TABLE 12

NORMAL OPERATING PRESSURES

COOLING OPERATION

(Liquid ±10 and Vapor ±5 psig)

First Stage (Low Capacity)

Outdoor Coil

HPXA19−024

HPXA19−036

HPXA19−038

HPXA19−048

HPXA19−060

Outdoor Coil

Entering Air

Temp. °F (°C)

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

65 (18.3)

217

143

227

142

222

142

222

140

225

140

75 (23.9)

250

145

262

145

255

145

258

143

259

142

85 (29.4)

291

147

305

146

295

146

298

145

293

146

95 (35.0)

336

149

352

148

343

148

343

147

356

147

105 (40.6)

386

151

403

152

390

153

402

147

408

147

115 (49.0)

440

153

458

155

446

156

452

152

455

151

Second Stage (High Capacity)

Outdoor Coil 

HPXA19−024

HPXA19−036

HPXA19−038

HPXA19−048

HPXA19−060

Outdoor Coil 

Entering Air 

Temp. °F (°C)

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

65 (18.3)

222

143

244

136

231

133

232

134

249

126

75 (23.9)

256

145

282

139

263

139

266

136

289

134

85 (29.4)

302

145

325

142

305

142

309

139

330

140

95 (35.0)

349

147

377

144

354

145

359

142

378

143

105 (40.6)

403

149

428

146

403

147

410

144

433

146

115 (49.0)

464

152

488

148

461

149

468

147

492

149

TABLE 13

NORMAL OPERATING PRESSURES

HEATING OPERATION

(Liquid ±10 and Vapor ±5 psig)

First Stage (Low Capacity)

Outdoor

Coil

HPXA19−024

HPXA19−036

HPXA19−038

HPXA19−048

HPXA19−060

Coil

Entering

Air

T

°F

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

40 (4.4)

321

99

296

95

308

97

315

97

319

93

50 (10)

340

120

310

112

323

116

330

114

335

111

Second Stage (High Capacity)

Outdoor

Coil

HPXA19−024

HPXA19−036

HPXA19−038

HPXA19−048

HPXA19−060

Coil 

Entering

Air Temp.

°F (°C)

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

20 (−7.0)

273

68

277

60

288

59

294

60

300

57

30 (−1.0)

296

80

296

74

308

74

303

75

312

70

40 (4.4)

321

95

321

88

316

90

314

90

323

83

50 (10)

341

115

341

104

330

108

325

106

339

97

Содержание HPXA19

Страница 1: ...of this R410A unit are higher than pressures in R22 units Always use service equipment rated for R410A WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...99 0 99 Outdoor Coil F M t Full load amps 0 8 0 8 2 8 1 7 1 7 Fan Motor Locked rotor amps 2 2 Not Applicable 3 1 3 1 OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Hard Start Kit Factory Instal...

Страница 3: ...ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the out er crescent shaped gas pocke...

Страница 4: ...ing for second stage Second stage high capacity is achieved by blocking the bypass ports figure 5 bypass ports closed with a slider ring The slider ring begins in the open position and is con trolled...

Страница 5: ...ch Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating op eration on heat pump or below cooling operation the room temperature 5 F 3 Remove control access...

Страница 6: ...ctifier plug Listen for a click as the solenoid is energized See figure 6 compressor solenoid fusite terminals compressor fusite terminals meter rectifier plug leads apply 24vac FIGURE 6 3 Unplug the...

Страница 7: ...is normally closed and is permanently adjusted to trip open at 640 10 psi and close at 448 10 psi See fig ure 13 for switch location E Capacitor C12 The compressor in XP19 024 036 048 and 060 units us...

Страница 8: ...et to close at 40 2 F on a temperature drop and reset at 50 2 F on a temperature rise TABLE 2 Control Setpoints Low Ambient Thermostat Adjustable Range Factory Setting Min Max Cut In Close on Temperat...

Страница 9: ...s controlled by the compressor con tactor See ELECTRICAL DATA and SPECIFICATIONS section for more information See figure 11 if condenser fan motor replacement is necessary Rain shield location is crit...

Страница 10: ...er to maintain constant airflow cfm Motor rpm is continually adjusted internally to maintain constant static pressure against the fan blade The control ler monitors the static work load on the motor a...

Страница 11: ...rb moisture the dryness of the system must be verified any time the refrigerant sys tem is exposed to open air A compressor oil sample must be taken to determine if excessive moisture has been introdu...

Страница 12: ...s in all units are equipped with a 70 watt belly band type crankcase heater HR1 prevents liquid from ac cumulating in the compressor HR1 is controlled by the crankcaseheater thermostat X Crankcase hea...

Страница 13: ...sure switch is present check Flash Code 2 information 4 If low pressure switch is present check Flash Code 1 information Yellow Alert Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line vo...

Страница 14: ...e off the compressor and the strike counter in the board will count one strike S87 is ignored during certain conditions During the defrost cycle and 90 seconds after the termination of defrost When th...

Страница 15: ...nitiated after 34 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable system temperatu...

Страница 16: ...connection of gauge manifold during charging procedure Figure 22 shows HPXA19 refrigerant flow and gauge manifold connections TABLE 7 M d l Valve Field Size Connections Recommended Line Set Model Liq...

Страница 17: ...nnect gauge to the service port 3 When testing is complete replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjustable wrench 2...

Страница 18: ...that can re sult in personal injury or death Using an Electronic Leak Detector 1 Connect a cylinder of R410A to the center port of the manifold gauge set 2 With both manifold valves closed open the v...

Страница 19: ...losing the manifold gauge valves 9 When the absolute pressure requirement above has been met disconnect the manifold hose from the vacu um pump and connect it to an upright cylinder of R410A refrigera...

Страница 20: ...r best results indoor temperature should be 70 F 21 C to 80 F 26 C Monitor system pressures while charging 1 Record outdoor ambient temperature using a digital thermometer 2 Attach high pressure gauge...

Страница 21: ...244 136 231 133 232 134 249 126 75 23 9 256 145 282 139 263 139 266 136 289 134 85 29 4 302 145 325 142 305 142 309 139 330 140 95 35 0 349 147 377 144 354 145 359 142 378 143 105 40 6 403 149 428 14...

Страница 22: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Страница 23: ...POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the electrical power to unit OFF at dis connect switch es...

Страница 24: ...Page 24 VII DIAGRAM OPERATING SEQUENCE HPXA19 024 036 048 060...

Страница 25: ...nergized The slider ring re mains open limiting compressor to low capacity B Ambient temperature BELOW S23 low ambient thermostat setting S23 closes shunting Y1 and Y2 1 Internal wiring de energizes t...

Страница 26: ...Page 26 1 2 3 4 HPXA19 038 with Variable Speed Motor...

Страница 27: ...pen limiting compressor to low capacity B Ambient temperature BELOW S23 low ambient setting S23 closes shunting Y1 and Y2 1 Internal wiring de energizes terminal O by heating mode selection de energiz...

Отзывы: