LZP-4

ZONE CONTROL PANEL

INSTALLATION INSTRUCTIONS FOR ZONE CONTROL PANELS

USED WITH LENNOX HEATING AND COOLING EQUIPMENT

Shipping & Packing List

Package 1 of 1 contains the following:

(1) Model LZP-4 Zone Control Panel
(1) Model 88K38 Temperature Sensor
(1) Installation Instructions
(1) Owners Manual
(1) Warranty Card

Required Components (ordered separately):

24 VAC Transformer

– The size of the transformer

needed is determined by the total power
requirements for the control panel, thermostats and
dampers. The control panel and thermostat together
require 10VA. The dampers require 10VA each. The
size of the transformer will depend on the greatest
number of dampers that could be energized at any
given time.

NOTE

– When using power close, spring

open dampers, at least one zone’s dampers will not
be energized during a heating or cooling call.

Thermostats

– see selection chart on page 5.

Only 24-volt electronic thermostats with a common
connection are to be used with this zoning panel. Do
not use mechanical or power robbing thermostats.

Dampers

– 2 or 3-wire, 24-volt dampers required.

2-wire, power closed/spring open preferred.

Application

• Up to four zones

• Single or two-stage furnace

• Single or two-stage air conditioner

• Single or two stage-heat pump with one stage of

electric auxiliary heat; separate emergency heat
output available

• Single or two stage-heat pump with single-stage fossil

fuel auxiliary heat (dual fuel system)

Features

• Adjustable high and low discharge air temperature limits

• Vacation (central) mode setting

• Staging control by number of zones calling

• Staging control by time or thermostat input

• Auxiliary heat control by time or thermostat input

• Standard single-stage heat/cool thermostats or heat

pump thermostats can be used to control heat pumps
or multi-stage equipment

• Dual fuel system compatible

• ON/OFF duct air purge control

• Visible LED outputs

• Time Delay Override

• Zone1 or Any Zone mode control

• 2 or 3-wire damper compatibility

ZONING SYSTEM

TABLE 1 – TRANSFORMERS

Part Number

Size

Voltage Description

10P17

40VA

120/208/240V-24V

10P87

50VA

120/208/240V-24V

12P61

75VA

120/208/240V-24V

83P74

4" Square Electrical Box

Содержание Zoning System LZP-4

Страница 1: ...connection are to be used with this zoning panel Do not use mechanical or power robbing thermostats Dampers 2 or 3 wire 24 volt dampers required 2 wire power closed spring open preferred Application...

Страница 2: ...Page 2 FIGURE 1 LZP 4 CONTROL PANEL SCHEMATIC...

Страница 3: ...ES AUX MINUTES A C 45 140 B D CL 40 HT 160 OFZONES TO STAGE DAS SENSOR Lennox LXZ 4 49M9201 Rev 0 Install the control panel indoors only If the Vacation and or Emergency Heat switches on the control p...

Страница 4: ...mal position Sizing the Transformer The system requires approximately 10 VA for the control panel and thermostats and 10 VA for each damper The size of the transformer will depend on the greatest numb...

Страница 5: ...one 1 HEAT COOL R C W Y G O B 1 2 HEAT COOL R C W Y G 1 2 Heat Pump Optional W2 and Y2 3 4 7 Optional W2 and Y2 3 4 7 Any Zone Heat Pump HEAT PUMP R C W1 Y1 G O 8 HEAT PUMP R C W1 Y1 G O 8 Electric Op...

Страница 6: ...T COOL TERMINAL DEFINITIONS Thermostat Terminal Function R 24 VAC Hot C 24 VAC Common W 1st Stage Heat W2 2nd Stage Heat Y 1st Stage Cool Y2 2nd Stage Cool G Fan O Cooling Mode B Heating Mode TABLE 2b...

Страница 7: ...Input First Stage Second Stage First Stage Second Stage First Stage Second Stage Auxiliary Emergency Setup 1 Stat Type output Cool Cool Electric Electric Compressor Compressor Heat Heat Furnace Furnac...

