IOM / @DNOVA_THS-0508
9
Refrigerant connections
THIS OPERATION MUST BE CARRIED OUT BY AN EXPERT TECHNICIAN
1. Lines positioning
Connect the air conditioner to the condensing unit by using refrigerant lines in hard or soft copper.
Limit the number of preshaped bends; if this is not possible, every bend must have a
radius of at least 100mm
The gas line must be insulated
The liquid line must be kept far from heat sources; if this is not possible it has to be
insulated
If the condensing unit is placed above the evaporating unit, the last segment of the
intake tube (insulated tube) must lean towards the condensing unit.
If, on the other hand, the condensing unit is placed under the conditioner it is advisable
to create a trap on the intake tube.
The recommended sizes for the power cables and emergency line are shown in the table below:
Models
Main power supply
Cable type
Emergency
power UPS
Cable type
THI025
THI035
THI045
THI056
THI073
THI090
THI105
THI120
THI145
230V/1Ph/50Hz
2 x 6 mm2 + T x 6 mm2
48 Vdc
2 x 2,5 mm2
Unità
modello
Main power supply
Cable type
Emergency
power UPS
Cable type
THC025
THC035
THC045
THC056
THC073
230V/1Ph/50Hz
2 x 6mm2 + T x 6 mm2
48 Vdc
2 x 2,5 mm2
THC090
THC105
THC120
THC145
400V/3Ph+N/50Hz
4 x 6 mm2 + T x 6 mm2
48 Vdc
2 x 4 mm2
Evacuation and charging operations for THS-type units
This type of work must be carried out by qualified personnel only trained to do
their job in accordance with current laws and regulations