Table 34. Monitor and video problems (continued)
• Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
• See Chapter 5 “Parts listing, Lenovo System x3750 M4 Type 8753” on page 203 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units (FRU).
• If an action step is preceded by
(Trained service technician only),
that step must be performed only by
a Trained service technician.
Symptom
Action
The monitor has screen
jitter, or the screen image is
wavy, unreadable, rolling, or
distorted.
1. If the monitor self-tests show that the monitor is working correctly, consider
the location of the monitor. Magnetic fields around other devices (such as
transformers, appliances, fluorescents, and other monitors) can cause screen
jitter or wavy, unreadable, rolling, or distorted screen images. If this happens,
turn off the monitor.
Attention:
Moving a color monitor while it is turned on might cause screen
discoloration.
Move the device and the monitor at least 305 mm (12 in.) apart, and turn on
the monitor.
Notes:
a. To prevent diskette drive read/write errors, make sure that the distance
between the monitor and any external diskette drive is at least 76 mm (3 in.).
b. Non-Lenovo monitor cables might cause unpredictable problems.
2. If the server is attached to a KVM switch, bypass the KVM switch to eliminate it
as a possible cause of the problem; connect the monitor cable to the correct
connector on the rear of the server. If the image clears, replace the KVM switch.
3. Reseat the monitor cable.
4. Try the monitor on a different server. If it still does not work, replace the cable,
then the monitor.
5. Replace the adapter, if installed.
6. (Trained service technician only) Replace the system board.
Wrong characters appear on
the screen.
1. Verify that the language and locality settings are correct for the keyboard and
operating system.
2. If the wrong language is displayed, update the server firmware to the latest level
(see “Updating the firmware” on page 131) with the correct language.
Observable problems
Use this information to solve observable server problems.
Table 35. Symptoms and user actions for observable problems
• Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
• See Chapter 5 “Parts listing, Lenovo System x3750 M4 Type 8753” on page 203 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units (FRU).
189
Содержание System x3750 M4
Страница 1: ...Lenovo System x3750 M4 Installation and Service Guide Machine Type 8753 ...
Страница 6: ...iv Lenovo System x3750 M4 Installation and Service Guide ...
Страница 144: ...130 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 170: ...156 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 319: ...Adapter SAS signal connector SAS signal cable Chapter 6 Removing and replacing components 305 ...
Страница 321: ...Adapter SAS signal connector SAS signal cable Chapter 6 Removing and replacing components 307 ...
Страница 324: ...8x2 5 inch backplane 310 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 492: ...478 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 522: ...508 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 956: ...942 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 960: ...946 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 968: ...Taiwan BSMI RoHS declaration 954 Lenovo System x3750 M4 Installation and Service Guide ...
Страница 981: ......
Страница 982: ...Part Number 00MV562 Printed in China 1P P N 00MV562 1P00MV562 ...