background image

Page 25

DO NOT CHARGE UNIT

(Results of charging at low

temperatures not reliable)

START: Measure outdoor ambient temperature

USE WEIGH-IN METHOD

Weigh-in or remove refrigerant
based upon line set length

BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures]
Use cardboard or plastic sheet to restrict the airflow through the outdoor coil
to achieve pressures from 325−375 psig (2240−2585 kPa).

 

Higher pressures

are needed to check charge. Block equal sections of air intake panels and
move coverings sideways until the liquid pressure is in the above noted
ranges.

If value is 

MORE

than shown, remove
refrigerant.

1. Confirm proper airflow across coil using Figure

18.

2. Compare unit pressures with Table 5 or 6.

3. Set thermostat to call for heat (must have a

cooling load between 70-80ºF (21−26ºC)

4. Connect gauge set

5. Measure outdoor ambient temperature

6. When heat demand is satisfied, set thermostat to

call for cooling

7. Allow temperatures and pressures to stabilize.

NOTE − If necessary, block outdoor coil to
maintain 325 − 375 psig.

8. Record liquid line temperature:

LIQº = ______

9. Measure liquid line pressure and use the value to

determine saturation temperature (see Table 7):

SATº = ______

10. Subtract to determine subcooling (SCº):

SATº_____ − LIQº _____ = SCº _____

11. Compare results with Tables 3 or 4 .

Figure 21. HFC−410A Subcooling Charge

MORE 

or

LESS

If value is 

LESS

than shown, add
refrigerant.

 ABOVE or

BELOW

 

65ºF

(18.3ºC)

and

ABOVE

64ºF

(17.7ºC) and

BELOW

Table 3.

 

Subcooling (SC) Values TXV System − ºF

(ºC) +1ºF (0.5ºC) (1−PHASE)

TSA*S4 50Hz International (1−Phase)

F(

5

C)

−024

−030

−036

−048

−060

65 (18)

10

6

5

2

4

70 (21)

10

6

5

2

4

75 (24)

11

6

6

3

4

80 (27)

11

7

6

3

5

85 (29)

11

7

6

3

5

90 (32)

11

7

7

4

5

95 (35)

11

7

7

4

5

100 (38)

11

7

7

5

5

105 (41)

11

7

7

5

5

110 (43)

11

8

7

5

5

115 (45)

11

8

8

6

5

Table 4.

 

Subcooling (SC) Values  TXV System − ºF

(ºC) +1ºF (0.5ºC) (3−PHASE)

TSA*S4 50Hz International (3−Phase)

F(

5

C)

−036

−048

−060

65 (18)

8

2

2

70 (21)

8

2

3

75 (24)

9

3

3

80 (27)

9

3

3

85 (29)

9

4

4

90 (32)

10

4

4

95 (35)

10

4

4

100 (38)

10

5

4

105 (41)

10

5

4

110 (43)

10

5

4

115 (45)

10

6

4

Содержание TSA024S4N41M

Страница 1: ...Dimensions 2 Typical Control Panel Parts Arrangement 4 Typical Unit Parts Arrangement 5 Model Number Identification 5 Unit Components 6 General Information 8 Operating Gauge Set and Service Valves 8 Recovering Refrigerant from Existing System 10 New Outdoor Unit Placement 11 New or Replacement Line Set 12 Metering Devices and Flushing the System 15 Testing for Leaks 16 Evacuating the System 17 Ele...

Страница 2: ...3 4 4 4 4 Motor W hp 75 1 10 150 1 5 185 1 4 185 1 4 185 1 4 L s cfm 924 1958 944 2000 1377 2917 1443 3058 1416 3000 Rev min 842 908 688 696 692 Watts 138 154 250 246 238 Shipping Data kg lb 1 package 56 123 60 133 81 178 88 194 99 218 Electrical Data Line voltage data 50 hz 1 phase 220 240V 220 240V 220 240V 220 240V 220 240V 2 Maximum overcurrent protection amps 25 25 35 35 45 3 Minimum circuit ...

Страница 3: ...6 238 Shipping Data kg lb 1 package 61 135 88 194 99 218 Electrical Data Line voltage data 50 hz 3 phase 380 420V 380 420V 380 420V 2 Maximum overcurrent protection amps 10 15 20 3 Minimum circuit ampacity 8 0 10 7 14 2 Compressor Rated load amps 6 0 7 8 10 6 Locked rotor amps 46 0 51 5 74 0 Condenser Fan Motor Full load amps 0 55 1 0 1 0 Locked rotor amps 1 1 2 3 2 3 NOTE Extremes of operating ra...

Страница 4: ...Tand M 24 1 4 616 25 1 4 641 TSA030S4N41T and M 24 1 4 616 29 1 4 743 TSA036S4N41M 28 1 4 724 29 1 4 743 TSA036S4N41T 24 1 4 616 29 1 4 743 TSA048S4N41T and M 28 1 4 724 37 1 4 925 TSA060S4N41T and M 28 1 4 724 33 1 4 845 Typical Control Panel Parts Arrangement GROUND LUG CONTROL CAPACITOR C12 CONTROL WIRE LOOP CUTOUT FOR HIGH VOLTAGE CONDUIT THREE PHASE ONE PHASE OR CONTACTOR LOCATION ONE POLE TH...

Страница 5: ...36 S 4 4 N Major Design Sequence A 1st Generation B 2nd Generation Brand Family T T Class Product Line Unit Type S Split System Air Conditioner 024 2 Tons 030 2 5 Tons 0036 3 Tons 048 4 Tons 060 5Tons Cooling Efficiency S Standard Efficiency Minor Design Sequence 1 1st Revision 2 2nd Revision 3 3rd Revision Voltage M 380 420V 3 phase 50hz T 220 240V 1 phase 50hz Refrigerant Type 4 R 410A Part Load...

Страница 6: ...ch opens and shuts off the compressor LOSS OF CHARGE SWITCH S24 FIELD INSTALLED OPTION The loss of charge switch is N C auto re set and located on the liquid line of the compressor The switch opens when liquid line pressure drops to 25 5 psig and shuts off the compressor The switch closes on a pressure rise at 55 5 psig The settings are factory set and cannot be adjusted CRANKCASE HEATER HR1 AND O...

Страница 7: ... effects of liquid return If liquid enters the scrolls the orbiting scroll is allowed to separate from the stationary scroll The liquid is worked toward the center of the scroll and is discharged If the compressor is replaced conventional Lennox cleanup practices must be used Due to its efficiency the scroll compressor is capable of drawing a much deeper vacuum than reciprocating compressors Deep ...

Страница 8: ...ness 50Rc Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks roundingor breaking off the wrench or stripping the valve stem recess See the Lennox Service and A...

Страница 9: ...vice port 3 When testing is completed replace service port cap and tighten as fol lows 1 2 3 4 5 6 7 8 9 10 11 12 1 6 TURN Operating Angle Type Service Valve 1 Remove stem cap with an appropriately sized wrench 2 Use a service wrench with a hex head extension 3 16 for liquid line valve sizes and 5 16 for vapor line valve sizes to back the stem out counterclockwise as far as it will go Operating Ba...

Страница 10: ...ssor stops pumping when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips drive bearings and internalseals Once the compressor can not pump down to a lower pr...

Страница 11: ... a very high level of sound transmission For proper placement of unit in relation to a window see the provided illustration in Figure 10 INSTALL UNIT AWAY FROM WINDOWS TWO 90 ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION Figure 10 Outside Unit Placement PLACING OUTDOOR UNIT ON SLAB When installing a unit at grade level the top of the slab should be high enough above the grade so that...

Страница 12: ... The length and bore of the RFC line corresponded to the size of cooling unit If the XP is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device RFCI the liquid line must be replaced prior to the installation of the XP unit Typically a liquid line used to meter flow is 1 4 in diameter and copper LIQUID LINE FILTER DRIER INSTALLA...

Страница 13: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WOOD BLOCK BETWEEN STUDS STRAP WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL REFRIGERANT LINE SET INSTALLING VERTICAL RUNS NEW CONSTRUCTION SHOWN INSTALLATION LINE SET NOTE Insulate liq...

Страница 14: ...ection on the vapor service valve NOTE The fixed orifice or check expansion valve metering device at the indoor unit will allow low pressure nitrogen to flow through the system NITROGEN HIGH LOW USE REGULATOR TO FLOW NITROGEN AT 1 TO 2 PSIG BRAZE LINE SET INSTALL SERVICE PORT CAPS ONLY Braze the liquid line to the liquid line service valve Turn off nitrogen flow After all connections have been bra...

Страница 15: ...tting to temporary reconnect the liquid line to the indoorunit s liquid line orifice housing I Reverse above order to install LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUI...

Страница 16: ...th a leak detector F After leak testing disconnect gauges from service ports USE REGULATOR TO FLOW NITROGEN AT 1 TO 2 PSIG LINE SET AND INDOOR COIL After the line set has been connected to the indoor unit and air conditioner check the line set connections and indoor unit for leaks Use the following procedure to test for leaks LEAK TEST A Connect an HFC 410A manifold gauge set high pressure hose to...

Страница 17: ...t rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to an uprightcylinder of HFC 410A refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the li...

Страница 18: ...and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low voltage control power 24VAC 40 VA minimum SERVICE DISCONNECT SWITCH MAIN FUSE BOX BREAKER PANEL Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power ...

Страница 19: ... 24VAC control wires through hole with grommet and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field provided wire nuts Yellow to Y1 Black to C common NOTE For proper voltages select thermostat wire control wires gauge per Table above NOTE Wire tie provides low voltage control wire strain relief and to mai...

Страница 20: ... Cooling demand initiates at Y1 in the thermostat 2 24VAC from indoor unit Y1 energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 END OF COOLING DEMAND 4 Cooling demand is satisfied Terminal Y1 is de energized 5 Compressor contactor K1 is de energized 6 K1 1 opens and compressor B1 and outdoor fan motor B4 are de energized and stop immediately NOTE The thermo...

Страница 21: ... Cooling demand initiates at Y1 in the thermostat 2 24VAC from indoor unit Y1 energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 END OF COOLING DEMAND 4 Cooling demand is satisfied Terminal Y1 is de energized 5 Compressor contactor K1 is de energized 6 K1 1 opens and compressor B1 and outdoor fan motor B4 are de energized and stop immediately NOTE The thermo...

Страница 22: ...utlined in Figure 20 Unit Start Up IMPORTANT If unit is equipped with a crankcase heater it should be energized 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Rotate fan to check for binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the r...

Страница 23: ...perature of air entering indoor coil ºF INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19º A Dry bulb Wet bulb ºF A 72º B 64º C 53º air flow air flow All temperatures are expressed in ºF 1 Determine the desired DT Measure entering air temperature using dry bulb A and wet bulb B DT is the intersecting value of A and B in the Table see triangle 2 Find temperature drop across coil Measure the coil s ...

Страница 24: ...MBIENT TEMPERATURE START Measure outdoor ambient temperature 64ºF 17 7ºC and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table5 or 6 3 Conduct leak check evacuate as previously outlined 4 Weigh in the unit nameplate charge plus any charge required for line set differences over feet Liquid Line Set Diameter g per 1 5 m adjust from 4 6 m line set 9 5 mm 85 g per 1 5...

Страница 25: ...or cooling 7 Allow temperatures and pressures to stabilize NOTE If necessary block outdoor coil to maintain325 375 psig 8 Record liquid line temperature LIQº ______ 9 Measureliquid line pressure and use the value to determinesaturation temperature see Table 7 SATº ______ 10 Subtract to determine subcooling SCº SATº_____ LIQº _____ SCº _____ 11 Compare results with Tables 3 or 4 Figure 21 HFC 410A ...

Страница 26: ...15 45 507 152 497 147 487 148 498 149 492 157 Temperature of the air entering the outside coil Table 6 HFC 410A Normal Operating Pressures Liquid 10 and Suction 5 Psig 3 Phase TSA S4 50Hz International 3 Phase XP 036 048 060 5F 5C Liquid Suction Liquid Suction Liquid Suction 65 18 269 135 247 132 269 136 70 21 290 136 269 134 289 137 75 24 311 137 290 136 310 139 80 27 334 138 312 138 332 140 85 2...

Страница 27: ...____ Actual __________ 6 Inspect drain holes in coil compartment base and clean if necessary NOTE If insufficient cooling occurs the unit should be gauged and refrigerant charge should be checked Outdoor Coil Clean and inspect outdoor coil may be flushed with a water hose Ensure power is off before cleaning NOTE It may be necessary to flush the outdoor coil more frequently if it is exposed to subs...

Страница 28: ...um Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Suction Pressure Refrigerant Charge Checked Refrigerant Lines Leak Checked Properly Insulated Outdoor Fan Checked Service Valves Fully Opened Caps Tight Thermostat Voltage With Compressor Operating Calibrate...

Отзывы: