5 Wiring Work 

NOTE:

Units must be grounded securely, or it may cause electric shock. 

(1)  Please carefully read the nameplate and the wiring diagram before carry out the wiring 

work, incorrect wiring could cause malfunction or even damage the unit. 

(2)  The capacity of power supply must be sufficient and the sectional area of wires in the 

room should be above 2.5mm

2

(3)  The unit should be powered by independent circuit and specific socket. 
(4)  The wiring should be in accordance with related regulations in order to ensure the units 

operate reliably. 

(5)  Install  circuit  breaker  for  branch  circuit  according  to  related  regulations  and  electrical 

standards. 

(6)  All  wiring  must  use  pressure  terminal  or  single  wire.  Multi-twisted  wire  that  connects 

directly to the wiring board may cause fire hazard. 

(7)  Keep cable away from refrigerant piping, compressor and fan motor. 
(8)  Do  not  alter  the  inner  wires  of  air  conditioner.  Manufacturer  does  not  assume             

responsibility for damage or abnormal operation due to this reason. 

(9)  If  the  unit  is  installed  in  places  with  strong  electromagnetic  interference,  it's 

recommended  to  use  twin-twisted  shield  wire.  During  wire  connection,  please  pay 
attention that the metal shield layer of the twin-twisted wire must be grounded (outer case) 
in order to prevent the unit from electromagnetic interference. 

(10) The  communication  wires  should  be  separated  from  power  cord  and  connection  wire 

between indoor unit and outdoor unit.   

(11) If the project needs higher static pressure, you can set it through the wired controller. 
(12) The appliance must be fitted with means for disconnection from the supply mains having 

a  contact  separation  in  all  poles  that  provide  full  disconnection  under  overvoltage 
category  III  conditions,  and  these  means  must  be  incorporated  in  the  fixed  wiring  in 
accordance with the wiring rules. 

5.1 Connection of Wire and Patch Board Terminal 

(1)  Connection of single branch wire (as shown in Fig 5.1.1). 

1)  Use a stripper to strip away about 25mm of the insulation layer at the end of single 

branch line so that the single-core wire can be exposed. 

2)  Remove the wiring screws on the terminal board. 
3)  Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in 

accordance with screw. 

4)  Lead  the  screw  across  the  circle  of  the  single  branch  line  and  fix  it  on  the  wiring 

board. 

(2)  Connection of multi-twisted wire (as shown in Fig 5.1.2). 

1)  Use a wired stripper to strip away about 10mm of the insulation layer at the end of 

Содержание VE2C009N432U

Страница 1: ...32U VE2C017N432U VE2C019N432U VE2C021N432U VE2C024N432U Thank you for selecting LENNOX air conditioners Please read this manual carefully before operation and keep it for further reference VRF Indoor...

Страница 2: ......

Страница 3: ...perly select the model according to actual using environment otherwise it may impact the using convenience 4 This product has gone through strict inspection and operational test before leaving the fac...

Страница 4: ...Notice This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given s...

Страница 5: ...Drainage System Testing 11 4 4 Panel Installation 15 4 5 Installation of Wired Controller 16 5 Wiring Work 17 5 1 Connection of Wire and Patch Board Terminal 17 5 2 Power Cord Connection 18 5 3 Connec...

Страница 6: ...s in Manual Cover is a partial unit complying with partial unit of IEC 60335 2 40 2018 and must only be connected to other units that have been confirmed as complying to corresponding partial unit req...

Страница 7: ...n welding pipes Never short circiut or cancel the pressure switch to prevent unit damage Please firstly connect the wired controller before energization otherwise wired controller can not be used Befo...

Страница 8: ...lease don t set the room temperature too low and keep the temperature difference between indoor and outdoor unit within 5 If anything abnormal happens such as burning smell please power off the unit a...

Страница 9: ...Temp C Dry Bulb Temp C Wet Bulb Temp C Rated Cooling 27 19 35 24 Rated Heating 20 15 7 6 3 Preparations for Installation NOTE this picture is for reference only please refer to the actual product the...

Страница 10: ...be used together with the hanger bolt for installing the unit 12 Washer fixing plate 4 Prevent the washer from falling off 3 2 Installation Position Selection 1 The location should be able to withstan...

Страница 11: ...e unit shall be installed in accordance with national standards or local regulations Only qualified personnel can carry out installation work please contact with local dealer before installation Make...

Страница 12: ...Fig 3 3 2 Wire type Total length of communication wire between indoor unit and indoor unit outdoor unit m Wire diameter mm2 Wire standard Remark Light Ordinary polyvinyl chloride sheathed cord 60227...

Страница 13: ...rcuit breaker Model Power Supply Air Switch Capacity A Minimum Sectional Area of Grounding Wire mm2 Minimum Sectional Area of Power Cord mm2 VE2C009N432U 220 240V 1ph 50Hz 208 230V 1ph 60Hz 6 1 1 VE2C...

Страница 14: ...ling work must be carried out by qualified personnel 4 1 2 Suspend The Indoor Unit 1 Drill bolt holes and install bolts 1 Stick the paper pattern on the installation position drill 4 holes according t...

Страница 15: ...rn Refer to paper pattern of installation for ceiling opening dimension The center of ceiling opening is indicated on the paper pattern Fix the paper pattern to the unit with 4 screws and fix the corn...

Страница 16: ...of Drainage Pipe 1 It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which are likely to produce corrosive or peculiar smell to prevent the smell from entering...

Страница 17: ...larger diameter than the connection pipes PVC pipe outside diameter 25mm thickness 1 5mm 2 Keep drainage pipe short and sloping downwards at a gradient of at least 1 for preventing forming air bubble...

Страница 18: ...4 Fig 4 3 5 9 Drainage pipes should have a downward slope of at least 1 2 in order to prevent pipes from sagging install hanger bracket at intervals of 1000 1500mm Fig 4 3 4 10 The installation heigh...

Страница 19: ...he water over the electrical components e g water pump etc 1 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can chec...

Страница 20: ...oper decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that it s clearance free between decoration panel and ceiling board after installation if not please adjust the...

Страница 21: ...the 2 screws in the middle of panel 4 Install the air inlet grille and then lock the clasp 5 Tighten the screw until the thickness of sealing material between panel and indoor unit is about 5 8mm Fig...

Страница 22: ...use twin twisted shield wire During wire connection please pay attention that the metal shield layer of the twin twisted wire must be grounded outer case in order to prevent the unit from electromagn...

Страница 23: ...o tighten the terminal screw Fig 5 1 1 Fig 5 1 2 5 2 Power Cord Connection NOTICE Every unit should be equipped with a circuit breaker for short circuit and overload protection During operation all in...

Страница 24: ...ox 5 In order to ensure the reliability of communication between IDU and ODU and the communication among each IDU add a matched resistance supplied in a package before ex factory on the wiring board o...

Страница 25: ...equipped with signal receiver and available for wireless control respectively 5 5 Wiring Instructions of Wired Controller and Indoor Units Network 1 Communication wire of indoor unit and outdoor unit...

Страница 26: ...Multi Variable Air Conditioners Two way Cassette Type Indoor Unit 21 Fig 5 5 1...

Страница 27: ...l detergent Please contact after sales service staff if there is abnormal situation 6 1 Cleaning of Filter 1 Remove the air filter on the air inlet for cleaning Use a dust catcher or water to clean it...

Страница 28: ...Master Indoor Unit Error d6 Outlet Pipe Temperature Sensor Error db Special Code Field Debugging Code L8 Power Insufficiency Protection d7 Humidity Sensor Error C0 Communication Error L9 Quantity Of...

Страница 29: ...peration light Timer light Error code display sheet Error code C0 A0 A3 A 4 L0 L1 L3 L5 d1 d3 d4 d6 d7 E0 db Power light Operati on light Timer light Error description Communication error To be debugg...

Страница 30: ...emperature is higher than 43 C Poor cooling effect The filter is dirty or blocked Too heavy heat load of room e g too many people Door or windows is open Inlet and outlet of IDU are blocked Setting te...

Страница 31: ......

Страница 32: ...s at 1 305 718 2901 lennoxglobalhvac lennoxintl com C 2020 Lennox Industries Inc For a complete list of the registered and common law trademarks owned by Lennox Industries Inc please visit www lennoxg...

Отзывы: