ...on on the history of your power consumption This is found under the Power History tab The below images are screen shots of a servers power history in chart and table format You can view the history of the servers AC or DC power consumption in minutes hours or days 18 ...

Страница 19: ...e policies allow This prevents resiliency and performance impacts such as unexpected throttling and system nodes powering off unexpectedly The System x Power Maximizer functions by running separate sub system specific workloads and then calculates a total worst case power consumption estimate The result of the System x Power Maximizer is reported to the respective management interhttp www Systemx ...

Страница 20: ...e Graphical Processing Unit or MIC Many Integrated Core I O adapters These adapters are characterized by running highly parallel graphic rendering workloads for complete characterization All tests are conducted using default uEFI BIOS settings The System x Power Configurator provides three groups of environmental information The first represents Idle or minimum power consumption the second is Maxi...

Страница 21: ...NEMA L6 30P 9 C19 3 C13 40K9615 1ph 200V 240V 60A 48A IEC 309 2P G 46M4003 System x 1U 9 C19 3 C13 AEM 60A 3 Phase PDU Attached 3ph Δ 208V 60A 27 7A ph IEC 309 3P G 9 C19 3 C13 46M4004 System x 1U 12 C13 AEM DPI PDU 40K9614 1ph 200V 240V 30A 24A NEMA L6 30P 12 C13 40K9615 1ph 200V 240V 60A 48A IEC 309 2P G 46M4005 System x 1U 12 C13 AEM 60A 3 Phase PDU Attached 3ph Δ 208V 60A 27 7A ph IEC 309 3P G...

Страница 22: ...6M4002 System x 1U 9 C19 3 C13 Active Energy Manager DPI PDU 40K9612 1ph 220V 240V 32A IEC 309 P N G 9 C19 3 C13 40K9613 1ph 220V 240V 63A IEC 309 P N G 40K9617 1ph 230V 240V 32A AUS NZ 3112 40K9618 1ph 220V 30A KSC 8305 40K9611 3ph Y 380V 415V 32A 32A ph IEC 309 3P N G 47C2495 3ph Y 380V 415V 16A 16A ph IEC 309 3P N G 46M4004 System x 1U 12 C13 AEM DPI PDU 40K9612 1ph 220V 240V 32A IEC 309 P N G ...

Страница 23: ... 3 Phase 60A PDU Basic Attached 3ph Δ 208V 60A 27 7A ph IEC 309 2P G 9 C19 3 C13 39M2816 System x DPI C13 Enterprise 1U PDU without line cord Monitored 40K9614 1ph 200V 240V 30A 24A NEMA L6 30P 12 C13 40K9615 1ph 200V 240V 60A 48A IEC 309 2P G 39Y8941 DPI Single Phase C13 Enterprise 1U PDU without line cord 40K9614 1ph 200V 240V 30A 24A NEMA L6 30P 12 C13 40K9615 1ph 200V 240V 60A 48A IEC 309 2P G...

Страница 24: ... IEC 309 3P N G 71762MX System x Ultra Density Enterprise PDU C19 1U PDU WW 40K9612 1ph 220V 240V 32A IEC 309 P N G 9 C19 3 C13 40K9613 1ph 220V 240V 63A IEC 309 P N G 40K9617 1ph 230V 240V 32A AUS NZ 3112 40K9618 1ph 220V 30A KSC 8305 40K9611 3ph Y 380V 415V 32A 32A ph IEC 309 3P N G 47C2495 3ph Y 380V 415V 16A 16A ph IEC 309 3P N G 39M2816 System x DPI C13 Enterprise 1U PDU without line cord Mon...

Страница 25: ...617 1ph 230V 240V 32A AUS NZ 3112 40K9618 1ph 220V 30A KSC 8305 40K9611 3ph Y 380V 415V 32A 32A ph IEC 309 3P N G 47C2495 3ph Y 380V 415V 16A 16A ph IEC 309 3P N G 39Y8948 DPI Single Phase C19 Enterprise 1U PDU without line cord 40K9612 1ph 220V 240V 32A IEC 309 P N G 6 C19 40K9613 1ph 220V 240V 63A IEC 309 P N G 40K9617 1ph 230V 240V 32A AUS NZ 3112 40K9618 1ph 220V 30A KSC 8305 40K9611 3ph Y 380...

Страница 26: ...ed 1ph 125V 30A 24A NEMA L5 30P 3 C19 39Y8939 30 amp 240V Front end U PDU Included 1ph 200V 240V 30A 24A NEMA L6 30P 3 C19 39Y8940 60 amp Front end U PDU Included 1ph 200V 240V 60A 48A IEC 309 2P G 3 C19 Front end PDUs International 39Y8934 DPI 32 amp Front end U PDU Included 1ph 200V 240V 32A IEC 309 P N G 3 C19 39Y8935 DPI 63 amp Front end U PDU Included 1ph 200V 240V 63A IEC 309 P N G 3 C19 26 ...

Страница 27: ... 4 3m 39M5283 39Y8953 DPI Universal Rack 1U PDU with Denmark LC Included 1ph 230V 16A 309 P N G 7 C13 Optional line cord 1 8m 39M5321 Optional line cord 2 5m 39M5322 Optional line cord 4 3m 39M5323 39Y8954 DPI Universal Rack 1U PDU with Israel LC Included 1ph 220V 16A Israel SI 32 7 C13 Optional line cord 1 8m 39M5309 Optional line cord 2 5m 39M5310 Optional line cord 4 3m 39M5311 39Y8955 DPI Univ...

Страница 28: ...ord 1 8m 39M5293 Optional line cord 2 5m 39M5294 Optional line cord 4 3m 39M5294 39Y8958 DPI Universal Rack 1U PDU with AUS NZ LC Included 1ph 230V 240V 15A Aus NZ 3112 Australia NZ 7 C13 Optional line cord 1 8m 39M5329 Optional line cord 2 5m 39M5330 Optional line cord 4 3m 39M5331 39Y8959 DPI Universal Rack 1U PDU with China LC Included 1ph 220V 16A China GB 2099 1 7 C13 Optional line cord 1 8m ...

Страница 29: ...5m 39M5342 Optional line cord 4 3m 39M5343 39Y8960 DPI Universal Rack 1U PDU Brazil Included 1ph 220V 240V 15A Brazil NBR 14136 7 C13 Optional line cord 1 8m 39M5357 Optional line cord 2 5m 39M5358 Optional line cord 4 3m 39M5359 39Y8961 DPI Universal Rack 1U PDU India Included 1ph 230V 16A India IS 6538 7 C13 Optional line cord 1 8m 39M5444 Optional line cord 2 5m 39M5445 Optional line cord 4 3m ...

Страница 30: ... Δ 208V 50A 23 09A ph CS8365L 12 C19 12 C13 0U Basic PDUs International 46M4131 System x 0U 24 C13 32A PDU Attached 1ph 200V 240V 32A IEC 309 P N G 24 C13 46M4122 System x 0U 24 C13 16A 3ph PDU Attached 3ph Y 380V 415V 16A 16A ph IEC 309 3P N G 24 C13 46M4143 System x 0U 12 C19 12 C13 32A 3ph PDU Attached 3ph Y 380V 415V 32A 32A ph IEC 309 3P N G 12 C19 12 C13 See the System x PDU Technical Refere...

Страница 31: ... 250V C13 to IEC 320 C20 Rack Power Cable 39Y7932 6263 4 3m 10A 100 250V C13 to IEC 320 C14 Rack Power Cable 47C2487 A3SS 1 2m 10A 100 250V 2 Short C13s to Short C14 Rack Power Cable 47C2488 A3ST 2 5m 10A 100 250V 2 Long C13s to Short C14 Rack Power Cable 47C2489 A3SU 2 8m 10A 100 250V 2 Short C13s to Long C14 Rack Power Cable 47C2490 A3SV 4 1m 10A 100 250V 2 Long C13s to Long C14 Rack Power Cable...

Страница 32: ... America or countries on a similar type power grid to connect the X6 system PSUs directly to NEMA 6 15R and NEMA 5 15R outlets Option P N Feature Code FC P N Description 39Y7931 6207 4 3M 10A 125V C13 to NEMA 5 15P 6369 1 8M 10A 125V C13 to NEMA 5 15P 6313 2 8m 10A 120V C13 to NEMA 5 15P 6351 1 8m 10A 250V C13 to NEMA 6 15P 6372 2 8m 10A 250V C13 to NEMA 6 15P 46M2592 A1RF 2 8m 10A 250V C13 to NEM...

Страница 33: ...s 6317 2 8m 10A 240V C13 to CNS 10917 3 Taiwan 69Y1988 6532 2 8m 10A 250V C13 to NBR 14136 Brazil 39Y7927 6269 2 8m 10A 250V C13 2P Gnd India 39Y7924 6211 2 8m 10A 250V C13 to AS NZ 3112 Australia NZ 6215 2 8m 10A 250V C13 to BS 1363 A UK 39Y7918 6213 2 8m 10A 250V C13 to DK2 5a Denmark 39Y7930 6222 2 8m 10A 250V C13 to IRAM 2073 Argentina 39Y7922 6214 2 8m 10A 250V C13 to SABS 164 S Africa 39Y791...

Страница 34: ...ased on your exact node configuration please download the System x Power Configurator tool The tool can be found here http www ibm com support entry portal docdisplay lndocid LNVO PWRCONF Configuration 1 Power Results 1x x3850 X6 4x E7 4830v2 105W 48x 4GB 1 35V Dimms 4x 2 5 300GB 15K SAS HDD 2x Single Port HBA 1 x ServeRAID Adapter 4x 1400W PSUs 1 Load Factor 85 represents steady state Linpack Tur...

Страница 35: ...resents steady state Linpack Turbo Mode OFF 2 2 Maximum represents steady state Linpack Turbo Mode ON Configuration 3 Power Results 1x x3850 X6 4x E7 8880v2 130W 48x 4GB 1 35V DIMMs 4x 2 5 300GB 15K SAS HDD 2x Single Port HBA 1 x ServeRAID Adapter 4x 1400W PSUs 1 Load Factor 85 represents steady state Linpack Turbo Mode OFF 2 Maximum represents steady state Linpack Turbo Mode ON 35 ...

Страница 36: ...4 x E7 8890v2 155W 48 x 4GB 1 35V DIMMs 4 x 2 5 300GB 15K SAS HDD 2 x Single Port HBA 1 x ServeRAID Adapter 4x 1400W PSUs 1 Load Factor 85 represents steady state Linpack Turbo Mode OFF 2 Maximum represents steady state Linpack Turbo Mode ON 36 ...

Страница 37: ...rks Typical PDU Configurations The following figures are examples of the connections from Single phase and Three phase PDUs for a x3850 X6 These meet the X6 power supply label ratings and is an example of what is possible although other valid configurations can be designed 1400W PSU Configuration Diagrams The 1400W power supply is covered in the following section for both North America and Interna...

Страница 38: ...undant N N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 38 ...

Страница 39: ... 4 x 1400W PSUs AC source redundant N N 200V 220V North America 39 ...

Страница 40: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 40 ...

Страница 41: ...undant N N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 41 ...

Страница 42: ...edundant N 1 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 42 ...

Страница 43: ... 4 x 1400W PSUs power supply redundant N 1 200V 220V North America 43 ...

Страница 44: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 44 ...

Страница 45: ...edundant N 1 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 45 ...

Страница 46: ...undant N N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 46 ...

Страница 47: ... 2 x 1400W PSUs AC source redundant N N 200V 220V North America 47 ...

Страница 48: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 48 ...

Страница 49: ...undant N N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 49 ...

Страница 50: ...edundant N 1 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 50 ...

Страница 51: ... 2 x 1400W PSUs power supply redundant N 1 200V 220V North America 51 ...

Страница 52: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 52 ...

Страница 53: ... 2 x 1400W PSUs power supply redundant N 1 220V 240V International 53 ...

Страница 54: ... Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 54 ...

Страница 55: ...dant N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 55 ...

Страница 56: ... 1 x 1400W PSUs non redundant N 200V 220V North America 56 ...

Страница 57: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 57 ...

Страница 58: ...dant N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 58 ...

Страница 59: ...and non redundant scenarios are covered For the following figures the following applies N N refers to AC source redundancy N 1 refers to power supply redundancy N refers to the system having enough power supplies to support the configuration budget and all supplies are connected to the same AC source Refer to the Reference Material on page 96 for additional clarification on N N N 1 and N configura...

Страница 60: ...undant N N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 60 ...

Страница 61: ... 4 x 900W PSUs AC source redundant N N 200V 220V North America 61 ...

Страница 62: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 62 ...

Страница 63: ...undant N N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 63 ...

Страница 64: ...dundant N 1 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 64 ...

Страница 65: ... 4 x 900W PSUs power supply redundant N 1 200V 220V North America 65 ...

Страница 66: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 66 ...

Страница 67: ...undant N 1 220V 240V International v Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 67 ...

Страница 68: ...undant N N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 68 ...

Страница 69: ... 2 x 900W PSUs AC source redundant N N 200V 220V North America 69 ...

Страница 70: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 70 ...

Страница 71: ...undant N N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 71 ...

Страница 72: ...dundant N 1 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 72 ...

Страница 73: ... 2 x 900W PSUs power supply redundant N 1 200V 220V North America 73 ...

Страница 74: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 74 ...

Страница 75: ...dundant N 1 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 75 ...

Страница 76: ...dant N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 76 ...

Страница 77: ... 1 x 900W PSUs non redundant N 200V 220V North America 77 ...

Страница 78: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 78 ...

Страница 79: ...dant N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 79 ...

Страница 80: ...cy power supply redundancy and non redundant scenarios are covered For the following figures the following applies N N refers to AC source redundancy N 1 refers to power supply redundancy N refers to the system having enough power supplies to support the configuration budget and all supplies are connected to the same AC source Refer to the Reference Material on page 96 for additional clarification...

Страница 81: ...e redundant N N 100V 127V North America Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 81 ...

Страница 82: ... 2 x 900W 2 x 1400W PSUs AC source redundant N N 200V 220V North America 82 ...

Страница 83: ... Refer to the following tables for PDU options for North America Switched and Monitored PDUs North America Enterprise PDUs North America Front end PDUs North America 0U Basic PDUs North America 83 ...

Страница 84: ...e redundant N N 220V 240V International Refer to the following tables for PDU options for International Switched and Monitored PDUs International Enterprise PDUs International Front end PDUs International 0U Basic PDUs International 84 ...

Страница 85: ...f Outlet Form Factor Front End Basic 39Y8939 Comes with PDU A11T 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9614 6012 12 C13 Front 1U Enterprise Basic 39Y8948 40K9614 6062 6 C19 Front 1U Ultra Density Enterprise Basic 71762NX 40K9614 6500 9 C19 Front 3 C13 Back 1U 0U 24 C13 Basic 46M4128 Attached 5924 24 C13 Front 0U Enterprise PDU C13 Monitored 39M2816 40K9614 6032 12 C13 Front 1U 1U 12 C13 Sw...

Страница 86: ...connector P N HBL360C6W This plug may have a short guide pin Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Front End Basic 39Y8940 Comes with PDU A11U 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9615 6013 12 C13 Front 1U Enterprise Basic 39Y8948 40K9615 6063 6 C19 Front 1U Ultra Density Enterprise Basic 71762NX 40K9615 6501 9 C1...

Страница 87: ...ee Phase Delta 41 55A Total Derated Circuit Capacity Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor 0U 24 C13 Basic 46M4125 Attached 5923 24 C13 Front 0U 1U 9 C19 3 C13 Switched Monitored 46M4167 Attached 5928 9 C19 Front 3 C13 Back 1U 87 ...

Страница 88: ...eded to mate with the plug on the PDU input line cord Matching receptacle listing CS8369 Matching connector listing CS8364 Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor 0U 12 C19 12 C13 Basic 46M414 0 Attached 5926 12 C19 Front 12 C13 Back 0U 0U 12 C19 12 C13 Switched Monitored 46M413 4 Attached 5931 12 C19 Front 12 C13 Back 0U 88...

Страница 89: ...ls on IEC309 Matching receptacle listing 460R9W IP 67 HUBBELL Hubbell receptacle P N HBL460R9W Matching connector listing 460C9W IP 67 HUBBELL Hubbell connector P N HBL460C9W Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Enterprise Basic 39Y8923 Attached 6061 6 C19 Front 1U Ultra Density Enterprise Basic 71763NU Attached 6051 9 C1...

Страница 90: ...ell connector P N HBL332C6 Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Front End Basic 39Y8934 Comes with PDU A11V 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9612 6014 12 C13 Front 1U DPI Enterprise Basic 39Y8948 40K9612 6064 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 40K9612 6502 9 C19 Front 3 C13 Back 1U 0U 2...

Страница 91: ...h PDU A11Y 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9617 6017 12 C13 Front 1U DPI Enterprise Basic 39Y8948 40K9617 6067 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 40K9617 6505 9 C19 Front 3 C13 Back 1U Enterprise C13 Monitored 39M2816 40K9617 6037 12 C13 Front 1U 1U 12 C13 Switched Monitored 46M4004 40K9617 5913 12 C13 Front 1U 1U 9 C19 3 C13 Switched Monitored 46M4002 40K9617 ...

Страница 92: ...11X 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9618 6018 12 C13 Front 1U DPI Enterprise Basic 39Y8948 40K9618 6068 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 40K9618 6506 9 C19 Front 3 C13 Back 1U Enterprise C13 Monitored 39M2816 40K9618 6038 12 C13 Front 1U 1U 12 C13 Switched Monitored 46M4004 40K9618 5914 12 C13 Front 1U 1U 9 C19 3 C13 Switched Monitored 46M4002 40K9618 5907 9 ...

Страница 93: ...ll connector P N HBL363C6W Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Front End Basic 39Y8935 Comes with PDU A11W 3 C19 Front U Enterprise C13 Basic 39Y8941 40K9613 6015 12 C13 Front 1U DPI Enterprise Basic 39Y8948 40K9613 6065 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 40K9613 6503 9 C19 Front 3 C13 Back 1U Ente...

Страница 94: ...tor listing 516C6W IP 67 HUBBELL Hubbell connector P N HBL516C6W Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Enterprise C13 Basic 39Y8941 47C2495 A3T1 12 C13 Front 1U DPI Enterprise Basic 39Y8948 47C2495 A3T3 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 47C2495 A3TC 9 C19 Front 3 C13 Back 1U Enterprise C13 Monitored...

Страница 95: ...HBL532C6W Compatible with PDU Name PDU Part Number Line Cord Part Number PDU Line Cord FC Number Type of Outlet Form Factor Enterprise C13 Basic 39Y8941 40K9611 6016 12 C13 Front 1U DPI Enterprise Basic 39Y8948 40K9611 6066 6 C19 Front 1U DPI Ultra Density Enterprise Basic 71762NX 40K9611 6504 9 C19 Front 3 C13 Back 1U 0U 12 C19 12 C13 Basic 46M4143 Attached 5927 12 C19 Front 12 C13 Back 0U Enterp...

Страница 96: ...PSU redundancy is where N is the minimum number of PSUs needed to keep the system operational plus one PSU for redundancy N 1 is used when a system needs only to tolerate a single PSU failure and stay operational See example diagrams in Typical PDU Configurations above Think of N 1 as having one PSU as a hot spare N N and N 1 Examples Notice in the N 1 diagrams below that there are two sources Typ...

Страница 97: ... IEC 320 Connectors 97 ...

Страница 98: ... Supplies And Other Portable Power Supplies C7 Female C8 Male 2 5A Laptop Power Supplies And Other Portable Power Supplies C13 Female C14 Male 10A Desktop Computers Monitors Switches And Servers C15 Female C16 Male 10A Used In Hot Conditions Since It Is Rated To 1200 C 2480 F Unlike C13 C14 Which Is Rated To 700 C 1580 F C19 Female C20 Male 16A Blade Chassis Flex System High power Servers UPSs PDU...

Страница 99: ... IEC 309 Pin Sleeve Plug Decode 99 ...

Страница 100: ... Ingress Protection IP Decode Example IP67 Ingress Protection Dust Tight Temporary Immersion 60A Three Phase Delta Power Calculations 100 ...

Страница 101: ... 50A Three Phase Delta Power Calculations 30A Three Phase Delta Power Calculations 101 ...

Страница 102: ... 32A Three Phase Delta Power Calculations 16A Three Phase Delta Power Calculations 102 ...

Страница 103: ...y portal docdisplay lndocid LNVO PWRCONF Hubbell Twist Lock Plug Outlet Catalog Includes NEMA Outlets http www hubbellcatalog com wiring catalogpages section b pdf Hubbell Pin Sleeve Plug Outlet Catalog Includes IEC309 Outlets http www hubbellcatalog com wiring catalogpages section E pdf System x Configuration and Options Guide http www ibm com systems xbc cog System x BladeCenter and System x Ref...

Страница 104: ... Support 104 ...