AQUA
4
–AGU-1405-E
- 14 -
7
Operating combination depending on the thermal load:
The following tables show the possible operating regimes of the AQUA
4
units at partial loads. The units are equipped with two
thermodynamic circuits and two or four compressors that combine their operations to meet the changing demands of the heating
system. For example, in heating mode, the units AQUA
4
M (2 pipe) are able to share their heating capacity with 50% heating and 50%
domestic hot water.
- AQUA M (2 pipe) units : 2 compressors / 2 thermodynamic circuits :
Summer: Cooling mode
Winter : Heating mode
o
100% Cooling
o
50% Cooling
o
100% Heating
o
50% Heating
o
100% C 50% to 100% DHW
o
50% C 50% to 100% DHW
o
50% H 50% DHW
o
100% DHW
o
50% DHW
o
100% DHW
o
50% DHW
- AQUA M (2 pipe) units: 4 compressors / 2 thermodynamic circuits :
Summer: Cooling mode
Winter : Heating mode
o
100% Cooling
o
75% Cooling
o
50% Cooling
o
25% Cooling
o
100% Heating
o
75% Heating
o
50% Heating
o
25% Heating
o
100% C 50% to 100% DHW
o
75% C 25% to 75% DHW
o
50% C 25% to 100% DHW
o
25% C 25% to 75% DHW
o
25% H 25% to 50% DHW
o
50% H 25% to 50% DHW
o
100% DHW
o
75% DHW
o
50% DHW
o
25% DHW
o
100% DHW
o
75% DHW
o
50% DHW
o
25% DHW
- AQUA P (2 pipe) units : 2 compressors / 2 thermodynamic circuits :
All the year : Summer to winter
o
100% Cooling
o
50% Cooling
o
100% C 50% to 100% Heating
o
50% C 50% to 100% Heating
o
100% Heating
o
50% Heating
Содержание AAH041
Страница 1: ...lennoxemeia com AQUA4 AAH APPLICATION GUIDE Polyvalent air cooled heat pump 50 330 kW AQUA4 AGU 1405 E...
Страница 2: ......
Страница 13: ...AQUA4 AGU 1405 E 11 Example of 2 pipe installation for Hotel and Hospital...
Страница 20: ...AQUA4 AGU 1405 E 18 Nb of compressor 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4...
Страница 45: ...AQUA4 AGU 1405 E 43 AAH PS PL MS ML 094 and 104 Box F3 AAH PS PL MS ML 124 144 164 and 194 Box F4...
Страница 46: ...AQUA4 AGU 1405 E 44 AAH PS PL MS ML 214 and 244 Box F5 AAH PS PL MS ML 274 294 and 324 Box F6...