Страница 8: ...in 0 Panel Y1 O G Y1 Y2 O G W1 W2 B Y1 B G Y1 Y2 B G Zone 1 Output Heat Pump Panel Y G Y 2S G or By Aux Timer By Emergency W W 2S or by Gas Heat Cool Input by Stage Timer Only Switch Only Stage Timer...

Страница 9: ...ss damper and duct should be sized to handle the excess pressure created when the smallest zone is operating alone worst case To size the bypass damper subtract the total air volume capacity of the sm...

Страница 10: ...AGRAM 1 POWER CLOSE SPRING OPEN DAMPER WIRING DIAGRAM 2 DAMPER WIRING WITH SEPARATE TRANSFORMER Field Wiring Thermostats DIAGRAM 3 HEAT COOL THERMOSTAT WITHOUT O AND B TERMINALS DIAGRAM 4 HEAT COOL TH...

Страница 11: ...ield Wiring Thermostats continued DIAGRAM 5 HEAT PUMP THERMOSTAT DIAGRAM 6 HEAT PUMP THERMOSTAT SignatureStat 51M28 AND ELITE 49M57 DIAGRAM 7 HEAT PUMP THERMOSTAT SignatureStat 51M28 AND ELITE 49M57 D...

Страница 12: ...Page 12 Field Wiring HVAC Equipment Furnace and Air Conditioner DIAGRAM 8 SINGLE STAGE FURNACE AND AIR CONDITIONER DIAGRAM 9 TWO STAGE FURNACE AND TWO STAGE AIR CONDITIONER...

Страница 13: ...Page 13 Field Wiring HVAC Equipment Heat Pumps DIAGRAM 10 SINGLE STAGE HEAT PUMP DIAGRAM 11 TWO STAGE HEAT PUMP...

Страница 14: ...Page 14 Field Wiring HVAC Equipment Heat Pumps continued DIAGRAM 12 TWO STAGE HEAT PUMP WITH DUAL FUEL...

Страница 15: ...ero thermostat inputs or of Zones Calling control staging SWITCHES ARE SHOWN AS BLACK AUX MINUTES With the control panel configured for ZONE 1 operation auxiliary heat can only be controlled by time C...

Страница 16: ...SELECTOR This switch allows the homeowner to switch from normal operation ZONE to a VACATION mode In VACATION mode switch in the ON position Zone 1 becomes the only zone from which a call for heating...

Страница 17: ...g LED will stop flashing DAMPER OPERATION The NO output will be energized and the NC output will be de energized for any zone not calling for heating or cooling while the equipment output is energized...

Страница 18: ...NO PURGE is the preferred method of purge when this zone panel is applied to Lennox equipment HEATING OPERATION HEAT PUMP SYSTEMS When a zone makes a call for Heat the Y1 G and B output terminals wil...

Страница 19: ...call If you choose not to use the SignatureStat or Elite thermostats dual fuel feature or wish to use a standard heat pump thermostat to control the dual fuel system the furnace will turn on with an...

Страница 20: ...Page 20 System Setup Flowchart...

Страница 21: ...Page 21 System Setup Flowchart continued...

Страница 22: ...Page 22 System Setup Flowchart continued...

Страница 23: ...Page 23 System Setup Flowchart continued...

Страница 24: ...Page 24 System Setup Flowchart continued...

Страница 25: ...Page 25 System Setup Flowchart continued...

Страница 26: ...t to place the senor past the take offs High static pressure must be corrected Bypass tap is too close to inlet of air handler Adjust bypass tap in the return air duct so that is further away from the...

Страница 27: ...EC change setting to GAS HVAC system has built in duct purge Set PURGE NO PURGE jumper on control panel to NO PURGE An open or short in the DAS sensor has been detected Install or repair the sensor Em...

Страница 28: ...ng the resistance at room temperature warm the tip of the sensor by holding it in the palm of your hand and take another resistance reading This reading should be noticeable lower than the room temper...

Отзывы: