Multi Variable Air Conditioners Two-way Cassette Type Indoor Unit
19
5.3 Connection of Communication Wire Between Indoor Unit and Outdoor
Unit (or indoor unit)
(1) Detach the electric box cover.
(2) Let the Communication cable pass through the wiring through-holes.
(3) Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board, as
shown in Fig5.3.1.
Fig 5.3.1 Fig 5.3.2
(4) Fix the communication cable with clamp of electric box.
(5) In order to ensure the reliability of communication between IDU and ODU and the
communication among each IDU, add a matched resistance (supplied in a package
before ex-factory) on the wiring board of the last indoor unit in a series connection. The
matched resistance should be connected in parallel between terminal screw D1 and D2,
as shown in Fig 5.3.2.
5.4 Connection of Communication Wire for Wired Controller
(1) Detach the electric box cover.
(2) Let the communication wire pass through the wiring through-holes.
(3) Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board.
(4) Fix the communication wire with clamp.