background image

43

240012994 Rev. B  [08/31/2020]

9.11 Chimney Sweep Function (CO

2

 Adjust)

For correct boiler operation, content of (CO

- O

2

) in the combustion flue must be within tolerances indicated in table below.

COMBUSTION TABLE

Gas A 

(Natural Gas)  

150

Gas A 

(Natural Gas) 

205

Gas E (LPG)

CO2 %

O2 %

CO2 %

O2 %

CO2 %

O2 %

Maximum 

power (100%)

Nominal value

9.0

4.9

9.0

4.9

10.0

6.0

Permitted value

8.5 – 9.5 5.7 – 4.0 8.7 – 9.3

5.4 – 4.3

9.5 – 10.5 6.8 – 5.2

Ignition power 

(*)

Nominal value

8.7

5.4

8.7

5.4

10.8

4.8

Permitted value

8.2 – 9.3 6.3 – 4.3 8.2 – 9.3

6.3 – 4.3 10.3 – 11.3 5.5 – 4.1

Minimum 

power (0%)

Nominal value

8.8

5.2

9.0

4.9

10.0

6.0

Permitted value

8.2 – 9.3 6.3 – 4.3 8.7 – 9.3

5.4 – 4.3

9.5 – 10.5 6.8 – 5.2

Chimney Sweep Function enables boiler to generate maximum 

heating power. 

After activation, boiler power % can be adjusted from 

minimum (0%) to maximum (100%) in DHW mode.

A. 

Press and hold 

 and 

 at the same time for 6 

seconds. When the function is enabled, displays shows 

On

” for few seconds followed by program row “

303” 

alternating with % of boiler power.

B. 

Press 

to gradually adjust power (increments of 

1%).

C. 

To exit press both buttons together for at least 6 

seconds.

If value of CO

2

-O

2 

is different, check the electrodes and their 

relative distances. See Figure 11-1.

If necessary, replace electrodes and position them correctly. 

f problem persists, use "COMBUSTION ADJUSTMENT 

FUNCTION (CO

2

%

)". See Section 11 General Maintenance, 

Figure 11-1 Electrodes. If problem persists,

 use Section 9.8 

Automatic Calibration Function, and Section 9.9 Manual 

Calibration Function.

NOTICE

• 

Press 

 to display instantaneous flow temperature for 

15 seconds.

• 

Use a regularly calibrated combustion analyzer for 

combustion analysis. 

• 

During normal operation boiler performs combustion 

control cycles. In this phase CO values higher than 400 

ppm can occur for brief periods of time.

9 - START UP PROCEDURE

(*)

  

Automatically calculated from the PCB

9.13 Check Firing Rate

1. 

Measure input, if a gas meter is installed in the system.

• 

Turn off gas to all other appliances.

• 

Activate some heating zones to dissipate heat.

• 

Set boiler on high fire using Chimney Sweep Function.

• 

Use ½, 1 or 2 cu ft dial on gas meter.  Measure time 

required for two or more complete revolutions.  Measure 

time 

for one or more minutes.

•  Calculate input.

9.12 Combustion Adjustment Function (CO

2

%)

This function sets out to partially adjust the value of CO

2

%. 

Use the following procedure:

1. 

Press buttons 

 and 

 together for at least 6 seconds. 

When the function is enabled, displays shows “On” for a 

few seconds followed by program row “

304” alternated 

with the % of boiler power;

2. 

After burner is lit, boiler reverts to maximum DHW power 

(100). When display shows "100" it is possible to partially 

adjust value of CO

2

 %;

3. 

Press 

 and 

 . Display shows "00

" alternating with 

function number "304" (

flashes);

4. 

Press 

  

    to raise or lower the amount of CO

2

 

(from -0.3% to + 0.3%);

5. 

Press 

 to save new value. Power value "

100" will show 

on display again. Boiler continues operating at maximum 

DHW power.

This procedure can be used to adjust CO

2

 to ignition power 

and minimum power by pressing 

 

 after performing step 

5 above. 

6. 

After saving the new value (step 5 above), press 

 

to set boiler to ignition power. Wait for value of 

CO

2

 

to stabilize. Adjust as described in step 4 of procedure 

(power value is a number <> 100 and <> 0). Repeat step 

5 to save.

7. 

Press 

 to adjust boiler to minimum power. Wait for 

value of CO

2

 to stabilize. Go to step 4 to adjust (power 

value = 00);

8. 

Exit function by pressing 

 and 

  together for at least 

6 seconds, see step 1.

      If proper combustion cannot be reached see Automatic     

      and Manual Calibration sections 9.7 and 9.8.

