TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units
SPECIFICATIONS
General
D t
Model No.
TPA036S2
TPA048S2
TPA060S2
Data
Nominal Tonnage (kW)
3 (10.6)
4 (14.1)
5 (17.6)
Connections
(sweat)
Liquid line o.d. − in. (mm)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
(sweat)
Vapor line o.d. − in. (mm)
7/8 (22.2)
7/8 (22.2)
1-1/8 (28.6)
2
Refrigerant
R−22 charge furnished
8 lbs. 10 oz.
(3.91 kg)
11 lbs. 12 oz.
(5.33 kg)
14 lbs. 0 oz.
(6.35 kg)
Outdoor
Coil
Net face area
sq ft (m
2
)
Outer coil
15.21 (1.41)
21.11 (1.96)
24.94 (2.32)
Coil
sq. ft. (m
2
)
Inner coil
14.50 (1.35)
20.31 (1.89)
24.13 (2.24)
Tube diameter − in. (mm) no. of rows
5/16 (8) − 2
5/16 (8) − 2
5/16 (8) − 2
Fins per inch (m)
22 (866)
22 (866)
22 (866)
Outdoor
Fan
Diameter − in. (mm) − No. of Blades
18 (457) − 4
22 (559) − 4
26 (660) − 4
Fan
Motor hp (W)
208/230V − 1/5 (149)
460V − 1/6 (124)
1/3 (249)
1/3 (249)
Cfm (L/s)
2450 (1155)
3890 (1835)
4550 (2145)
Rpm
1100
1085
830
Watts
190
375
307
Shipping Data
− lbs. (kg) 1 package
178 (81)
248 (112)
284 (129)
ELECTRICAL DATA
Line voltage data − 60 hz − 3ph
208/230V
460V
208/230V
460V
208/230V
460V
3
Maximum overcurrent protection (amps)
20
10
30
15
40
15
4
Minimum circuit ampacity
13.1
6.5
20.0
9.5
23.4
10.1
Compressor
Rated Load Amps
9.6
4.8
14.7
7.0
17.3
6.7
p
Locked Rotor Amps
77
35
91
50
123
49.5
Power Factor
.96
.88
.96
.87
.96
.88
Outdoor
Fan Motor
Full Load Amps
1.1
.55
1.7
.82
1.8
.9
Fan Motor
Locked Rotor Amps
1.9
1.1
4.1
2.2
2.9
2.3
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Low Ambient Cut−Off
45F08
S
S
S
Compressor Sound Cover
69J03
S
S
S
Freezestat
3/8 in. tubing
93G35
S
S
S
5/8 in. tubing
50A93
S
S
S
Hail Guards
92M89
S
92M90
S
27W36
S
High Pressure Switch Kit
94J46
S
S
S
Loss of Charge Kit
84M23
S
S
S
5
Low Ambient Kit
(down to 30°F)
27J00
S
S
S
Low Ambient Control Option
(down to 0°F)
See table page 7
See table page 7
See table page 7
Mild Weather Kit
33M07
S
S
S
Monitor Kit − Service Light
76F53
S
S
S
Mounting Base
69J06
S
g
69J07
S
S
Outdoor
Thermostat
Thermostat
56A87
S
S
S
Thermostat
Kit
Mounting Box
31461
S
S
S
Refrigerant
Line Sets
L15−65−30, L15−65−40, or L15−65−50
S
S
g
Line Sets
Field Fabricate
S
Time Delay Relay Kit
58M81
S
S
S
Unit Stand−Off Kit
94J45
S
S
S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Freezestat is recommended with Low Ambient Kit.
Содержание TPA036S2