XC17 SERIES
CONTROL PANEL
ACCESS
LOCATION
6 (152)
36 (914)
12 (305)
30 (762)
LINE SET
CONNECTIONS
24 (610)
LINE SET
CONNECTIONS
ACCESS PANEL
REAR VIEW OF UNIT
48 (1219)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
CLEARANCE ON ALL SIDES INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
S
Clearance to one of the other three
sides must be 36 inches (914mm).
S
Clearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
Figure 3. Installation Clearances
New Outdoor Unit Placement
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
See
Unit Dimensions
on page 3 for sizing mounting slab,
platforms or supports. Refer to Figure 3 for mandatory
installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
S
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in Figure 4,
Detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in Figure 4,
Detail B.
NOTE If necessary for stability, anchor unit to slab as
described in
Figure 4, Detail D.