Page 61
It is normal for the
electrode to protrude
at an unusual angle
GAP
0.115"
+0.000"
−0.010"
APPROX. 45
°
ELECTRICAL TESTING
CHECKING FOR OPEN SWITCH
CHECKING VOLTAGE AT PURGE BLOWER
CHECKING FOR OPEN SWITCH
IN LIMIT CONTROL
SPARK PLUG
AIR INTAKE CHAMBER
TO FLUE
DIFFERENTIAL
PRESSURE SWITCH
R x 1
READ 0 OHMS
FOR CONTINUITY
AIR
INTAKE
4
CERAMIC
RESISTOR
TYPE
NOTE− CARBON RESISTOR TYPE
PLUGS
SHOULD NOT BE USED.
10
1
2
3
4
5
6
WIRING
HARNESS
120VAC?
120VAC?
8
9
AIR INTAKE CHAMBER
R x 1
READ 0 OHMS
FOR
CONTINUITY
AIR
INTAKE
5
PRIMARY
LIMIT CONTROL
TRACE LIMIT WIRE TO
CONTROL BOX. WIRE NUT
CONNECTION FOR METER
LEAD TEST POINT.
ORANGE
LIMIT
WIRES
PURGE BLOWER
WHITE (NEUTRAL)
RED*
*NOTE−RED WIRE GOES
TO PRIMARY CONTROL
HARNESS JP72−5.
PRIMARY CONTROL
WIRING HARNESS PLUG
(JP72)
CHAMPION FI21500
or equivalent only
TO FLUE
CHECK VOLTAGE AT TERMINAL AND
CHECKING THERMOSTAT DEMAND
CHECKING VOLTAGE AT GAS VALVE
24VAC DURING
IGNITION TRIALS?
GAS VALVE
3
LOW VOLTAGE TERMINAL STRIP WITH 3 AMP FUSE
LOCATED ON CONTROL BOX
1
2
24VAC
WITH DEMAND?
24VAC
POWER?
W1
W2
G
Y1
Y2
DS
C
R
NM
CHECKING VOLTAGE AT PRIMARY CONTROL
1
2
3
4
5
6
LOW VOLTAGE TERMINAL
STRIP WITH 3 AMP FUSE
LOCATED ON CONTROL BOX
24VAC?
24VAC?
6
7
PRIMARY CONTROL
WIRING HARNESS PLUG (JP1)
W1
W2
G
Y1
Y2
DS
C
R
NM
MANUAL−RESET
SECONDARY LIMIT*
REVERSE FLOW
APPLICATION ONLY
*Secondary limit on CGA
units may be
manual−reset or
auto−reset.
Содержание G21Q3-80