background image

Page 27

II−PLACEMENT AND INSTALLATION

Make sure unit is installed in accordance with installation
instructions and applicable codes.

III−START-UP

A−Preliminary and Seasonal Checks

1 −  Inspect electrical wiring, both field and factory installed

for loose connections. Tighten as required.

2 − Check voltage at disconnect switch. Voltage must be

within range listed on the nameplate. If not, consult the
power company and have voltage condition corrected
before starting unit.

B−Heating Start-Up

WARNING

Shock and burn hazard.

G50UH(X)  units are equipped with a hot surface igni-
tion system. Do not attempt to light manually.

 1 −

STOP

! Read the safety information at the beginning of

this section.

 2 − Set thermostat to lowest setting.

 3 − Turn off all electrical power to appliance.

 4 − This appliance is equipped with an ignition device

which automatically lights the burners. Do 

not

 try to

light the burners by hand.

 5 − Remove top access panel.
 6 −

White Rodgers Gas Valve −− 

Switch lever to 

OFF

.

See figure 15.

Honeywell Gas Valve −− 

Turn knob on gas valve

clockwise

 to  

OFF

. Do not force. See figure 17.

 7 − Wait five (5) minutes to clear out any gas. If you then

smell gas,

 STOP

! Immediately call your gas supplier from

a neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.

 8 −

White Rodgers  Gas Valve −− 

Switch gas valve lever to

ON

.

Honeywell  Gas Valve −− 

Turn knob on gas valve coun-

terclockwise

 

 

to 

ON

.  Do not force.

 9 − Replace access panel.

10− Turn on all electrical power to unit.

11− Set thermostat to desired setting.

12− If the appliance will not operate, follow the instructions

To Turn Off Gas To Unit" and call your service techni-
cian or gas supplier.

Turning Off Gas To Unit

 1 − Set thermostat to lowest setting.
 2 − Turn off all electrical power to unit if service is to be

performed.

 3 − Remove access panel.

 4 − Switch lever on White Rodgers gas valve to 

OFF

; turn

knob on Honeywell valve clockwise

 to  

OFF

. Do not

force.

 5 − Replace access panel.

C−Safety or Emergency Shutdown

Turn off  unit power. Close manual and main gas valves.

D−Extended Period Shutdown

Turn off thermostat or set to UNOCCUPIED" mode. Close
all gas valves (both internal and external to unit) to guaran-
tee no gas leak into combustion chamber. Turn off power to
unit. All access panels and covers must be in place and se-
cured.

IV−HEATING SYSTEM SERVICE CHECKS
A−C.S.A. Certification

All units are C.S.A. (formally A.G.A. and C.G.A. combined)
design certified without modifications. Refer to the
G50UH(X) Installation Instruction.

B−Gas Piping

CAUTION

If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet.

WARNING

Do not exceed 600 in−lbs (50 ft−lbs) torque when
attaching the gas piping to the gas valve.

Gas supply piping should not allow more than 0.5"W.C. drop
in pressure between gas meter and unit. Supply gas pipe
must not be smaller than unit gas connection.

Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.

C−Testing Gas Piping

IMPORTANT

In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit.  These controls should be properly
labeled by the installer.

When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged if
subjected to more than 0.5psig (14" W.C.). See figure 18

If

the pressure is equal to or less than 0.5psig (14"W.C.), use
the manual shut−off valve before pressure testing to isolate
furnace from gas supply.

FIGURE 18

MANUAL MAIN SHUT−OFF VALVE

GAS VALVE

CAP

GAS PIPING TEST PROCEDURE

FIELD PROVIDED

LINE PRESSURE TAP

Содержание G50UH Series

Страница 1: ...n only and do not supersede or replace local or state codes In the absence of local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do...

Страница 2: ...CH33 36B 2F CH33 42B 2F CH33 44 48B 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Air Filter and Rack Kit Number and size of fi...

Страница 3: ...36C 2F CH33 48C 2F CH33 50 60C 2F Electrical characteristics 120 volts 60 hertz 1 phase less than 12 amps OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Air Filter Rack Kit Horizontal end 87L96 1 18 x 25...

Страница 4: ...g Base Dimensions H x W x D 4 x 21 5 8 x 28 5 8 in 102 x 549 x 727 mm 4 x 24 5 8 x 28 5 8 in 102 x 625 x 727 mm Number and size of field provided fil ter 20 x 25 x 1 in 508 x 635 x25 mm 24 x 24 x 1 in...

Страница 5: ...6K63 1 16 x 25 x 1 406 x 635 x 25 EZ Filter Base Catalog Number Shipping Weight 73P57 8 lbs 4 kg 73P58 10 lbs 5 kg Base Dimensions H x W x D 4 x 21 5 8 x 28 5 8 in 102 x 549 x 727 mm 4 x 24 5 8 x 28 5...

Страница 6: ...with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 24A 070 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Externa...

Страница 7: ...h 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 36B 090 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds External St...

Страница 8: ...555 1265 595 459 40 100 1820 860 699 1670 790 611 1470 695 525 1255 590 443 50 125 1740 820 664 1600 755 575 1420 670 496 1215 575 414 60 150 1635 770 624 1530 720 544 1350 635 464 1175 555 400 70 17...

Страница 9: ...t with 1 in 25 mm cleanable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 48C 135 PERFORMANCE External Static Air Volume Watts at Various Blower Speeds Extern...

Страница 10: ...filter not furnished field provided in place Also see Filter Air Resistance table G50UH 60C 110 1 2 3 PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated transition to acc...

Страница 11: ...60 667 30 75 2205 1040 1218 2075 980 924 1860 875 782 1605 755 655 40 100 2130 1005 1189 2005 945 905 1815 855 752 1595 750 636 50 125 2045 965 1159 1920 905 864 1750 825 726 1565 740 619 60 150 1955...

Страница 12: ...tts 00 0 2715 1280 1407 2255 1065 1070 1910 900 850 1660 785 674 10 25 2640 1245 1403 2250 1060 1030 1900 895 834 1645 775 668 20 50 2540 1200 1355 2245 1060 1006 1890 890 821 1630 770 665 30 75 2480...

Страница 13: ...nable filter not furnished field provided in place Also see Filter Air Resistance table G50UH 60D 155 1 2 3 PERFORMANCE Single Side Return Air Air volumes in bold require field fabricated transition t...

Страница 14: ...r Air volumes in bold require field fabricated transition to accom modate 20 x 25 x 1 in 508 x 635 x25 mm cleanable air filter in order to maintain proper air velocity External Static Air Volume Watts...

Страница 15: ...10 0 2 49 HIGH ALTITUDE G50UH 1 1 High Altitude Orifice Kit Natural Gas Only High Altitude Prove Switch Kit LPG Propane Kit G50UH 1 to 14 Natural Gas Only 4501 7500 ft 1373 2286m 7501 10 000 ft 2287...

Страница 16: ...Burner Bottom Shield Limit Shield Secondary Limit as required NOx Units Only G50UH X PARTS ARRANGEMENT UP FLOW POSITION FIGURE 1 Gas Manifold 135 and 155 kBtuh units only Flame rollout switches are lo...

Страница 17: ...HEATING COMPONENTS COMBUSTION AIR INDUCER PROVE SWITCH PRIMARY LIMIT PRIMARY LIMIT SHIELD GAS VALVE ROLLOUT SWITCHES MANIFOLD BURNER ASSEMBLY NOx Insert NOx Units Only HEAT EXCHANGER FLUE COLLECTOR B...

Страница 18: ...also located in the control box The switch provides overcurrent protection to the trans former T1 The breaker is rated 3A at 32V If the cur rent exceeds this limit the breaker will trip and all unit...

Страница 19: ...times with an inter purge and warm up time between trials of 35 seconds Af ter a total of five trials for ignition including the initial trial the control goes into Watchguard Flame Failure mode Af t...

Страница 20: ...4 shows 24 volt and 120 volt control terminal designations Tables 5 and 6 show jack plug terminal designations See table 8 for troubleshooting diagnostic codes Units equipped with the SureLight system...

Страница 21: ...ight control utilizes less power to energize the ignitor on successive calls for heat The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will...

Страница 22: ...tor improperly attached ON ON ON OFF Circuit board failure or control wired incorrectly OFF ON y FAST FLASH SLOW FLASH Main power polarity reversed Switch line and neutral SLOW FLASH FAST FLASH Low fl...

Страница 23: ...the board voltage cannot be measured so ignitor must be ohmed Ohm value should be 10 9 to 19 7 See figure 12 for ignitor location NOTE The G50UH X furnace contains electronic components that are polar...

Страница 24: ...60C 110 4 5 units 2 5 32 36C 110 2 5 32 48C 60D 135 6 and later 1 to 5 units 2 3 8 2 5 32 60D 155 2 60 Horizontal Applications The G50UH X furnace can be installed in horizontal ap plications The comb...

Страница 25: ...nace control energizes the supply air blower and closes the gas valve The limit automatically resets when unit tempera ture returns to normal The switch must reset within three min utes or SureLight...

Страница 26: ...throw proving switch elec trically connected to the furnace control The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the flue becomes obstr...

Страница 27: ...rical power to unit if service is to be performed 3 Remove access panel 4 Switch lever on White Rodgers gas valve to OFF turn knob on Honeywell valve clockwise to OFF Do not force 5 Replace access pan...

Страница 28: ...anifold pres sure settings Manifold Adjustment Procedure 1 Connect a test gauge to outlet pressure tap on gas valve See figures 15 16 and 17 Start unit and allow 5 minutes for unit to reach steady sta...

Страница 29: ...AD TO IGNITION CONTROL SENSOR WIRE FIGURE 20 TABLE 16 FLAME SIGNAL in MICROAMPS SureLight Normal Low Drop Out 56L83 97L48 0 61 0 21 0 60 0 20 69M15 0 31 0 25 0 30 0 24 V TYPICAL OPERATING CHARACTERIST...

Страница 30: ...COOL terminal The con tinuous blower tap is connected to the FAN terminal To change existing heat tap turn off power then switch out speed tap on HEAT with tap connected to one of two PARK terminals S...

Страница 31: ...n air inducer Leaving off screws may cause leaks 13 Clean burner by running a vacuum with a soft brush at tachment over face of burners Visually inspect inside of burners and crossovers for any blocka...

Страница 32: ...2 minutes or control goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 second warm up period begins 5 Ga...

Страница 33: ...oes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 s...

Страница 34: ...COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence holds until PROVE switch closes or thermostat resets control NO NO YES NO IS THERE PROPER GROUND IS VOLTAGE...

Страница 35: ...CER OFF INDOOR BLOWER OFF WITH DELAY LED 1 ALT SLOW FLASH LED 2 ALT SLOW FLASH IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES FLAME SIGNAL NORMAL S...

Страница 36: ...ACTOR AND SYSTEM FAN ENERGIZED AFTER DELAY Control 69M15 2 second delay Control 56L83 97L48 0 second delay COOL SPEED AND ELECTRONIC AIR CLEANER TERMINAL IS ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS C...

Страница 37: ...OPENS COMBUSTION AIR INDUCER AND HEATING ACCESSORY TERMINAL ARE DE ENERGIZED INDOOR BLOWER SWITCHES TO COOL SPEED THERMOSTAT OPENS INDOOR BLOWER SWITCHES TO CONTINUOUS BLOWER ELECTRONIC AIR CLEANER T...

Страница 38: ...ION 1 Manually reset the roll out switch by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code LED 1 O 1 2 2 Roll out switch failure ACTI...

Страница 39: ...1997 combustion air inducer will cycle 5 seconds on 55 seconds off LED 1 Alternating Fast Flash LED 2 Alternating Fast Flash 2 1 2 Broken or failed ignitor ACTION 1 Unplug ignitor and read resistance...

Страница 40: ...ing demand Diagnostic lights flash the pressure switch failure code 2 5 minutes after heating demand 4 1 2 Prove switch does not close due to obstructions in the pressure lines ACTION 1 Remove any obs...

Страница 41: ...ssure switch code LED 1 Off LED 2 Slow Flash 6 1 1 Low pressure differential at the prove switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing Se...

Страница 42: ...6 3 3 Insufficient flow through the heat ex changer caused by a sooted or re stricted heat exchanger ACTION 1 Check for sooting deposits or other restrictions in the heat exchanger assembly Clean asse...

Страница 43: ...Properly locate the sense rod or replace if rod cannot be located correctly sense code LED 1 Slow Flash LED 2 Fast Flash 7 1 2 Sense rod is contaminated ACTION 1 Check sense rod for contamination or...

Отзывы: