Page 11
BLOWER DATA
G50UH−60C−110 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air
from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2655
1250
1407
2370
1120
1063
2085
985
894
1665
785
679
.10
25
2580
1215
1376
2350
1110
1043
2065
975
875
1650
780
667
.20
50
2500
1180
1346
2305
1085
1012
2045
965
849
1645
775
662
.30
75
2410
1135
1305
2230
1050
978
2010
950
820
1640
775
649
.40
100
2320
1095
1270
2165
1020
947
1940
915
786
1625
765
634
.50
125
2225
1050
1235
2090
985
914
1895
895
763
1610
760
622
.60
150
2130
1005
1205
2000
945
880
1840
870
740
1570
740
603
.70
175
2030
955
1155
1915
905
851
1760
830
709
1535
725
590
.80
200
1925
910
1123
1820
860
823
1670
790
681
1475
695
566
.90
225
1795
845
1078
1690
795
788
1560
735
655
1395
660
537
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60C−110 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accom-
modate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2430
1145
1309
2245
1060
1006
1910
900
843
1635
770
686
.10
25
2355
1110
1277
2190
1035
978
1905
900
817
1620
765
677
.20
50
2280
1075
1242
2140
1010
950
1885
890
797
1610
760
667
.30
75
2205
1040
1218
2075
980
924
1860
875
782
1605
755
655
.40
100
2130
1005
1189
2005
945
905
1815
855
752
1595
750
636
.50
125
2045
965
1159
1920
905
864
1750
825
726
1565
740
619
.60
150
1955
920
1132
1850
875
840
1700
800
705
1525
720
605
.70
175
1860
875
1105
1760
830
817
1610
760
674
1475
700
582
.80
200
1755
830
1067
1670
790
789
1540
725
654
1395
660
560
.90
225
1645
775
1033
1575
745
763
1445
680
627
1325
625
540
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60D−135−1, −2, −3 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return
Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
2465
1165
1205
2325
1100
1060
2155
1015
930
1895
895
780
0.05
12
2430
1145
1195
2295
1085
1050
2125
1000
920
1875
885
770
0.10
25
2395
1130
1180
2265
1070
1040
2095
990
910
1855
875
765
0.15
37
2350
1110
1165
2230
1050
1025
2070
975
900
1830
865
755
0.20
50
2310
1090
1150
2195
1035
1010
2045
965
890
1805
850
745
0.25
62
2265
1070
1135
2155
1015
995
2010
950
875
1785
840
735
0.30
75
2220
1050
1120
2115
1000
980
1975
930
865
1765
830
730
0.40
100
2120
1000
1080
2035
960
950
1915
905
845
1715
810
720
0.50
125
2050
970
1055
1955
925
925
1830
865
815
1645
775
700
0.60
150
1930
910
1015
1860
880
895
1745
825
795
1585
745
680
0.70
175
1835
865
985
1775
840
870
1655
780
770
1530
720
670
0.80
200
1720
810
955
1645
775
830
1560
735
745
1445
685
650
0.90
225
1595
755
925
1535
725
800
1455
685
720
1310
620
620
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.