Page 33
CBX40UHV
UNIT SEQUENCE OF OPERATIONS
Table 9. CBX40UV with ComfortSense
®
7000 Thermostat and Single-Stage Outdoor Unit Operating Sequence
Operating Sequence
System Demand
System Response
System
Condition
Step
Thermostat Demand
Relative Humidity
Comp
Air
Handler
CFM
(COOL)
Comments
Y1
Y2
O
G
W1
W2
Status
D
NO CALL FOR DEHUMIDIFICATION
Normal
Operation
1
On
On
On
Acceptable
24 VAC
High
100%
Compressor and indoor
air handler follow
thermostat demand
BASIC MODE (Only active on a Y1 thermostat demand)
Normal
Operation
1
On
On
On
Acceptable
24 VAC
High
100%
ComfortSense 7000 ther
mostat energizes Y1 and
de-energizes D on a call
for dehumidification.
Note: No over cooling.
Dehumidification
Call
2
On
On
On
Demand
0 VAC
High
70%
PRECISION MODE (Operates independent of a Y1 thermostat demand)
Normal
Operation
1
On
On
On
Acceptable
24 VAC
High
100%
Dehumidification mode
begins when humidity is
greater than set point
Dehumidification
call
2
On
On
On
Demand
0 VAC
High
70%
Dehumidification
call ONLY
1
On
On
On
Demand
0 VAC
High
70%
ComfortSense 7000 will
keep outdoor unit
energized after cooling
temperature setpoint has
been reach in order to
maintain room humidity
setpoint.
Note: Allow to over cool
2
0
F from cooling set
point.