Содержание GCWB95W-150

Страница 1: ...ndards Association for use with Natural and Propane Gases They are constructed and hydrostatically tested for a maximum working pressure of 50 psi pounds per square inch in accordance with A S M E Ame...

Страница 2: ...0 PSI Safety Relief Valve Temperature Pressure Gauge 4 ea 17x24x2 Gaskets Includes Essential Documents and Warranty 11x17 Wire Diagrams Drain Valve 5 GPM Flow Restrictor 205 Combi Factory Installed Us...

Страница 3: ...gement Of 0 10v Input 37 9 Start Up Procedure 39 9 1 Central Heating System Connections Combi 38 9 2 System Start Up 39 9 3 Fill Condensate Trap With Water 39 9 4 Control Panel 40 9 5 Prior To Commiss...

Страница 4: ...tem temperature 176 F 80 C 176 F 80 C Pressure Relief Valve Setting 30 00 psi 2 11 bar 30 00 psi 2 11 bar Expansion Tank Minimum Size pre charge press 2 2 gal at 11 6 psi 10 0 L at 0 8 bar 2 2 gal at...

Страница 5: ...CAL DATA Front View All Models Top View All Models 205 COMBI Bottom View Dimensions 150 COMBI Bottom View Dimensions D E I G C B F H B A Vent Connector Combustion Air 5 31 2 31 2 6 6 9 7 41 2 7 51 2 3...

Страница 6: ...ish washing and other sanitizing needs can scald and cause permanent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never l...

Страница 7: ...output available for domestic hot water GCWB95W 150 136 000 btu h 40 kW capable of providing 3 5 U S gpm 13 2 liters min with a temperature rise of 70 F 39 C GCWB95W 205 180 000 btu h 53 kW capable of...

Страница 8: ...changer 12 Water Safety Thermostat 13 NTC Heating sensor Flow Return QTY 2 1 Shown for clarity 14 Flue Sensor 15 Pressure Switch 16 Coaxial Connector 17 Heat Exchanger Temperature Protector 18 Heat Ex...

Страница 9: ...1 Water Safety Thermostat 12 Flue Sensor 13 Coaxial Connector 14 Heat Exchanger Temperature Protector 15 Heat Exchanger 16 Burner Door Temperature Sensor 17 Burner not shown 18 Ignition Electrode 19 F...

Страница 10: ...weight of the boiler Room sealed boiler installed in a room containing bath or shower shall be installed so person using bath or shower cannot touch any electrical switch or boiler control utilizing l...

Страница 11: ...30 in 763 mm 150 13 9 16 in 345 mm 4 2 Clearances 205 211 2in 571 5 mm 1 1 3 4 3 4 in in 45 mm 45 mm Left Side View of Boiler Front View of Boiler Service Clearances Combustible Clearances 1 3 4 in 45...

Страница 12: ...ial flue See sizing below 150 4 3 8 110 mm diameter 205 5 5 16 135 mm diameter 6 Pre pipe supply and return water connections with factory fittings before wall mounting 7 Mount boiler on wall using wa...

Страница 13: ...ith thermal insulation shall be prohibited Failure to follow these instructions could result in death or serious injury Note Follow venting manufacturer s equivalent lengths for specialty fittings Fig...

Страница 14: ...liances remaining connected to common venting system are located and other spaces of building Turn on clothes dryer and any appliance not connected to common venting system Turn on exhaust fans such a...

Страница 15: ...all vent systems shall be from same manufacturer and compatible with the vent pipe See list for approved Manufacturers Installation shall conform to requirements of authority having jurisdiction or i...

Страница 16: ...into intake air vent and pass them through hole in wall Check all measurements before cutting Clearance to combustible materials is zero when using coaxial vent system After installing venting use cal...

Страница 17: ...8 181 mm Max 14 356 mm Maintain 12 305 mm US 18 457 mm Canada clearance above highest anticipated snow level 24 610 mm above roof or ground Ground Anticipated Snow Line 18 Vertical Clearance to venti...

Страница 18: ...ne venting an adapter kit is available C Twin Pipe Separated Flue Exhaust and combustion air intake are not located in same general location D Twin Pipe Common Atmospheric Zone Termination Exhaust and...

Страница 19: ...uld not be used in outdoor applications Follow venting manufacturer s instructions for applying the securing mechanism on twin pipe polypropylene venting Example for Natalini venting system See Figure...

Страница 20: ...305 mm Min 84 2 2 m Max vertical separation between combustion air intake and vent of different appliances 15 381 mm Max horizontal length of vent Min vent intake between different appliances 12 305...

Страница 21: ...and combustion air of other boilers required in all multiple boiler installations FIGURE 5 22 2 60 mm ONLY Twin Pipe Side Wall Vent CAN BE USED ON ALL SIZES 3 80 mm Min 24 610 mm Max Separation See Gr...

Страница 22: ...sed on equivalent straight runs only Include rigid pipe and fittings in overall equivalent length calculations Flexible venting installations use single wall polypropylene to pass flue gasses to base...

Страница 23: ...6 456 mm H Clearance to each side of center line extended above meter regulator assembly 3 ft 0 9 m within a height of 15 ft 4 5 m above the meter regulator assembly 3 ft 0 9 m I Clearance to service...

Страница 24: ...Use field source condensate pump designated for use with condensing boiler if boiler located below disposal point Condensate pump should have overflow switch Condensate from Boiler is slightly acidic...

Страница 25: ...valves are not installed install them to properly clean the system When purging installations that include standing iron radiators and systems with manual vents at high points start with nearest manua...

Страница 26: ...elbow s if used close to safety relief valve outlet and downstream of union if used Terminate pipe with plain end not threaded Check Local Codes For Check Local Codes For Maximum Distance To Floor Ma...

Страница 27: ...ield supplied external control Boiler control allows domestic hot water prioritization WARNING Burn and scald hazard Verify all plastic caps are removed from boiler connections Failure to follow these...

Страница 28: ...PLACE ISOLATION VALVE BEFORE TEE OR LWCO Note 1 To Drain Check Local Codes for Maximum Distance to Floor Arrange piping to prevent water dripping onto boiler 1 Return 5 gpm Limiter Factory Installed...

Страница 29: ...EC or Canadian Electrical Code CEC Locate LWCO sensing device in the supply piping above the minimum height of boiler See Figure 6 6 Piping Diagram Position control in HORIZONTAL piping to assure prop...

Страница 30: ...ing potable water before entering the boiler The strainer prevents any sedimentation and debris from your water supply piping from entering the boiler Debris carried from the water supply will clog DH...

Страница 31: ...will acknowledge the presence of the flame in the combustion chamber and send a signal to the control board Temperature sensors will send a signal to the control board allowing the control board to in...

Страница 32: ...SA National Fuel Gas Code ANSI Z223 1 NFPA 54 Canada Natural Gas and Propane Installation Code CAN CSA B149 1 GAS SUPPLY REQUIRED MODEL NATURAL GAS A LIQUID PROPANE E GCWB95W 150 143 ft3 h 4 00 m3 h 6...

Страница 33: ...leakage using gas detector noncorrosive detection fluid or other leak detection method acceptable to authority having jurisdiction Do not use matches candles open flames or other methods that can prov...

Страница 34: ...IGURE 8 1 Electric Knockouts Bottom Of Boiler Illustration shown size 150 illustration is for location purposes wiring knockouts found same general location on all sizes 8 ELECTRICAL CONNECTIONS Note...

Страница 35: ...n supply is connected to terminal block M1 which is high voltage 120V 60Hz Fuses 3 15 A 250 V Fast Acting are incorporated in the power supply terminal block To check or replace fuse pull out black fu...

Страница 36: ...apply 24 volts between 6 and 7 A Room End Switch 8 7 Optional Electrical Connections A 1K Ohm 1K Outdoor Temperature Sensor To connect this accessory see figure 8 5 terminals 4 5 and instructions supp...

Страница 37: ...86 860 7 140 60 23 7 80 800 31 1 105 980 8 154 68 28 0 95 500 36 7 125 100 9 167 75 32 3 110 200 42 3 144 220 10 176 80 36 6 125 000 48 1 164 000 The functions with 0 10V regulator are activated by me...

Страница 38: ...4 22 2 mm 1 25 4 mm D Cold DHW inlet tap system filling connection for Combi 1 2 15 9 mm 3 4 NPT E Gas shutoff connection 3 4 22 2 mm F Boiler Fast Fill External to Boiler NA G DHW outlet 1 2 15 9 mm...

Страница 39: ...boiler drain may be open until water flows out Close drain as soon as water appears During initial system air purge open valve connected to top left of heat exchanger see figure 9 1 Open 4 full turns...

Страница 40: ...rmation 06 Heating return temperature F C 16 Manufacturing information 07 Thermo fuse status 000 001 17 Fan speed i17 x100 08 Not used 18 Manufacturing information DHW temperature adjustment to increa...

Страница 41: ...tic Calibration Function Manual Calibration may be necessary if combustion is not within specified range After furel type is detected confirm P02 is set for the desired fuel type by checking the param...

Страница 42: ...is interrupted by power blackout start function again when power is restored Press and together and hold at same time for at least 6 seconds B If display shows fault E118 low pressure in hydraulic ci...

Страница 43: ...erforms combustion control cycles In this phase CO values higher than 400 ppm can occur for brief periods of time 9 START UP PROCEDURE Automatically calculated from the PCB 9 13 Check Firing Rate 1 Me...

Страница 44: ...tting optional 00 no function is associated 01 close contact with a room thermostat request other than ECR thermostat 02 close contact with a ECR room thermostat request 03 relay for indicating low wa...

Страница 45: ...ut 0 100 00 P16 Maximum CH set point C 00 176 F 80 C 01 113 F 45 C 00 P17 Pump overrun time in heating mode 01 240 minutes 03 P18 Burner ignition delay in CH mode 00 10 minutes 00 10 seconds 03 P19 Ma...

Страница 46: ...Boiler Model PARAMETER P13 Heating Output Btu h KW 150 20 400 6 0 0 23 800 7 0 3 27 200 8 0 6 30 700 9 0 9 34 100 10 0 12 40 900 12 0 18 47 700 14 0 24 54 500 16 0 29 61 400 18 0 35 68 200 20 0 41 75...

Страница 47: ...ling stage the combustion fan comes on at ignition speed closing the air pressure switch allowing power to spark generator and gas valve creating ignition in the combustion chamber 3 Flame sensor ackn...

Страница 48: ...ath or serious injury Note Verify proper operation after servicing Note Perform regular service and maintenance by qualified service agency at least once every 12 months to assure safe trouble free op...

Страница 49: ...in death or serious injury CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Failure to follow these instructions could re...

Страница 50: ...o comply will result in death or serious injury 11 4 Draining the Boiler turn boiler off isolate electrical supply close boiler gas service cock allow boiler to cool drain boiler through onboard drain...

Страница 51: ...em to achieve temperature difference across heating supply and return pipes at the boiler Check system for proper volume and pressure See page 4 for acceptable volume and pressure Turn off boiler Thor...

Страница 52: ...e as indicated in the Combustion Table Components replaced Primary heat exchanger Fan Gas valve Gas orifice Burner Flame sensing electrode Spark electrode 11 10 User Information Advise and demonstrate...

Страница 53: ...owance of 1 15 Contact Technical Support before selecting boiler for installations having unusual piping and pickup requirements such as intermittent system operation extensive piping systems etc Max...

Страница 54: ...3048 m GCWB95W 205 113 20 3 105 95 0 141 20 3 120 17 Max CH Supply temp 176 F 80 C for GCWB9 150 Max DHW temp 140 F 60 C GCWB9 150 Max DHW Flow rate 3 5 gpm 13 2 l min GCWB9 205 Max DHW flow rate 5 0...

Страница 55: ...circulation of water and pump 118 Hydraulic pressure too low Refill heating system by opening cold water tap 117 Hydraulic pressure too high Relieve pressure via relief valve or drain Ensure water fee...

Страница 56: ...the combustion levels E70 Flame signal problem micro interruption of the flame signal Check cable and integrity of the sensing electrode verify the continuity between burner and earth E73 Combustion a...

Страница 57: ...ET ANOMALY P32 C00 P33 C01 P34 C02 P35 C03 P36 C04 P37 C05 P38 C06 RESET ANOMALY P39 C07 P40 C08 P41 C09 FAILURE CODE NUMBER OF TIMES OCCURRED SYSTEM STATUS CODES 0 STANDBY 1 DHW ON 2 CHIMNEY SWEEP AC...

Страница 58: ...ls made of or surfaced with wood compressed paper plant fibers or other materials capable of being ignited and burned Such material shall be considered combustible even though flame proofed fire retar...

Страница 59: ...nstallation testing repair or servicing of appliances and equipment Experienced in such work Familiar with all precautions required Complies with all requirements of authority having jurisdiction SAFE...

Страница 60: ...60 240012994 Rev B 08 31 2020 APPENDIX A WIRING DIAGRAMS A 3 MODEL 150 Combi...

Страница 61: ...61 240012994 Rev B 08 31 2020 APPENDIX A WIRING DIAGRAMS A 4 MODEL 205 Combi...

Страница 62: ...62 240012994 Rev B 08 31 2020 NOTES...

Страница 63: ...___ Measured BTU HR input____________ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner maintenance person In...

Страница 64: ...s provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An e...

Отзывы: