TS − 3 to 5 Ton R−410A Air Conditioners 

/ Page 9

ARI RATINGS − INDOOR COIL / AIR HANDLER SUBSTITUTION 

Substituting Coils in the ARI Tables

Most R−22 and R−410A indoor coils and air handlers are
the same except for the factory installed expansion
device. C33 coils can be used in place of the CX34 coils,
CB26UH−R, CB27UH, and CB30M air handlers can be
used in place of the CBX26UH, CBX27UH, and CBX32M,
respectively.

The expansion device is based on the size of the outdoor
unit. The factory installed RFC or TXV on the
C33/CB26UH−R/CB27UH/CB30M must be replaced to
correspond to the outdoor unit. The correct TXV’s are:

1.5−3 ton air conditioners

37L51

3.5 ton air conditioners

39L72

4−5 ton air conditioners

91M02

Example:

A four−ton air conditioner is being installed. The ARI table
shows that CBX32M−048 is a matching air handler. A
CB30M−51 with a 91M02 TXV can be used in its place.

UP−FLOW COILS

R−410A

R−22

CX34−18/24A−6F

=

C33−24A−2

CX34−18/24B−6F

=

C33−24B−2

CX34−18/24C−6F

=

C33−24C−2

CX34−19A−6F

=

C33−19A−2

CX34−25A−6F

=

C33−25A−2

CX34−25B−6F

=

C33−25B−2

CX34−30A−6F

=

C33−30A−2

CX34−30B−6F

=

C33−30B−2

CX34−30C−6F

=

C33−30C−2

CX34−31A−6F

=

C33−31A−2

CX34−31B−6F

=

C33−31B−2

CX34−36A−6F

=

C33−36A−2

CX34−36B−6F

=

C33−36B−2

CX34−36C−6F

=

C33−36C−2

CX34−38A−6F

=

C33−38A−2

CX34−38B−6F

=

C33−38B−2

CX34−42B−6F

=

C33−42B−2

CX34−43B−6F

=

C33−43B−2

CX34−43C−6F

=

C33−43C−2

no equivalent

C33−44C−2

CX34−44/48B−6F

=

C33−48B−2

CX34−44/48C−6F

=

C33−48C−2

CX34−49C−6F

=

C33−49C−2

CX34−50/60C−6F

=

C33−50/60C−2

CX34−60D−6F

=

C33−60D−2

CX34−62C−6F

=

C33−62C−2

CX34−62D−6F

=

C33−62D−2

AIR HANDLERS

R−410A

R−22

CBX26UH−018

=

CB26UH−018−R

CBX26UH−024

=

CB26UH−024−R

CBX26UH−030

=

CB26UH−030−R

CBX26UH−036

=

CB26UH−036−R

CBX26UH−042

=

CB26UH−042−R

CBX26UH−048

=

CB26UH−048

CBX26UH−060

=

CB26UH−060−R

CBX27UH−018/024

=

CB27UH−018/024

CBX27UH−030

=

CB27UH−030

CBX27UH−036

=

CB27UH−036

CBX27UH−042

=

CB27UH−042

CBX27UH−048

=

CB27UH−048

CBX27UH−060

=

CB27UH−060

CBX32M−018/024

=

CB30M−21/26

CBX32M−030

=

CB30M−31

CBX32M−036

=

CB30M−41

CBX32M−042

=

CB30M−46

CBX32M−048

=

CB30M−51

CBX32M−060

=

CB30M−65

CBX32MV−all

no equivalent

Содержание TSA036S4

Страница 1: ...or Design Sequence A 1st Generation B 2nd Generation Brand Family T T Classt Product Line Unit Type S Split System Air Conditioner Nominal Cooling Capacity Tons 036 3 Tons 042 3 5 Tons 048 4 Tons 060...

Страница 2: ...on utility bills and help protect the environment Applications SEER up to 14 0 3 through 5 ton Three phase power supply Vertical air discharge allows concealment behind shrubs at grade level or out o...

Страница 3: ...between them During compression one scroll remains stationary while the other scroll orbits around it Gas is drawn into the outer pocket the pocket is sealed as the scroll rotates As the spiral moveme...

Страница 4: ...for outdoor units High density polyethylene structural material is lightweight sturdy sound absorbing and will withstand the rigors of the sun heat cold moisture oil and refrigerant Will not mildew or...

Страница 5: ...cessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1 C0SN...

Страница 6: ...mpressor Rated load amps 10 4 5 8 13 5 6 0 13 7 6 2 4 8 15 6 7 8 5 8 Power factor 85 84 83 81 90 92 88 90 91 90 Locked rotor amps 73 38 88 44 83 1 41 30 4 110 52 35 5 Outdoor Fan Motor Full load amps...

Страница 7: ...ained between two units 48 in 1219 mm clearance required on top of unit See NOTES See NOTES See NOTES See NOTES CONTROL BOX OUTDOOR SOUND DATA 1 Unit Model No Octave Band Sound Power Levels dBA re 10...

Страница 8: ...S LIQUID LINE CONNECTION TOP VIEW BASE SECTION 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed B C A OPTIONAL UNIT STAND OFF KIT 4 Field...

Страница 9: ...6F C33 24A 2 CX34 18 24B 6F C33 24B 2 CX34 18 24C 6F C33 24C 2 CX34 19A 6F C33 19A 2 CX34 25A 6F C33 25A 2 CX34 25B 6F C33 25B 2 CX34 30A 6F C33 30A 2 CX34 30B 6F C33 30B 2 CX34 30C 6F C33 30C 2 CX34...

Страница 10: ...43B 6F 4 G60UHV 36B 090 2 37L51 35 600 14 00 12 00 2965 CX34 50 60C 6F 4 G60UHV 60C 110 2 37L51 36 400 14 00 11 60 3140 CX34 50 60C 6F 4 G61MPV 60C 091 2 37L51 36 400 14 00 11 60 3140 CX34 50 60C 6F 4...

Страница 11: ...00 2965 4 CBX32MV 048 Multi Position 2 37L51 36 200 14 00 12 00 3015 3 CBX27UH 042 Up Flow Horizontal 2 37L51 TSA042S4 3 5 TON Up Flow Indoor Coils Up Flow Coils 40 000 13 00 10 80 3700 3 CX34 38A B...

Страница 12: ...L72 41 000 14 00 11 50 3495 CR33 60D F 4 G71MPP 60D 135 2 39L72 41 000 14 00 11 50 3495 CR33 60D F 4 G61MPV 60D 135 2 39L72 41 000 14 00 11 50 3515 CR33 50 60C F 4 G60DFV 60C 110 2 39L72 41 000 14 00...

Страница 13: ...11 50 3575 CH33 50 60C 2F 4 G71MPP 60C 110 2 39L72 41 500 13 50 11 50 3575 CH33 50 60C 2F 4 G61MPV 60C 110 2 39L72 41 500 13 50 11 50 3615 CH33 50 60C 2F 4 G71MPP 60C 090 2 39L72 41 500 13 50 11 50 3...

Страница 14: ...G61MPV 60D 135 Factory TXV 48 500 14 00 11 50 4080 CX34 60D 6F 4 G71MPP 60D 135 Factory TXV 48 500 14 00 11 50 4110 CX34 49C 6F 4 G60UHV 60C 110 Factory TXV 48 500 14 00 11 50 4155 CX34 49C 6F 4 G61MP...

Страница 15: ...320 CH33 43C 2F 4 G71MPP 60C 110 2 91M02 47 500 13 50 11 00 4320 CH33 43C 2F 4 G61MPV 60C 111 2 91M02 47 500 13 50 11 00 4180 CH33 48C 2F 4 G61MPV 60C 090 2 91M02 47 500 13 50 11 00 4180 CH33 48C 2F 4...

Страница 16: ...M02 48 500 14 00 12 00 4045 CH33 62D 2F 4 G60UHV 60D 135 2 91M02 48 500 14 00 11 50 4100 CH33 62D 2F 4 G71MPP 60D 135 2 91M02 48 500 14 00 11 50 4100 CH33 62D 2F 4 G61MPV 60D 135 2 91M02 Air Handlers...

Страница 17: ...C 6F 4 G71MPP 60C 110 Factory TXV 62 000 13 50 11 50 5420 CX34 62C 6F 4 G61MPV 60C 090 Factory TXV 62 000 13 50 11 50 5420 CX34 62C 6F 4 G71MPP 60C 090 Factory TXV 62 000 14 00 11 50 5250 CX34 62C 6F...

Страница 18: ...2F 4 G71MPP 60D 135 2 91M02 60 500 13 50 11 00 5500 CH33 50 60C 2F 4 G60UHV 60C 090 2 91M02 60 500 13 50 11 50 5195 CH33 60D 2F 4 G60UHV 60D 135 2 91M02 61 000 14 00 11 50 5200 CH33 62D 2F 4 G60UHV 60...

Страница 19: ...acturer s proprietary products and recommended installation Retain Reference Article when specifying products and installation by an industry reference standard If retained list standard s referenced...

Страница 20: ...Control equipment shipped loose showing final location in assembly d Field wiring diagrams e Dimensions internal and external construction details installation clearances recommended method of install...

Страница 21: ...lace until installation Specifier Note Include or remove following section as project dictates E Waste Management and Disposal Specifier Note ENVIRONMENT The disposal of packaging waste into landfill...

Страница 22: ...ries 1 Hail Guards Four sided of louvered heavy gauge steel painted to match cabinet 2 Mounting Base of high density polyethylene structural material for permanent foundation of outdoor units 3 Unit S...

Страница 23: ...in the USA 9 All units are to be factory run tested 10 Installer responsibilities a Set unit b Connect refrigerant lines c Make electrical connections Specifier Note Edit article below to suit project...

Страница 24: ...st technical information www lennoxcommercial com Contact us at 1 800 9 LENNOX NOTE Due to Lennox ongoing committment to quality Specifications Ratings and Dimensions subject to change without notice...

Отзывы: